Eaton Moeller® series P5 Main switch, P5, 160 A, rear mounting, 3 pole, 1 N/O, Emergency switching off function, With red rotary handle and yellow locking ring, Lockable in the 0 (Off) position
Product Name |
Eaton Moeller® series P5 Main switch
|
Catalog Number |
280929
|
EAN |
4015082809294
|
Product Length/Depth |
115 mm
|
Product Height |
150 mm
|
Product Width |
130 mm
|
Product Weight |
1.345 kg
|
Compliances |
CE Marked
|
Certifications |
IEC 60947
UL 508 CSA Std. C22.2 No. 14-05 EN 60947-3 VDE CSA-C22.2 No. 14-05 VDE 0660 CSA CE IEC/EN 60947-3 CSA File No.: 223805 CSA-C22.2 No. 94 IEC/EN 60204 UL IEC/EN 60947 UL Category Control No.: NLRV, NLRV7 UL File No.: E36332 CSA Class No.: 3211-05 |
Catalog Notes |
Rated Short-time Withstand Current (Icw) for a time of 1 second
|
Model Code |
P5-160/V/SVB/HI10
|
Features |
Version as emergency stop installation
Version as maintenance-/service switch Version as main switch |
Fitted with: |
Red rotary handle and yellow locking ring
|
Functions |
Emergency switching off function
Interlockable |
Locking facility |
Lockable in the 0 (Off) position
|
Number of poles |
3
|
Accessories |
Auxiliary contact or neutral conductor fitted by user.
|
Degree of protection |
NEMA 12
|
Degree of protection (front side) |
IP65
|
Lifespan, mechanical |
100,000 Operations
|
Mounting method |
Rear mounting
|
Mounting position |
As required
|
Operating frequency |
50 Operations/h
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product Category |
Main switch
|
Rated impulse withstand voltage (Uimp) |
8000 V AC
|
Safe isolation |
440 V AC, Between the contacts, According to EN 61140
|
Safety parameter (EN ISO 13849-1) |
B10d values as per EN ISO 13849-1, table C.1
|
Suitable for |
Intermediate mounting
Branch circuits, suitable as motor disconnect, (UL/CSA) |
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Terminal capacity |
3/0 AWG, solid or flexible conductor with ferrule
2 x 13 x 1.5 mm Number of segments x width x thickness, copper strip 1 x 70 mm², flexible with ferrules to DIN 46228 2 x 35 mm², solid or stranded 2 x 25 mm², flexible with ferrules to DIN 46228 1 x 13 x 3 mm Number of segments x width x thickness, copper strip 1 x 95 mm², solid or stranded 2/0 AWG, flexible |
Screw size |
5 mm AF, Hexagon socket-head spanner, Terminal screw
|
Tightening torque |
125 lb-in, Screw terminals
14 Nm, Screw terminals |
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3) |
900 A
|
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3) |
850 A
|
Rated breaking capacity at 500 V (cos phi to IEC 60947-3) |
850 A
|
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3) |
340 A
|
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
103 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
85 A
|
Rated operational current (Ie) at AC-3, 500 V |
80 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
42 A
|
Rated operational current (Ie) at AC-21, 440 V |
160 A
|
Rated operational current (Ie) at AC-23A, 230 V |
103 A
|
Rated operational current (Ie) at AC-23A, 400 V, 415 V |
105 A
|
Rated operational current (Ie) at AC-23A, 500 V |
106 A
|
Rated operational current (Ie) at AC-23A, 690 V |
42 A
|
Rated operational current (Ie) at DC-1, load-break switches l/r = 1 ms |
160 A
|
Rated operational current (Ie) at DC-23A, 24 V |
160 A
|
Rated operational current (Ie) at DC-23A, 48 V |
160 A
|
Rated operational current (Ie) at DC-23A, 60 V |
160 A
|
Rated operational current (Ie) at DC-23A, 120 V |
50 A
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
45 kW
|
Rated operational power at AC-3, 415 V, 50 Hz |
45 kW
|
Rated operational power at AC-3, 690 V, 50 Hz |
37 kW
|
Rated operational power at AC-23A, 220/230 V, 50 Hz |
30 kW
|
Rated operational power at AC-23A, 400 V, 50 Hz |
55 kW
|
Rated operational power at AC-23A, 500 V, 50 Hz |
75 kW
|
Rated operational power at AC-23A, 690 V, 50 Hz |
37 kW
|
Rated operational voltage (Ue) at AC - max |
690 V
|
Rated uninterrupted current (Iu) |
160 A
|
Uninterrupted current |
Rated uninterrupted current Iu is specified for max. cross-section.
|
Rated conditional short-circuit current (Iq) |
30 kA
|
Rated short-time withstand current (Icw) |
3 kA, Contacts, 1 second
3 kA |
Short-circuit current rating (basic rating) |
400A Class RK1, max. Fuse, SCCR (UL/CSA)
10 kA, SCCR (UL/CSA) |
Short-circuit current rating (high fault) |
65 kA, SCCR (UL/CSA)
300 A, Class J, max. Fuse, SCCR (UL/CSA) |
Short-circuit protection rating |
160 A gG/gL, Fuse, Contacts
|
Load rating |
2 x Iₑ (with intermittent operation class 12, 25 % duty factor)
1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor) 1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor) |
Number of contacts in series at DC-23A, 24 V |
3
|
Number of contacts in series at DC-23A, 48 V |
3
|
Number of contacts in series at DC-23A, 60 V |
3
|
Number of contacts in series at DC-23A, 120 V |
3
|
Switching capacity (main contacts, general use) |
200 A, Rated uninterrupted current max. (UL/CSA)
|
Switching capacity (auxiliary contacts, general use) |
10A, IU, (UL/CSA)
|
Switching capacity (auxiliary contacts, pilot duty) |
A600 (UL/CSA)
|
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3) |
1050 A
|
Voltage per contact pair in series |
42 V
|
Assigned motor power at 115/120 V, 60 Hz, 1-phase |
10 HP
|
Assigned motor power at 115/120 V, 60 Hz, 3-phase |
20 HP
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
25 HP
|
Assigned motor power at 230/240 V, 60 Hz, 3-phase |
40 HP
|
Assigned motor power at 277 V, 60 Hz, 1-phase |
25 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
60 HP
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
60 HP
|
Control circuit reliability |
1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
1
|
Actuator color |
Red
|
Actuator type |
Door coupling rotary drive
|
Equipment heat dissipation, current-dependent Pvid |
5 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
5 W
|
Rated operational current for specified heat dissipation (In) |
160 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
UV resistance only in connection with protective shield.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|