Eaton PSG Power supply unit, Single-phase, 85 - 264 V AC / 24 V DC, 2.5 A
| Product Name |
Eaton PSG power supply unit
|
| Catalog Number |
172891
|
| EAN |
4015081694792
|
| Product Length/Depth |
125 mm
|
| Product Height |
121 mm
|
| Product Width |
32 mm
|
| Product Weight |
0.37 kg
|
| Certifications |
Electrical equipment of machines: IEC60204-1 (Overvoltage category III)
2014/30/EU EN 55011 Protection against electric shock: DIN 57100-410 Mains harmonics limitation: EN 601000-3-2 PELV (EN 60204) ITE: EN 55022, EN 61000-3-2, EN 61000-3-3, EN 55024 2014/35/EU EN 50178/IEC 62103 Class2: UL1310 and CSA-C22.2 No. 223 IEC/EN 61204-3 RoHS Electrical Safety (of IT equipment) : SIQ to EN60950-1, UL/c-UL recognized to UL 60950-1, CSA-C22.2 No. 60950-1, CB scheme to IEC 60950-1 SELV (EN 60950) UL 508 IEC Rated CSA Std. C22.2 EN Listed EAC |
| Electric connection type |
Screw connection
|
| Enclosure material |
Aluminum
|
| Features |
Stabilized
Modular version Mains overvoltage protection (against internal overvoltage) Short-circuit-proof Output voltage stabilized |
| Fitted with: |
Not accessible internal input fuse (T3.15 AH/250 V) for device protection
|
| Functions |
Secondary voltage adjustable
Transient overvoltage protection (varistor) |
| Number of phases |
1
|
| Degree of Protection |
NEMA 1
IP20 |
| Environmental class |
3K3 (Climatic class, according to EN 60721)
|
| Mounting Method |
Rail mounting possible
|
| Pollution degree |
2
|
| Product category |
Power supply
|
| Connection type |
Screw terminal, pluggable
|
| LED indicator |
Status indication of "DC OK": Green LED
|
| Power consumption |
184 VA
|
| Rated operational current (Ie) |
Max. 1.4 A at 115 V AC
Max. 0.8 A at 230 V AC |
| Shock resistance |
30 g (300 m/s²) in all directions, Mechanical, According to IEC/EN 60068-2-27
|
| Vibration resistance |
10 - 500 Hz at 30 m/s² (3 G max ) for 60 min. in X-axis, Y-axis, Z-axis directions, (IEC/EN 60068-2-6)
|
| Ambient operating temperature - min |
-20 °C
|
| Ambient operating temperature - max |
80 °C
|
| Ambient storage temperature - min |
-25 °C
|
| Ambient storage temperature - max |
85 °C
|
| Climatic proofing |
< 95 % relative humidity at +25 °C, no condensation
|
| Terminal capacity (flexible with ferrule) |
0.32 - 3.3 mm²
|
| Terminal capacity (flexible with ferrule AWG) |
22 - 12
|
| Stripping length (main cable) |
7 mm
|
| Tightening torque |
0.5 Nm, Screw terminals
|
| Protection class |
1 (with PE connection)
|
| Current limitation |
Overcurrent = 150 % of max. output power, at short-circuit, safety and safety features
|
| Insulation resistance |
3 kV AC (routine test, input/output)
1.5 kV AC (type test, input) 4 kV AC (type test, input/output) 1.5 kV AC (type test, output) 500 V AC (routine test, output) 1.5 kV AC (routine test, input) |
| Mean time between failures (MTBF) |
> 1,000,000 h
|
| Input voltage at AC 50 Hz - min |
85 V
|
| Input voltage at AC 50 Hz - max |
264 V
|
| Input voltage at DC - min |
120 V
|
| Input voltage at DC - max |
375 V
|
| Inrush current |
< 35 A at 230 V AC (Inrush current limitation I²t (+25 °C))
< 20 A at 115 V AC (Inrush current limitation I²t (+25 °C)) |
| Leakage current at ground IPE - max |
< 1 mA (at 240 V AC)
|
| Mains failure bridging |
> 20 ms (at 115 V AC)
> 125 ms (at 230 V AC) |
| Ramp/run-up time |
< 2000 ms
|
| Short-term interruption |
100% voltage dip, 1 cycle (20 ms at 50 Hz), automatic start, Input characteristics
|
| Supply frequency |
47 Hz, Input, min. Range
50/60 Hz, Input, Rated value 63 Hz, Input, max. Range |
| Supply voltage at AC, 50 Hz - min |
85 VAC
|
| Supply voltage at AC, 50 Hz - max |
264 VAC
|
| Supply voltage at DC - min |
0 VDC
|
| Supply voltage at DC - max |
0 VDC
|
| Tripping characteristic |
B
|
| Residual ripple |
< 50 mV / < 150 mV
|
| Capacitive load |
8000 µF max. Capacitive load starting, Output characteristics
|
| Efficiency |
> 90 % (115 V AC)
> 90 % (230 V AC) |
| Output |
Parallel switching for redundancy, with O ring diode (PSG480R24RM/PSG960R24RM)
|
| Output current at AC, 50 Hz - max |
2.5 A
|
| Output voltage |
24 V
|
| Output voltage at DC - min |
24 V
|
| Output voltage at DC - max |
28 V
|
| Rated output power |
60 W
|
| Voltage tolerance |
± 2 %, Rated output voltage
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
7.4 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|