Eaton Moeller® series ES4P Safety relay, 24 V DC, 14DI, 4DO-Trans, 1DO relay, display, easyNet ES4P-221-DMXX1
| Product Name |
Eaton Moeller® series ES4P Safety relay
|
| Catalog Number |
111016
|
| EAN |
4015081105267
|
| Product Length/Depth |
72 mm
|
| Product Height |
90 mm
|
| Product Width |
108 mm
|
| Product Weight |
0.324 kg
|
| Compliances |
CE Marked
|
| Certifications |
UL Listed
EN Listed CSA Certified CE EN ISO 13849-1 EN 50156-1 EN 50581 IEC/EN 61000-4-2 CSA CSA-C22.20.4-04 IEC 61508 UL Category Control No.: NRAQ UL File No.: CSA report applies to both US and Canada CSA File No.: 012528 IEC/EN 61000-6-2 UL 508 CSA-22.2 No. 142-MI1987 EN 50156-2 EN 50178 IEC/EN 61000-6-3 CSA Class No.: 2252-81; 2252-01 IEC 62061 |
| Catalog Notes |
1000
|
| Features |
Expandable
Safety/standard circuit diagram |
| Fitted with: |
Timer
Real time clock Relay output Expandable standard inputs/outputs Expandable standard bus systems |
| Functions |
Redundancy
Thermal cutout |
| Inscription |
Individual laser inscriptions possible
|
| Accuracy |
± 5 s/day depending on the ambient temperature
± 2 s/day (± 0.5 h⁄year), Real-time clock, normally |
| Cable length |
1000 m, shielded, Single cable length of test signal output to the device input, Digital inputs 24 V DC
3000 m, shielded, Total of single cable lengths from one test signal output to the device inputs, Digital inputs 24 V DC 50 m, unscreened, Transistor outputs 100 m, unscreened, Digital inputs 24 V DC |
| Degree of protection |
IP20
|
| Duty factor |
T0.95 ≈ 3 x T0.65 = 3 x L/R (Inductive load to EN 60947-5-1, Without external suppressor circuit)
T0.95 = Time in ms, until 95 % of the steady-state current has been reached (Inductive load to EN 60947-5-1, Without external suppressor circuit) 100 % (Inductive load to EN 60947-5-1, With external suppressor circuit) |
| Insulation resistance |
According to EN 50178
|
| Lifespan, mechanical |
10,000,000 Operations
10,000,000 Operations (Relay outputs) |
| Mounting method |
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Top-hat rail fixing (according to IEC/EN 60715, 35 mm) Rail mounting possible Wall mounting/direct mounting |
| Mounting width |
107.5 mm
|
| Operating frequency |
Resistive load < 100 kΩ, depending on program and load
900 Operations/h at input (does not apply to I1, I2, if function block SM or OM is used) 13500 Operations/h at resistive load |
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Product category |
Control relays for safety applications
|
| Rated impulse withstand voltage (Uimp) |
6 kV (contact-coil)
|
| Residual ripple |
5 % (transistor outputs)
≤ 5 % |
| Resolution |
|
| Suitable for |
Safety functions
|
| Switching capacity |
AC: R300 (in accordance with UL 508), Relay outputs
AC-15, 230 V AC, 3 A: 80000 operations (in accordance with IEC 60947-5-1), Relay outputs DC: B300 (in accordance with UL 508), Relay outputs DC-13, 24 V DC, 0.1 Hz: 40000 operations (in accordance with IEC 60947-5-1), Relay outputs |
| Switching frequency |
15 Hz, Relay outputs
0.5 Hz, Transistor outputs, Inductive load to EN 60947-5-1, with external suppressor circuit, Max. switching frequency, max. duty factor = 50% |
| Type |
easy800 with safety function blocks
|
| Voltage type |
DC
|
| Constant acceleration |
2 g, 57 - 150 Hz
|
| Constant amplitude |
0,15 mm, 10 - 57 Hz, according to IEC/EN 60068-2-6, Vibrations
|
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
| Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Vibration resistance |
3.5 mm / 1 g, According to IEC/EN 60068-2-6
|
| Air pressure |
795 - 1080 hPa (operation)
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
55 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
70 °C
|
| Environmental conditions |
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 142, EN 60664-1:2003 |
| Relative humidity |
5 - 95 % (non-condensing, IEC 60068-2-30, IEC 60068-2-78)
|
| Air discharge |
15 kV
|
| Burst impulse |
4 kV, Supply cable
According to IEC/EN 61000-4-4 4 kV, Signal cable |
| Contact discharge |
8 kV
|
| Electromagnetic compatibility |
Increased EMC requirements for safety-relevant functions (according to ICE 62061)
|
| Electromagnetic fields |
30 V/m (according to IEC EN 61000-4-3)
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3) 10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
| Immunity to line-conducted interference |
20 V (according to IEC/EN 61000-4-6)
|
| Radio interference class |
Class B (EN 55022)
Class B (EN 55011) |
| Surge rating |
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
4 kV, semi-conductor outputs, symmetrical, power pulses (Surge), EMC 2 kV, Supply cables, symmetrical, power pulses (Surge), EMC |
| Voltage dips |
≤ 10 ms
According to EN 61131-2 |
| Terminal capacity |
0.2 - 4 mm² (AWG 22 - 12), solid
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule |
| Tightening torque |
0.6 Nm, Screw terminals
|
| Screwdriver size |
3.5 x 0.8 mm, Terminal screw
|
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
6 A
|
| Input current |
< 250 mA (at 115/230 V AC)
5.7 mA (Digital inputs, at 24 V DC, at signal 1, I1 - I6) |
| Output voltage |
24 V DC (test signal outputs)
U = Uₑ - 1 V (signal 1 at Iₑ = 0.5 A, transistor outputs) Output Voltage@≤ 2.4 V (at signal 0 at external load < 10 MΩ, transistor outputs) |
| Peak short-circuit current |
16 A
|
| Rated control supply voltage |
24 V DC (Us)
|
| Rated insulation voltage (Ui) |
250 V
|
| Rated operational current (Ie) |
Max. 0.5 A at signal „1” DC per channel
|
| Rated operational voltage |
250 V AC
20.4 - 28.8 V DC 24 V DC (transistor outputs) 20.4 - 28.8 V DC (Transistor outputs) 24 V DC (digital inputs) 24 V DC (-15 %/+ 20 % - power supply) < 5 V DC on 0 signal > 15 V DC on 1 signal |
| Short-circuit current |
8 A, Transistor outputs
|
| Short-circuit protection |
Yes, Transistor outputs
≤ 8 A, Back-up fuse, Transistor outputs |
| Short-circuit tripping current |
0.7 ≤ Ie ≤ 2 per output, For Ra ≤ 10 mΩ, Transistor outputs
|
| Supply current |
60/100 mA, Normally⁄max., On 1 signal, Transistor outputs
50/50 mA, Normally⁄max., On 0 signal, Transistor outputs |
| Supply voltage at AC, 50 Hz - min |
0 VAC
|
| Supply voltage at AC, 50 Hz - max |
0 VAC
|
| Supply voltage at DC - min |
20.4 VDC
|
| Supply voltage at DC - max |
28.8 VDC
|
| Bus termination |
First and last station, easyNet
|
| Data transfer rate |
20 kBit/s, 700 m, easyNet
1000 kBit/s, 6 m, easyNet 10 kBit/s, 1000 m, easyNet 500 kBit/s, 25 m, easyNet 50 kBit/s, 300 m, easyNet 250 kBit/s, 40 m, easyNet 125 kBit/s, 125 m, easyNet |
| Memory |
100,000,000,000,000 Write cycles of the retentive memory
|
| Module interface |
easyNet/easyLink
|
| Number of modules |
Max. 8
|
| Protocol |
Other bus systems
|
| Capacitive load |
0.6 µF max., Transistor outputs
|
| Lamp load |
5 W (without Rv per channel)
|
| Number of inputs (analog) |
0
|
| Number of inputs (digital) |
14
|
| Number of outputs (analog) |
4
|
| Number of outputs (digital) |
5
|
| Off-delay |
< 1 ms
|
| Output |
4 Test signal outputs (T1 - T4)
4 Transistor Outputs Relay outputs in groups of 1 |
| Parallel switching |
Not permitted
|
| Pulse characteristics |
1 ms (max. duration of external test pulse)
1 ms (Off test pulse) |
| Utilization factor |
1 (Inductive load to EN 60947-5-1, With external suppressor circuit)
|
| Explosion safety category for dust |
None
|
| Explosion safety category for gas |
None
|
| Potential isolation |
Between easyNet and Power supply: yes
Between Digital inputs 24 V DC and easyNet: yes Between Transistor outputs and easyLink: yes Between Relay outputs and easyNet: yes Between Relay outputs and Power supply: yes Between Transistor output and interface: yes Between Digital inputs 24 V DC and Outputs: yes Between easyNet and Outputs: yes Between Power supply and easyNet: yes Between Relay outputs and Digital inputs: yes Between Inputs and internal Power supply: Yes Between Power supply and Inputs: yes Between Relay outputs and Inputs: yes Between easyNet and Inputs: yes Between easyNet and PC interface: yes Basic isolation: 600 V AC (Relay outputs) Between Relay outputs and Interface: yes Between easyNet and Memory card: yes Safe isolation according to EN 50178: 300 V AC (Relay outputs) Between Power supply and Outputs: yes |
| Protection |
|
| Protection against polarity reversal |
Yes
|
| Safe isolation |
Between coil and contacts in accordance with EN 50178
300 V AC, Between coil and contacts, According to EN 50178 |
| Safety function/level |
Enabling switch
Two-hand control Protective door OSSD input 3 redundant relay outputs, 6 months test interval Stopping in the event of an emergency Zero speed monitoring Highest speed monitoring Safety timing relay Mode selection Feedback circuit According to EN 50156 ESPE with muting function |
| Safety parameter (EN ISO 13849-1) |
Cat. 4, Category
PL e, Performance level |
| Safety parameter (IEC 62061) |
SILCL 3, Safety integrity level claim limit
23 x 10-10, PFHd, Probability of failure per hour SIL 3, Safety integrity level, In accordance with IEC 61508 |
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
6 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|