Eaton DG1 Variable frequency drive, 230 V AC, 3-phase, 61 A, 15 kW, IP21/NEMA1, Brake chopper, DC link choke
| Product Name |
Eaton DG1 variable frequency drive
|
| Catalog Number |
9701-4002-00P
|
| EAN |
4015081734108
|
| Product Length/Depth |
294 mm
|
| Product Height |
630 mm
|
| Product Width |
237.7 mm
|
| Product Weight |
34.4 kg
|
| Certifications |
Certified by UL for use in Canada
IEC/EN 61800-3 EAC UL508 IEC/EN61800-5 Safety requirements: IEC/EN 61800-5 UL File No.: E134360 IEC/EN61800-3 Specification for general requirements: IEC/EN 61800-2 UkrSEPRO CE RoHS, ISO 9001 UL UL report applies to both US and Canada CUL CSA-C22.2 No. 274-13 C-Tick UL Category Control No.: NMMS, NMMS7 |
| Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
| Model Code |
DG1-32061FB-C21C
|
| Features |
Externally accessible fan
Temperature-controlled fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
| Functions |
4-quadrant operation possible
|
| Air volume capacity |
260 m³/h
|
| Cable length |
C2 ≤ 10 m, Radio interference level, maximum motor cable length
C3 ≤ 50 m, Radio interference level, maximum motor cable length 200 m, screened, maximum permissible, Motor feeder |
| Degree of protection |
NEMA 1
IP21 |
| Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
| Environmental class |
3C2, 3S2 (Air quality)
|
| Fitted with: |
Brake chopper
Internal DC link Additional PCB protection Radio interference suppression filter DC link choke Breaking resistance Control unit IGBT inverter PC connection Multi-line graphic display |
| Frame size |
FS4
|
| Mounting position |
Vertical
|
| Number of slots |
2 (expansion)
|
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Product Category |
Variable frequency drives
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
| Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. C1: with external filter, for conducted emissions only |
| Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
| Shock resistance |
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
UPS drop test (for weights inside the UPS frame) Storage and transportation: maximum 15 g, 11 ms (inside the packaging) |
| Suitable for |
Branch circuits, (UL/CSA)
|
| Vibration |
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) |
| Altitude |
Max. 1000 m
Max. 3000 m Above 1000 m with 1 % derating per 100 m Max. 2000 m for Corner Grounded TN Systems |
| Ambient operating temperature - min |
-10 °C
|
| Ambient operating temperature - max |
50 °C
|
| Ambient operating temperature at 150% overload - min |
-30 °C
|
| Ambient operating temperature at 150% overload - max |
50 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
70 °C
|
| Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
| Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
| Efficiency |
97.4 % (η)
|
| Input current ILN at 110% overload |
64.6 A
|
| Input current ILN at 150% overload |
54.4 A
|
| Leakage current at ground IPE - max |
6.2 mA
|
| Mains current distortion |
25.6 %
|
| Mains switch-on frequency |
Maximum of one time every 60 seconds
|
| Mains voltage - min |
208 V
|
| Mains voltage - max |
240 V
|
| Operating mode |
U/f control
Torque regulation Speed control with slip compensation Sensorless vector control (SLV) |
| Output frequency - min |
0 Hz
|
| Output frequency - max |
400 Hz
|
| Output voltage (U2) |
230 V AC, 3-phase
240 V AC, 3-phase |
| Overload current IL at 110% overload |
82.5 A
|
| Overload current IL at 150% overload |
91.5 A
|
| Rated conditional short-circuit current (Iq) |
100 kA
|
| Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
| Rated frequency - min |
45 Hz
|
| Rated frequency - max |
66 Hz
|
| Rated operational current (Ie) at 110% overload |
75 A
|
| Rated operational current (Ie) at 150% overload |
61 A
|
| Rated operational power at 220/230 V, 50 Hz, 1-phase |
15 kW
|
| Rated operational power at 220/230 V, 50 Hz, 3-phase, 110% overload |
22 kW
|
| Rated operational voltage |
240 V AC, 3-phase
230 V AC, 3-phase |
| Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
| Short-circuit protection rating |
100 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
| Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
| Supply frequency |
50/60 Hz
|
| Switching frequency |
3.6 kHz, 1 - 10 kHz adjustable, fPWM, Power section, Main circuit
|
| System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
| Voltage rating - max |
240 VAC
|
| Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
54 A
|
| Assigned motor current IM at 230 V, 50 Hz, 110% overload |
71 A
|
| Assigned motor current IM at 230 V, 50 Hz, 150% overload |
51 A
|
| Assigned motor current IM at 230 V, 60 Hz, 110% overload |
68 A
|
| Assigned motor power at 230/240 V, 60 Hz, 1-phase |
20 HP
|
| Assigned motor power at 230/240 V, 60 Hz, 3-phase, 110 % overload |
25 HP
|
| Apparent power at 230 V |
29.9 kVA
|
| Apparent power at 240 V |
31.2 kVA
|
| Braking resistance |
3.3 Ω
|
| Braking torque |
Adjustable to 150 %, DC - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Max. 30 % MN, Standard - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit |
| Switch-on threshold for the braking transistor |
425 VDC
|
| Number of inputs (analog) |
2
|
| Number of inputs (digital) |
8
|
| Number of outputs (analog) |
2
|
| Number of outputs (digital) |
1
|
| Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
| Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
| Communication interface |
SmartWire-DT, optional
Modbus RTU, built in Modbus TCP, built in DeviceNet, optional BACnet MS/TP, built in Ethernet IP, built in PROFIBUS, optional CANopen®, optional |
| Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
| Protocol |
PROFIBUS
CAN Other bus systems PROFINET IO BACnet TCP/IP MODBUS DeviceNet EtherNet/IP |
| Equipment heat dissipation, current-dependent Pvid |
689 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
61 A
|
| Static heat dissipation, non-current-dependent Pvs |
17.1 W
|
| Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|