Eaton XN Digital input card XI/ON, 24 VDC, 4DI, negative switching
Product Name |
Eaton XN Accessory Input card
|
Catalog Number |
140059
|
EAN |
7640130120297
|
Product Length/Depth |
55.4 mm
|
Product Height |
74.1 mm
|
Product Width |
12.6 mm
|
Product Weight |
0.03 kg
|
Certifications |
UL Category Control No.: NRAQ, NRAQ7
UL File No.: E205091 UL Recognized IEC/EN 61000-6-2 UL 508 UL report applies to both US and Canada CSA Class No.: 2252-01, 2252-81 CSA-C22.2 No. 142 cULus IEC/EN 61000-6-4 CE IEC/EN 61131-2 Certified by UL for use in Canada IEC/EN 6113-2 |
Electric connection type |
Screw-/spring clamp connection
|
Features |
Fieldbus connection over separate bus coupler possible
|
Functions |
Negative switching
|
Current consumption |
28 mA, from module bus, Analog input modules
40 mA, from supply terminal |
Degree of protection |
IP20
|
Mounting method |
Rail mounting possible
|
Number of channels |
4
|
Product category |
XN Slice module
|
Suitable for |
Base modules without C-Connection: 4-wire
Base modules without C-Connection: 2-/3-wire |
Type |
I/O module
|
Used with |
XN-S6S-SBBSBB
XN-S4T-SBBS XN-S4S-SBBS XN-S6T-SBBSBB |
Voltage type |
DC
|
Drop and topple |
According to IEC 60068-2-31, free fall according to IEC 60068-2-32
|
Shock resistance |
Continuous according to IEC/EN 60068-2-29
Mechanical, According to IEC/EN 60068-2-27 |
Vibration resistance |
According to IEC/EN 60068-2-6
|
Ambient operating temperature - min |
0 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient storage temperature - min |
-25 °C
|
Ambient storage temperature - max |
85 °C
|
Environmental conditions |
Harmful gasses - H2S: 1 ppm (relative humidity < 75%, no condensation)
Harmful gasses - SO2: 10 ppm (relative humidity < 75%, no condensation) |
Relative humidity |
5 - 95 % (indoor, Level RH-2, non-condensing for storage at 45°C)
|
Air discharge |
According to EN 61100-4-2
|
Burst impulse |
According to IEC/EN 61000-4-4
|
Contact discharge |
According to EN 61100-4-2
|
Electromagnetic fields |
According to IEC EN 61100-4-2
|
Emitted interference |
30 - 230 MHz (radiated, high frequency, according to EN 55016-2-3)
230 - 1000 MHz (radiated, high frequency, according to EN 55016-2-3) |
Radiated RFI |
IEC/EN 61100-4-6
|
Surge rating |
According to IEC/EN 61000-4-5 Level 4
|
Voltage dips |
According to EN 61131-2 (Voltage fluctuations/voltage dips)
|
Rated insulation voltage (Ui) |
500 V
|
Rated operational voltage |
24 V DC (supply terminal)
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at DC - min |
18 VDC
|
Supply voltage at DC - max |
30 VDC
|
Protocol |
Other bus systems
|
Input current |
1.3 - 6 mA (Digital inputs, high level)
0 - 1.2 mA (Digital inputs, low level) |
Input current at signal 1 |
1.3 mA
|
Input delay |
200 µs (falling edge)
200 µs (rising edge) |
Input voltage |
24 V DC (Digital inputs)
0 - 5 V (Digital inputs, high level) -30 - (UL - 11 V) (Digital inputs, low level) |
Number of inputs (digital) |
4
|
Number of outputs (digital) |
0
|
Output current |
0 A
|
Explosion safety category for dust |
None
|
Explosion safety category for gas |
None
|
Potential isolation |
Through optocoupler: yes
|
Equipment heat dissipation, current-dependent Pvid |
1 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
1 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|