Eaton xEffect SASY 60i Enclosures Switch- & Controlgear Enclosure. Bus-mounted fuse base, 25A, 500 V, DII/E27, 45mm
| Product Name |
Eaton xEffect SASY 60i Enclosures Switch- & Controlgear Enclosure
|
| Catalog Number |
107965
|
| EAN |
4015081076017
|
| Product Length/Depth |
295 mm
|
| Product Height |
160 mm
|
| Product Width |
267 mm
|
| Product Weight |
0.24 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC/EN 60269-1
VDE 0636 Part 301 |
| Model Code |
DII-SO/25/3-R
|
| Used with |
Double T profile
12 mm x 5/10 mm rail 20 mm x 5/10 mm rail 25 mm x 5/10 mm rail 30 mm x 5/10 mm rail 60 mm system Busbar fuse material Push-in gauge ring 185 mm system |
| Amperage Rating |
25 A
|
| Number of poles |
Three-pole
|
| Frame |
E27, D II
|
| Frequency rating |
40 Hz - 60 Hz
|
| Terminals |
Lift terminals
|
| Voltage rating at AC |
|
| Rated operational voltage (Ue) - max |
500 V
|
| Pollution degree |
3
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
25 A
|
| Current heat loss per contact at Ie |
0.4 W
|
| Enclosure width |
200 mm
|
| Heat dissipation per contact with fuse link at Ie |
1.2 W
|
| Rated conditional short-circuit current tested with links |
50 kA
|
| Rated impulse withstand voltage (Uimp) |
4 kV
|
| Distance between busbar centers |
60 mm
|
| Construction size |
DII
|
| Mounting position |
Vertical or horizontal
|
| Functions |
Basic device
D busbar mounted fuse device Uninterrupted operation (Control mode) |
| Overvoltage category |
III
|
| Material |
Plastic
|
| Frequency rating of contacts |
40 Hz - 60 Hz
|
| Mounting method |
Rail system
|
| Degree of protection |
IP20 enclosed
|
| Rated operation current (Ie) |
25 A
|
| Voltage rating |
500 V
|
| Type |
|
| Special features |
|
| Thread type |
E27
|
| Model |
Fitted ring
|
| Mounting width |
45 mm
|
| Permitted heat loss from fuse links - max |
4 W
|
| Terminal capacity (solid wire) |
1.5 mm² - 25 mm²
1.5 mm² - 25 mm² at box terminal |