Télécharger le document () de 20

100514
Model Code: NZM3-XKV70

Eaton Moeller series NZM - Molded Case Circuit Breaker. Connection width extension 3p, size 3

Spécifications générales

Product Name
Eaton Moeller series NZM connection type
Catalog Number
100514
EAN
4015081004980
Product Length/Depth
6 mm
Product Height
80 mm
Product Width
188 mm
Product Weight
0.75 kg
Compliances
IEC
UL/CSA
RoHS conform
Certifications
CSA (Class No. 1432-01)
CSA certified
UL (File No. E140305)
UL (Category Control Number DIHS)
CE marking
CSA-C22.2 No. 5-09
UL489
CSA (File No. 22086)
UL listed
IEC60947
Model Code
NZM3-XKV70

Delivery program

Type
  • Accessory
  • Connection width extension
  • Terminal
Number of poles
Three-pole
Amperage Rating
630 A
Special features
One hole
Frame
NZM3
Suitable for
Copper cable lugs
Three-pole
Used with
NZM3, PN3, N(S)3

Technical Data - Electrical

Amperage Rating
630 A

Technical Data - Mechanical

Special features
One hole

Technical Data - Mechanical - Terminals

Terminal capacity (flexible cable)
300 mm² (2x)
500 AWG/kcmil (2x)
Terminal capacity (copper busbar)
10 mm x 50 mm (2x)
Terminal capacity (copper strip)
10 segments of 50 mm x 1 mm (2x)

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Exporter les spécifications du produit

Remarque : L’absence d’un ou plusieurs fichiers dans un ficher .zip téléchargé peut être causée par l’absence de prise en charge du type de fichier pour un téléchargement groupé.