Eaton DG1 Variable frequency drive, 600 V AC, 3-phase, 750 A, 500 kW, IP00, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
3-4918-311A
|
EAN |
4015081941995
|
Product Length/Depth |
561 mm
|
Product Height |
980 mm
|
Product Width |
1037 mm
|
Product Weight |
410 kg
|
Certifications |
RoHS, ISO 9001
Safety requirements: IEC/EN 61800-5 EAC CE UkrSEPRO UL Specification for general requirements: IEC/EN 61800-2 CUL C-Tick IEC/EN 61800-3 |
Model Code |
DG1-35820FN-C00C
|
Features |
Externally accessible fan
Temperature-controlled fan |
Air volume capacity |
2800 m³/h
|
Cable length |
200 m, screened, maximum permissible, Motor feeder
C3 ≤ 10 m, Radio interference level, maximum motor cable length |
Degree of protection |
IP00
NEMA Other |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Environmental class |
3C2, 3S2 (Air quality)
|
Fitted with: |
Internal DC link
Additional PCB protection IGBT inverter Radio interference suppression filter DC link choke Multi-line graphic display Control unit PC connection |
Frame size |
FS8
|
Mounting position |
Vertical
|
Number of slots |
2 (expansion)
|
Overvoltage category |
III
|
Pollution degree |
2
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Radio interference class |
C1: with external filter, for conducted emissions only
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Shock resistance |
UPS drop test (for weights inside the UPS frame)
Storage and transportation: maximum 15 g, 11 ms (inside the packaging) Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 |
Suitable for |
Branch circuits, (UL/CSA)
|
Vibration |
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 |
Altitude |
Max. 2000 m
Above 1000 m with 1 % derating per 100 m Max. 1000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Apparent power at 690 V |
980 kVA
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Efficiency |
98.1 % (η)
|
Input current ILN at 110% overload |
813 A
|
Input current ILN at 150% overload |
739 A
|
Mains current distortion |
28 %
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage - min |
525 V
|
Mains voltage - max |
600 V
|
Operating mode |
U/f control
Sensorless vector control (SLV) Torque regulation Speed control with slip compensation |
Output frequency - min |
0 Hz
|
Output frequency - max |
400 Hz
|
Output voltage (U2) |
600 V AC, 3-phase
690 V AC, 3-phase |
Overload current IL at 110% overload |
902 A
|
Overload current IL at 150% overload |
1125 A
|
Rated conditional short-circuit current (Iq) |
65 kA
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) at 110% overload |
820 A
|
Rated operational current (Ie) at 150% overload |
750 A
|
Rated operational power at 525 V, 50 Hz |
500 kW
|
Rated operational power at 525 V, 50 Hz, 110% overload |
560 kW
|
Rated operational power at 600 V, 50 Hz |
560 kW
|
Rated operational power at 600 V, 50 Hz, 110% overload |
630 kW
|
Rated operational voltage |
600 V AC, 3-phase
690 V AC, 3-phase |
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
2 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
2 kHz, 1.5 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Voltage rating - max |
690 VAC
|
Assigned motor current IM at 525 V, 50 Hz, 110% overload |
770 A
|
Assigned motor current IM at 525 V, 50 Hz, 150% overload |
720 A
|
Assigned motor current IM at 600 V, 50 Hz, 110% overload |
765 A
|
Assigned motor current IM at 600 V, 50 Hz, 150% overload |
680 A
|
Assigned motor current IM at 690 V, 60 Hz, 110% overload |
810 A
|
Assigned motor current IM at 690 V, 60 Hz, 150% overload |
729 A
|
Assigned motor power at 690 V, 60 Hz |
900 HP
|
Assigned motor power at 690 V, 60 Hz, 110% overload |
1000 HP
|
Apparent power at 600 V |
852.2 kVA
|
Braking resistance |
2.5 Ω
|
Braking torque |
Adjustable to 150 %, DC - Main circuit
Adjustable to 150 % (I/Ie), DC - Main circuit Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Switch-on threshold for the braking transistor |
1050 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
1
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Communication interface |
SmartWire-DT, optional
PROFIBUS, optional Modbus RTU, built in BACnet MS/TP, built in Ethernet IP, built in DeviceNet, optional CANopen®, optional Modbus TCP, built in |
Connection to SmartWire-DT |
In conjunction with DXG-NET-SWD SmartWire DT module
Yes |
Protocol |
BACnet
CAN DeviceNet EtherNet/IP MODBUS Other bus systems PROFIBUS PROFINET IO TCP/IP |
Equipment heat dissipation, current-dependent Pvid |
16617 W
|
Rated operational current for specified heat dissipation (In) |
750 A
|
Static heat dissipation, non-current-dependent Pvs |
291 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|