Download document () of 20
To be discontinued

140037

Eaton XNE Analog input card XI/ON ECO, 24 V DC, 8AI(voltage, current)/4(PT, ni, R)

General specifications

Product Name
Eaton XNE Accessory Input card
Catalog Number
140037
EAN
7640130095311
Product Length/Depth
161.5 mm
Product Height
74.5 mm
Product Width
13 mm
Product Weight
0.064 kg
Certifications
IEC/EN 61131-2
CE
Rated data for terminations according to IEC/EN 60947-7-1
IEC/EN 61000-6-4
IEC/EN 6113-2
cULus
IEC/EN 61000-6-2

Features & Functions

Electric connection type
Plug-in connection
Features
Analog outputs configurable
Input, voltage
Input, resistor
Fieldbus connection over separate bus coupler possible
Input signal, configurable
Input, current
Analog inputs configurable
Input, resistance thermometer
Fitted with:
Connectable nickel sensors: Ni100, Ni1000 (according to DIN 43760)
Connectable platinum sensors: Pt100, Pt500, Pt1000 (according to DIN IEC 751)
Functions
Diagnosis function

General

Current consumption
30 mA, from module bus, Analog input modules
35 mA, from supply terminal
Degree of protection
IP20
NEMA 1
Limit frequency
1.5 Hz (- 3 db)
Mounting method
Rail mounting possible
Number of channels
8 (U/I)
Product category
XNE Slice module
Type
XI/ON I/O module
Voltage type
DC

Ambient conditions, mechanical

Drop and topple
According to IEC 60068-2-31, free fall according to IEC 60068-2-32
Shock resistance
Continuous according to IEC/EN 60068-2-29
Mechanical, According to IEC/EN 60068-2-27
Vibration resistance
According to IEC/EN 60068-2-6

Climatic environmental conditions

Ambient operating temperature - min
0 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-25 °C
Ambient storage temperature - max
85 °C
Environmental conditions
Harmful gasses - SO2: 10 ppm (relative humidity < 75%, no condensation)
Harmful gasses - H2S: 1 ppm (relative humidity < 75%, no condensation)
Relative humidity
5 - 95 % (indoor, Level RH-2, non-condensing for storage at 45°C)

Electro magnetic compatibility

Air discharge
According to EN 61100-4-2
Burst impulse
According to IEC/EN 61000-4-4
Contact discharge
According to EN 61100-4-2
Electromagnetic fields
According to IEC EN 61100-4-2
Emitted interference
230 - 1000 MHz (radiated, high frequency, according to EN 55016-2-3)
30 - 230 MHz (radiated, high frequency, according to EN 55016-2-3)
Radiated RFI
IEC/EN 61100-4-6
Surge rating
According to IEC/EN 61000-4-5 Level 4
Voltage dips
According to EN 61131-2 (Voltage fluctuations/voltage dips)

Terminal capacities

Terminal capacity
0.25 - 1.5 mm², flexible without ferrule, H07V-K
0.25 - 1.5 mm², solid, H07V-U
0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
Gauge pin
A1 (according to IEC/EN 60947-1)
Stripping length (main cable)
8 mm

Electrical rating

Rated operational voltage
24 V DC (supply terminal)
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
20.4 VDC
Supply voltage at DC - max
28.8 VDC

Communication

Connection
Connection of sensor types Pt100, Pt200, Pt500, Pt1000 and Ni100, Ni1000, NI1000TK5000 in 2- or 3-wire circuit
Connection type
Push-In spring-cage terminals, Connection design in TOP direction
Protocol
Other bus systems

Input/Output

Input
8 Analog input U/I
4 Analog inputs PT/NI
Input current
40 mA (Analog input)
0/4 - 20 mA (Analog input)
Input impedance
< 62 kΩ
≥ 200 kΩ
Input voltage
Max. 20 V DC
-10/0 - 10 V DC (Analog input modules)
Measured value representation
12-bit full range, flush left
16-bit signed integer
Standard/extended range/PA (NE43)
Measured variables
Current
Temperature (PT, NI)
Resistance
Voltage
Number of inputs (analog)
8
Number of outputs (analog)
0
Timing cycle
0.1 % Offset error

Safety

Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Through optocoupler: yes

Design verification

Equipment heat dissipation, current-dependent Pvid
1.5 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.5 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Export product specification