Eaton Moeller® series DILDC DC contactor, 2 N/O, 2 NC, 1000 V: 600 A, RDS 250: 110 - 250 V 40 - 60 Hz/110 - 350 V DC, AC and DC operation
Product Name |
Eaton Moeller® series DILDC DC Contactor
|
Catalog Number |
183315
|
EAN |
4015081782505
|
Product Length/Depth |
248 mm
|
Product Height |
219 mm
|
Product Width |
160 mm
|
Product Weight |
7.5 kg
|
Certifications |
UL Category Control No.: NRNT
UL CSA CSA Class No.: C321124 UL508 IEC/EN 60947-5-1 CSA File No.: 012528 UL File No.: E338590 IEC/EN 60947-4-1 CE CSA-C22.2 No. 14-05 |
Catalog Notes |
DILDC contactors feature an electronic arc suppression system. Because of this, it is important not to exceed any technical data limits in general – especially the making and breaking capacity limits. Opening the device will immediately void the warranty.
|
Accessories |
Fitting options auxiliary contacts: on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
|
Application |
DC contactor
|
Degree of protection |
IP00
|
Electromagnetic compatibility |
Designed for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression.
|
Lifespan, mechanical |
1,000,000 Operations (DC operated)
1,000,000 Operations (AC operated) |
Operating frequency |
100 electrical Operations/h
1000 mechanical Operations/h (DC operated) 1000 mechanical Operations/h (AC operated) |
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Contactors
|
Rated impulse withstand voltage (Uimp) |
8000 V DC
|
Shock resistance |
10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Signal level |
5 V - 15 V, PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2), Magnet systems
|
Voltage type |
DC
|
Ambient operating temperature - min |
-40 °C
|
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature (enclosed) - min |
-40 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Terminal capacity (busbar) |
40 mm width, Main connection
|
Terminal capacity (flexible with cable lug) |
50 - 240 mm²
|
Terminal capacity (flexible with ferrule) |
1 x (0.75 - 2.5) mm², Control circuit cales
1 x (0.75 - 2.5) mm², Control circuit cables |
Terminal capacity (solid) |
1 x (0.75 - 2.5) mm², Control circuit cales
1 x (0.75 - 2.5) mm², Control circuit cables |
Terminal capacity (solid/stranded AWG) |
1/0 - 500 MCM, Main cables
2 x (18 - 12) |
Terminal capacity (stranded with cable lug) |
50 - 240 mm²
|
Width across flats |
16 mm
|
Screw size |
M3.5, Terminal screw, Control circuit cables
M10, Terminal screw, Main connections |
Screwdriver size |
2, Terminal screw, Control circuit cables, Pozidriv screwdriver
0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver |
Tightening torque |
1.2 Nm, Screw terminals, Control circuit cables
24 Nm, Main cable connection screw/bolt |
Rated breaking capacity at 220/230 V |
900 A
|
Rated breaking capacity at 380/400 V |
900 A
|
Rated breaking capacity at 500 V |
900 A
|
Rated breaking capacity at 660/690 V |
900 A
|
Rated breaking capacity at 1000 V |
900 A
|
Rated insulation voltage (Ui) at DC |
1000 V
|
Rated making capacity (cos phi to IEC/EN 60947) |
900 A
|
Rated operational voltage (Ue) at DC - max |
1000 V
|
Rated operational current (Ie) at DC-1, 1000 V |
600 A
|
Rated operational current (Ie) at DC-3/DC-5 at 440 V |
0 A
|
Short-circuit protection rating |
Max. 900 A gR 1000 V DC (max. short-circuit current 6 kA), Fuse, Type “2” coordination, 400 V DC, Main conducting paths
Max. 900 A gR 1000 V DC (max. short-circuit current 30 kA), Fuse, Type “1” coordination, 1000 V DC, Main conducting paths Max. 900 A gR 1000 V DC (max. short-circuit current 6 kA), Fuse, Type “2” coordination, 690 V DC, Main conducting paths Max. 900 A gR 1000 V DC (max. short-circuit current 6 kA), Fuse, Type “2” coordination, 1000 V DC, Main conducting paths Max. 900 A gR 1000 V DC (max. short-circuit current 30 kA), Fuse, Type “1” coordination, 400 V DC, Main conducting paths |
Safe isolation |
1000 V, Between auxiliary contacts and main contacts, According to EN 61140
1000 V, Between control inputs and main contacts, According to EN 61140 1000 V, Between the contacts, According to EN 61140 |
Switching capacity (main contacts, general use) |
600 A, Maximum motor rating, Single-phase (UL/CSA)
|
Switching capacity (auxiliary contacts, general use) |
1 A, 250 V DC, (UL/CSA)
15 A, 600 V AC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
P300, DC operated (UL/CSA)
A600, AC operated (UL/CSA) |
Drop-out voltage |
0.2 x US max - 0.6 x US min, DC operated
AC operated: 0.2 x US max - 0.6 x US min, AC operated |
Duty factor |
100 %
|
Pick-up voltage |
0.7 - 1.15 V DC x Us
0.7 - 1.15 V AC x Us |
Power consumption, pick-up, 50 Hz |
600 VA, Pull-in power, Coil in a cold state and 1.0 x Us
550 W, Pull-in power, Coil in a cold state and 1.0 x Us |
Power consumption, pick-up, 60 Hz |
550 W, Pull-in power, Coil in a cold state and 1.0 x Us
600 VA, Pull-in power, Coil in a cold state and 1.0 x Us |
Power consumption, sealing, 50 Hz |
9.5 W, Coil in a cold state and 1.0 x Us
18 VA, Coil in a cold state and 1.0 x Us |
Power consumption, sealing, 60 Hz |
18 VA, Coil in a cold state and 1.0 x Us
9.5 W, Coil in a cold state and 1.0 x Us |
Rated control supply voltage (Us) at AC, 50 Hz - min |
110 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
250 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
110 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
250 V
|
Rated control supply voltage (Us) at DC - min |
110 V
|
Rated control supply voltage (Us) at DC - max |
350 V
|
Switching time (AC operated, make contacts, closing delay) - max |
80 ms
|
Switching time (AC operated, make contacts, opening delay) - max |
40 ms
|
Number of auxiliary contacts (normally closed contacts) |
2
|
Number of auxiliary contacts (normally open contacts) |
2
|
Number of contacts (normally closed contacts) |
2
|
Number of contacts (normally open contacts) |
2
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
72 W
|
Rated operational current for specified heat dissipation (In) |
600 A
|
Static heat dissipation, non-current-dependent Pvs |
9 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|