Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 40A, plug-in module, B1-S40-SVE
Product Name |
Eaton Moeller series NZM molded case circuit breaker magnetic
|
Catalog Number |
112724
|
Model Code |
NZMB1-S40-SVE
|
EAN |
4015081122646
|
Product Length/Depth |
90 mm
|
Product Height |
201 mm
|
Product Width |
95 mm
|
Product Weight |
1.2 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC/EN 60947
IEC |
Amperage Rating |
40 A
|
Voltage rating |
440 V - 440 V
|
Circuit breaker frame type |
NZM1
|
Accessories required |
NZM1-XSVS
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Pollution degree |
3
|
Mounting Method |
Plug-in unit
Built-in device plug-in technique |
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Equipment heat dissipation, current-dependent |
10.66 W
|
Utilization category |
A (IEC/EN 60947-2)
|
Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
40 °C
|
Protection against direct contact |
Finger and back-of-hand proof to VDE 0106 part 100
|
Rated insulation voltage (Ui) |
690 V
|
Rated operating power at AC-3, 230 V |
11 kW
|
Rated operating power at AC-3, 400 V |
18.5 kW
|
Switch off technique |
Magnetic
|
Degree of protection |
IP20 (basic degree of protection, in the operating controls area)
IP20 |
Direction of incoming supply |
As required
|
Electrical connection type of main circuit |
Other
|
Lifespan, mechanical |
20000 operations
|
Overvoltage category |
III
|
Rated operational current |
36 A (400 V AC-3)
|
Degree of protection (IP), front side |
IP66 (with door coupling rotary handle)
IP40 (with insulating surround) |
Degree of protection (terminations) |
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and strip terminal) |
Number of poles |
Three-pole
|
Terminal capacity (copper strip) |
Max. 9 segments of 9 mm x 0.8 mm at box terminal
Min. 2 segments of 9 mm x 0.8 mm at box terminal |
Lifespan, electrical |
7500 operations at 415 V AC-1
7500 operations at 400 V AC-1 |
Functions |
Short-circuit protection
|
Type |
Circuit breaker
|
Special features |
|
Application |
Use in unearthed supply systems at 440 V
|
Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
Rated operational current for specified heat dissipation (In) |
40 A
|
Short-circuit release non-delayed setting - max |
560 A
|
Short-circuit release non-delayed setting - min |
320 A
|
Handle type |
Rocker lever
|
Instantaneous current setting (Ii) - max |
14 A
|
Instantaneous current setting (Ii) - min |
8 A
|
Number of operations per hour - max |
120
|
Overload current setting (Ir) - max |
0 A
|
Overload current setting (Ir) - min |
0 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
30 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
18.5 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
18.5 kA
|
Standard terminals |
Box terminal
|
Optional terminals |
Connection on rear. Screw terminal. Tunnel terminal
|
Release system |
Thermomagnetic release
|
Short-circuit total breaktime |
< 10 ms
|
Terminal capacity (aluminum solid conductor/cable) |
16 mm² (1x) at tunnel terminal
10 mm² - 16 mm² (1x) direct at switch rear-side connection 10 mm² - 16 mm² (2x) direct at switch rear-side connection |
Terminal capacity (aluminum stranded conductor/cable) |
25 mm² - 35 mm² (2x) direct at switch rear-side connection
25 mm² - 95 mm² (1x) at tunnel terminal 25 mm² - 35 mm² (1x) direct at switch rear-side connection |
Terminal capacity (control cable) |
0.75 mm² - 1.5 mm² (2x)
0.75 mm² - 2.5 mm² (1x) |
Terminal capacity (copper busbar) |
Min. 12 mm x 5 mm direct at switch rear-side connection
Max. 16 mm x 5 mm direct at switch rear-side connection M6 at rear-side screw connection |
Terminal capacity (copper solid conductor/cable) |
6 mm² - 16 mm² (2x) at box terminal
10 mm² - 16 mm² (1x) direct at switch rear-side connection 10 mm² - 16 mm² (1x) at box terminal 16 mm² (1x) at tunnel terminal 6 mm² - 16 mm² (2x) direct at switch rear-side connection |
Terminal capacity (copper stranded conductor/cable) |
6 mm² - 25 mm² (2x) at box terminal
10 mm² - 70 mm² (1x) at box terminal 25 mm² (2x) direct at switch rear-side connection 25 mm² - 95 mm² (1x) at 1-hole tunnel terminal 10 mm² - 70 mm² (1x) direct at switch rear-side connection |
Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 400/415 V, 50/60 Hz |
18.5 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
53 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
53 kA
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
63 kA
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
6000 V
|
Power loss |
2.7 W
|