Eaton EU5E SWD I/O module, 2 analog inputs, 2 analog outputs, parameterizable 0-10V/0-20mA
Product Name |
Eaton EU5E I/O module
|
Catalog Number |
144063
|
EAN |
4015081405930
|
Product Length/Depth |
102 mm
|
Product Height |
90 mm
|
Product Width |
35 mm
|
Product Weight |
0.09 kg
|
Certifications |
UL Category Control No.: NKCR
IEC/EN 61131-2 UL CSA UL File No.: E29184 CSA Class No.: 3211-07 CSA File No.: 2324643 |
Catalog Notes |
alog outputs 0?10V or 0?20 mA
|
Type |
|
Features |
Output, current
Fieldbus connection over separate bus coupler possible Input, current Analog outputs configurable Output signal configurable Input, voltage Output, voltage Analog inputs configurable |
Air discharge |
8 kV, according to IEC 61131-2, level 3, ESD
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Electric connection type |
Flat plug-in connection
|
Pollution degree |
2
|
Burst impulse |
2 kV, Signal cable, according to IEC/EN 61131-2, Level 3
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3 2 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3 |
Resolution |
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2 |
Connection to SmartWire-DT |
Yes
|
Air pressure |
795 - 1080 hPa (operation)
|
Explosion safety category for dust |
None
|
Operating temperature - max |
55 °C
|
Operating temperature - min |
-25 °C
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Resolution of the analog inputs |
12 Bit
|
Resolution of the analog outputs |
12 Bit
|
Static heat dissipation, non-current-dependent Pvs |
1.5 W
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 60 Hz - max |
0 VAC
|
Supply voltage at AC, 60 Hz - min |
0 VAC
|
Supply voltage at DC - max |
0 VDC
|
Supply voltage at DC - min |
0 VDC
|
Product category |
SmartWire-DT slave
|
Power consumption |
1.5 W
|
Environmental conditions |
Condensation: prevent with appropriate measures
|
Input |
Current
Inputs configurable (0 - 10 V, 0 - 20 mA) Voltage |
Output voltage |
0 - 10 V (analog outputs)
|
Explosion safety category for gas |
None
|
Output current |
0 - 20 mA, Analog outputs
Max. 10 mA |
Mounting method |
Wall mounting/direct mounting
Top-hat rail fixing (according to IEC/EN 60715, 35 mm) Rail mounting possible |
Current consumption |
22 mA, SmartWire-DT network
|
Voltage type |
DC
|
Mounting position |
As required
|
Output |
Outputs configurable (0 - 10 V, 0 - 20 mA)
|
Input voltage |
0 - 10 V (Analog inputs)
|
Contact discharge |
4 kV, according to IEC/EN 61131-2, Level 2, ESD
|
Overvoltage category |
II
|
Dielectric strength |
30 kV/mm, according to IEC 60243-1
|
Constant acceleration |
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
|
Constant amplitude |
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
|
Surge rating |
1 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC |
Potential isolation |
Inputs for SmartWire-DT: yes
Outputs to SmartWire-DT: yes |
Power loss |
1.5 W
|
Conversions |
20 ms, Analog inputs
20 ms, Analog outputs |
Electromagnetic fields |
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008) 3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008) |
Protection against polarity reversal |
Yes
Yes, for supply voltage (Siemens MPI optional) |
Number of inputs (analog) |
2
|
Radiated RFI |
10 V (IEC/EN 61131-2:2008, Level 3)
|
Load resistance |
< 500 Ω
|
Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
Protocol |
Other bus systems
|
Radio interference class |
Class B (EN 55011)
|
Relative humidity |
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
|
Connection type |
Plug, 8-pole, SmartWire-DT
Push in terminals, Supply and I/O sensor Connection plug: external device plug SWD4-8SF2-5, SmartWire-DT |
Residual ripple |
≤ 5 % (input voltage)
|
Repetition accuracy |
0.5 % (Analog inputs)
0.5 % (Analog outputs) |
Rated operational voltage |
24 V DC (-15 %/+ 20 % - power supply)
|
Data transfer rate |
Setting automatically
250 kBit/s, SmartWire-DT |
Degree of protection |
IP20
NEMA 1 |
Station |
SmartWire-DT slave, SmartWire-DT network
|
Input impedance |
< 250 Ω
|
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
Short-circuit protection |
Yes, Short-circuit proof, Analog outputs
|
Functions |
Adjustable parameter settings
For connection of analog I/O signals |
System accessory |
Yes
|
Input current |
0 - 20 mA (Analog inputs)
|
Terminal capacity |
0.25 - 1.5 mm² (24 - 16 AWG), flexible with ferrule, Terminal for I/O sensor
0.2 - 1.5 mm² (AWG 24 - 16), solid, Terminal for I/O sensor |
Total error |
± 1 %, Outputs
± 1 %, Inputs |
LED indicator |
Status indication of SmartWire-DT network: Green LED
|
Safety performance level (EN ISO 13849-1) |
None
|
SIL (IEC 61508) |
None
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
0
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of HW-interfaces (wireless) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|