Eaton Moeller series Power Defense - Molded Case Circuit Breaker. Circuit-breaker LZM, 4 p, 20A, C1-4-A20-I
Product Name |
Eaton Moeller series Power Defense molded case circuit-breaker
|
Catalog Number |
111908
|
EAN |
4015081114566
|
Product Length/Depth |
88 mm
|
Product Height |
145 mm
|
Product Width |
120 mm
|
Product Weight |
1.324 kg
|
Compliances |
RoHS conform
|
Certifications |
VDE 0660
IEC/EN 60947 IEC |
Circuit breaker frame type |
LZM1
|
Application |
Use in unearthed supply systems at 690 V
|
Amperage Rating |
20 A
|
Number of poles |
Four-pole
|
Voltage rating |
690 V - 690 V
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
6000 V
|
Rated operational current |
20 A (660-690 V AC-3, making and breaking capacity)
20 A (415 V AC-3, making and breaking capacity) 160 A (690 V AC-1, making and breaking capacity) 125 A (415 V AC-1, making and breaking capacity) 160 A (380/400 V AC-1, making and breaking capacity) |
Current rating of neutral conductor |
200% of phase conductor
|
Instantaneous current setting (Ii) - min |
350 A
|
Instantaneous current setting (Ii) - max |
350 A
|
Overload current setting (Ir) |
15 A - 20 A
|
Overload current setting (Ir) - min |
15 A
|
Overload current setting (Ir) - max |
20 A
|
Short delay current setting (Isd) - min |
0 A
|
Short delay current setting (Isd) - max |
0 A
|
Short-circuit release non-delayed setting - min |
350 A
|
Short-circuit release non-delayed setting - max |
350 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
55 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
36 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
22.5 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz |
6 kA
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
121 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
76 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
63 kA
|
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz |
24 kA
|
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz |
14 kA
|
Short-circuit total breaktime |
< 10 ms
|
Electrical connection type of main circuit |
Frame clamp
|
Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
Overvoltage category |
III
|
Utilization category |
A (IEC/EN 60947-2)
|
Pollution degree |
3
|
Lifespan, electrical |
10000 operations at 415 V AC-1
10000 operations at 400 V AC-1 7500 operations at 415 V AC-3 7500 operations at 690 V AC-1 |
Type |
Circuit breaker
|
Release system |
Thermomagnetic release
|
Mounting Method |
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional Fixed |
Degree of protection |
In the area of the HMI devices: IP20 (basic protection type)
IP20 |
Degree of protection (IP), front side |
IP40 (with insulating surround)
IP66 (with door coupling rotary handle) |
Degree of protection (terminations) |
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and band terminal) |
Protection against direct contact |
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
|
Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Number of operations per hour - max |
120
|
Handle type |
Rocker lever
|
Position of connection for main current circuit |
Front side
|
Direction of incoming supply |
As required
|
Standard terminals |
Box terminal
|
Terminal capacity (copper busbar) |
M8 at rear-side screw connection
|
Terminal capacity (copper solid conductor/cable) |
16 mm² - 95 mm² (1x) at tunnel terminal
|
Terminal capacity (copper stranded conductor/cable) |
25 mm² - 70 mm² (1x) at box terminal
25 mm² (2x) at box terminal |
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Lifespan, mechanical |
20000 operations
|
Rated operational current for specified heat dissipation (In) |
20 A
|
Equipment heat dissipation, current-dependent |
9.82 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
Features |
Protection unit
|
Functions |
System and cable protection
|
Special features |
|