Photo is representative
Download
Eaton Moeller® series PKE Overload relay function, 24 V DC
| Product Name |
Eaton Moeller® series PKE Overload relay module
|
| Catalog Number |
173425
|
| EAN |
4015081698288
|
| Product Length/Depth |
105 mm
|
| Product Height |
50 mm
|
| Product Width |
105 mm
|
| Product Weight |
0.079 kg
|
| Compliances |
CE
|
| Model Code |
PKE-XZMR(24VDC)
|
| Features |
Status display via LED
|
| Functions |
Adjustable manual/auto reset
Overload relay function (the motor-protective circuit-breaker will not trip in the event of an overload) |
| Class |
Other
|
| Lifespan, electrical |
200,000 Operations
|
| Lifespan, mechanical |
5,000,000 Operations
|
| Mounting method |
Direct attachment
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Product Category |
Accessories
|
| Rated impulse withstand voltage (Uimp) |
6000 V AC
|
| Voltage type |
DC
|
| Mounting position |
Right side (of PKE motor-protective circuit-breakers with advanced PKE-XTU…A… trip blocks)
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
55 °C
|
| Terminal capacity (solid/flexible with ferrule) |
0.75 - 2.5 mm²
|
| Terminal capacity (solid/stranded AWG) |
18 - 14
|
| Operational voltage |
0.8 - 1.1 x Us
|
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V |
7777777 A
|
| Rated operational voltage (Ue) at AC - max |
7777777 V
|
| Rated operational voltage (Ue) at DC - max |
250 V
|
| Safe isolation |
440 V, Between auxiliary contacts and main contacts, According to EN 61140
|
| Safe isolation |
440 V, Between auxiliary contacts and main contacts, According to EN 61140
|
| Short-circuit protection rating |
6 A gG/gL, Fuse, Contacts
|
| Operational voltage |
0.8 - 1.1 x Us
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
| Rated control supply voltage (Us) at DC - min |
24 V
|
| Rated control supply voltage (Us) at DC - max |
24 V
|
| Number of auxiliary contacts (change-over contacts) |
0
|
| Number of auxiliary contacts (normally closed contacts) |
1
|
| Number of auxiliary contacts (normally open contacts) |
1
|
| Number of contacts (normally closed contacts) |
1
|
| Number of contacts (normally open contacts) |
1
|
| Power consumption (pick-up) at DC |
0.5 W
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0.017 W
|
| Rated operational current for specified heat dissipation (In) |
1.5 A
|
| Static heat dissipation, non-current-dependent Pvs |
0.61 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|