Eaton DA1 Variable frequency drive, 230 V AC, 1-phase, 4.3 A, 0.75 kW, IP20/NEMA 0, Radio interference suppression filter, 7-digital display assembly
Product Name |
Eaton DA1 Variable frequency drive
|
Catalog Number |
169078
|
EAN |
4015081655656
|
Product Length/Depth |
186 mm
|
Product Height |
231 mm
|
Product Width |
107 mm
|
Product Weight |
1.8 kg
|
Certifications |
IEC/EN61800-5
UL Category Control No.: NMMS, NMMS7 EAC Specification for general requirements: IEC/EN 61800-2 RoHS, ISO 9001 UL File No.: E172143 UL 508C RCM UkrSEPRO Certified by UL for use in Canada IEC/EN 61800-3 UL report applies to both US and Canada Safety: EN 61800-5-1: 2003 IEC/EN61800-3 CUL CE CSA-C22.2 No. 14 UL |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Cable length |
150 m, unscreened, maximum permissible, Motor feeder
C1 ≤ 1 m, Radio interference level, maximum motor cable length C2 ≤ 5 m, Radio interference level, maximum motor cable length C3 ≤ 25 m, Radio interference level, maximum motor cable length 100 m, screened, maximum permissible, Motor feeder 200 m, screened, with motor choke, maximum permissible, Motor feeder 300 m, unscreened, with motor choke, maximum permissible, Motor feeder |
Communication interface |
CANopen®, built in
Ethernet IP, optional DeviceNet, optional PROFIBUS, optional OP-Bus (RS485), built in Modbus-TCP, optional SmartWire-DT, optional EtherCAT, optional Modbus RTU, built in PROFINET, optional |
Connection to SmartWire-DT |
Yes
In conjunction with DX-NET-SWD1 SmartWire DT module |
Degree of protection |
IP20
NEMA Other |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Fitted with: |
PC connection
Breaking resistance Control unit Brake chopper 7-digital display assembly Radio interference suppression filter Internal DC link Additional PCB protection IGBT inverter |
Frame size |
FS2
|
Functions |
4-quadrant operation possible
|
Mounting position |
Vertical
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
PROFIBUS
PROFINET IO EtherNet/IP CAN Other bus systems MODBUS DeviceNet TCP/IP |
Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
Suitable for |
Branch circuits, (UL/CSA)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: for conducted emissions only Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Ambient operating temperature - min |
-10 °C
|
Altitude |
Max. 1000 m
Max. 4000 m Above 1000 m with 1 % derating per 100 m |
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
93.9 % (η)
|
Heat dissipation at current/speed |
34 W at 25% current and 0% speed
35 W at 25% current and 50% speed 38 W at 50% current and 0% speed 38 W at 50% current and 50% speed 42 W at 100% current and 0% speed 42 W at 50% current and 90% speed 53 W at 100% current and 50% speed 64 W at 100% current and 90% speed |
Input current ILN at 150% overload |
8.6 A
|
Leakage current at ground IPE - max |
2.49 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
200 V
|
Mains voltage - max |
240 V
|
Operating mode |
U/f control
Sensorless vector control (SLV) Speed control with slip compensation Optional: Vector control with feedback (CLV) |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
240 V AC, 3-phase
230 V AC, 3-phase |
Overload current IL at 150% overload |
6.45 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) at 150% overload |
4.3 A
|
Rated operational power at 220/230 V, 50 Hz, 1-phase |
0.75 kW
|
Rated operational voltage |
230 V AC, 1-phase
240 V AC, 1-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
16 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), for 4 seconds every 40 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
16 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
240 VAC
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
4.2 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
3.2 A
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
1 HP
|
Apparent power at 230 V |
1.71 kVA
|
Apparent power at 240 V |
1.79 kVA
|
Braking resistance |
100 Ω
|
Braking torque |
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Switch-on threshold for the braking transistor |
390 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
5
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
2
|
Number of relay outputs |
2 (parameterizable, 1 N/O and 1 changeover contact, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA)
|
Equipment heat dissipation, current-dependent Pvid |
45.75 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
4.3 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|