Eaton DG1 Variable frequency drive, 400 V AC, 3-phase, 9 A, 4 kW, IP54/NEMA12, Brake chopper, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
9702-1111-00P
|
EAN |
4015081710836
|
Product Length/Depth |
200.9 mm
|
Product Height |
327 mm
|
Product Width |
153 mm
|
Product Weight |
6.7 kg
|
Certifications |
UL report applies to both US and Canada
C-Tick IEC/EN61800-5 Safety requirements: IEC/EN 61800-5 CE IEC/EN 61800-3 RoHS, ISO 9001 Certified by UL for use in Canada CSA-C22.2 No. 274-13 UL508 EAC UL UL Category Control No.: NMMS, NMMS7 IEC/EN61800-3 UkrSEPRO CUL Specification for general requirements: IEC/EN 61800-2 UL File No.: E134360 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Model Code |
DG1-349D0FB-C54C
|
Features |
Tool-less swapping of fan
Temperature-controlled fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
Functions |
4-quadrant operation possible
|
Air volume capacity |
24 m³/h
|
Cable length |
100 m, screened, maximum permissible, Motor feeder
C3 ≤ 50 m, Radio interference level, maximum motor cable length C2 ≤ 10 m, Radio interference level, maximum motor cable length |
Degree of protection |
NEMA 12
IP54 |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Environmental class |
3C2, 3S2 (Air quality)
|
Fitted with: |
PC connection
DC link choke Internal DC link Brake chopper IGBT inverter Radio interference suppression filter Control unit Additional PCB protection Multi-line graphic display Breaking resistance |
Frame size |
FS1
|
Mounting position |
Vertical
|
Number of slots |
2 (expansion)
|
Overvoltage category |
III
|
Pollution degree |
2
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Radio interference class |
C1: with external filter, for conducted emissions only
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Shock resistance |
UPS drop test (for weights inside the UPS frame)
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 Storage and transportation: maximum 15 g, 11 ms (inside the packaging) |
Suitable for |
Branch circuits, (UL/CSA)
|
Vibration |
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) |
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 1000 m Max. 2000 m for Corner Grounded TN Systems Max. 3000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-30 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Efficiency |
98.1 % (η)
|
Input current ILN at 110% overload |
11.2 A
|
Input current ILN at 150% overload |
8.4 A
|
Leakage current at ground IPE - max |
2.9 mA
|
Mains current distortion |
35.3 %
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
500 V
|
Operating mode |
U/f control
Torque regulation Sensorless vector control (SLV) Speed control with slip compensation |
Output frequency - min |
0 Hz
|
Output frequency - max |
400 Hz
|
Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase 500 V AC, 3-phase |
Overload current IL at 110% overload |
13.2 A
|
Overload current IL at 150% overload |
13.5 A
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) at 110% overload |
12 A
|
Rated operational current (Ie) at 150% overload |
9 A
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
4 kW
|
Rated operational power at 380/400 V, 50 Hz, 3-phase, 110% overload |
5.5 kW
|
Rated operational power at 500 V, 50 Hz, 3-phase |
5.5 kW
|
Rated operational power at 500 V, 50 Hz, 3-phase, 110% overload |
5.5 kW
|
Rated operational voltage |
400 V AC, 3-phase
480 V AC, 3-phase 500 V AC, 3-phase |
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
15 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
4 kHz, 1 - 12 kHz adjustable, fPWM, Power section, Main circuit
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Voltage rating - max |
500 VAC
|
Assigned motor current IM at 400 V, 50 Hz, 110% overload |
11.5 A
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
8.5 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
7.6 A
|
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
11 A
|
Assigned motor current IM at 500 V, 50 Hz, 110% overload |
9 A
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
6.8 A
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
5 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase, 110 % overload |
7.5 HP
|
Apparent power at 400 V |
8.3 kVA
|
Apparent power at 480 V |
10.4 kVA
|
Braking resistance |
63 Ω
|
Braking torque |
Adjustable to 150 % (I/Ie), DC - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Adjustable to 150 %, DC - Main circuit Max. 30 % MN, Standard - Main circuit |
Switch-on threshold for the braking transistor |
850 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
1
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Communication interface |
Ethernet IP, built in
Modbus RTU, built in SmartWire-DT, optional BACnet MS/TP, built in DeviceNet, optional PROFIBUS, optional Modbus TCP, built in CANopen®, optional |
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Protocol |
PROFIBUS
CAN Other bus systems TCP/IP PROFINET IO BACnet MODBUS DeviceNet EtherNet/IP |
Equipment heat dissipation, current-dependent Pvid |
167 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
9 A
|
Static heat dissipation, non-current-dependent Pvs |
17.33 W
|
Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|