Eaton EC4P I/O expansion, integrated, 24 V DC, 6DI, 4DO(R)
Product Name |
Eaton EC4P I/O expansion
|
Catalog Number |
114296
|
Model Code |
EC4E-221-6D4R1
|
EAN |
4015081136933
|
Product Length/Depth |
58 mm
|
Product Height |
90 mm
|
Product Width |
71.5 mm
|
Product Weight |
0.16 kg
|
Certifications |
IEC/EN 61000-4-2, Level 3
|
Features |
Asynchronous, cyclic, acyclic PDO types (operating modes of the slave)
|
Fitted with: |
Real time clock
|
Functions |
CANopen® expansion
|
Cable length |
100 m, unshielded, Digital inputs 24 V DC
|
Degree of protection |
IP20
|
Lifespan, electrical |
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device)
25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC) 25,000 Operations (Filament bulb load at 500 W, 115/120 V AC) 25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated) 25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated) |
Lifespan, mechanical |
10,000,000 Operations
10,000,000 Operations (Relay outputs) |
Mounting method |
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Screw fixing using fixing brackets ZB4-101-GF1 (accessories) |
Overvoltage category |
II
|
Pollution degree |
2
|
Product category |
|
Protection |
Miniature circuit-breaker B16 or fuse 8 A (slow), Protection of an output relay
|
Rated impulse withstand voltage (Uimp) |
6 kV (contact-coil)
|
Rated insulation voltage (Ui) |
250 V
|
Rated operational voltage |
24 V DC (digital inputs)
Max. 300 V DC 20.4 - 28.8 V DC 24 V DC (-15 %/+ 20 % - power supply) Max. 300 V AC 250 V AC |
Short-circuit protection |
16 A, Short-circuit-proof cos ϕ = 1, characteristic B16 at 600 A, Contacts, Relay outputs
16 A, Short-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A, Contacts, Relay outputs |
Type |
Expansions
|
Used with |
XC100/200, EC4P, MFD4 (via CANopen®)
XC200 XC100 |
Utilization category |
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC
B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC |
Voltage type |
AC/DC
DC |
Mounting position |
Horizontal
Vertical |
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Environmental conditions |
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 142 |
Air discharge |
8 kV
|
Burst impulse |
According to IEC/EN 61000-4-4
|
Electromagnetic fields |
10 V/m (according to IEC EN 61000-4-3)
|
Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
Surge rating |
2 kV, Supply cables, symmetrical, EASY...AC, power pulses (Surge), EMC
0.5 kV, Supply cables, symmetrical, EASY…DC, power pulses (Surge), EMC According to IEC/EN 61000-4-5, power pulses (Surge), EMC |
Terminal capacity |
0.2 - 4 mm² (22 - 12 AWG), solid
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule |
Screwdriver size |
3.5 x 0.8 mm, Terminal screw
|
Tightening torque |
0.6 Nm, Screw terminals
|
Input voltage |
Signal 1: > 15 V DC (R1 - R6, Digital inputs, 24 V DC)
Signal 0: < 5 V DC (R1 - R6, Digital inputs, 24 V DC) |
Output current |
8 A
|
Residual ripple |
≤ 5 %
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at DC - min |
20.4 VDC
|
Supply voltage at DC - max |
28.8 VDC
|
Voltage dips |
20 ms
According to EN 61131-2 |
Bus termination |
EASY-NT-R plug (incl. bus terminating resistor 120 Ω),first and last station, CANopen®
|
Connection type |
Screw terminals
|
Data transfer rate |
500 kBit/s at 25 m, CANopen®
20 kBit/s at 700 m, CANopen® 250 kBit/s at 40 m, CANopen® 50 kBit/s at 300 m, CANopen® 125 kBit/s at 125 m, CANopen® 10 kBit/s at 1000 m , CANopen® |
Electric connection type |
Screw connection
|
Number of modules |
Max. 62
|
Station |
To DS 301 V4, Control contact rated current, Mode slave, Interfaces
|
Delay time |
0.25 ms typ, Digital inputs 24 DC (R1 - R12), Delay time from 0 to 1, Debounce OFF
20 ms, Digital inputs 24 DC, Delay time from 1 to 0 20 ms, Digital inputs 24 DC, Delay time from 0 to 1, Debounce ON |
Input |
6 Digital inputs
|
Input current |
150 mA (at no load)
3.3 mA (R1 - R6 (R12), at 24 V DC, at signal 1) |
Input current at signal 1 |
3.3 mA
|
Insulation resistance |
According to EN 50178
|
Making/breaking capacity |
3600/360 VA (AC, at B 300)
28/28 VA (DC, at R 300) |
Number of inputs (digital) |
6
|
Number of outputs (digital) |
4
|
Output |
Relay outputs in groups of 1
> 500 mA (Relay outputs, Recommended for load: 12 V AC/DC) |
Parallel switching |
Not permitted
|
Rated breaking capacity |
200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h)
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h) |
Switching frequency |
2 Hz, Resistive load/lamp load, Relay outputs
0.5 Hz, Inductive load, Relay outputs 10 Hz, Relay outputs |
Uninterrupted current |
1 A DC, at R 300 (UL/CSA)
10 A AC, at 240 V AC (UL/CSA) 8 A DC, at 24 V DC (UL/CSA) 5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA) |
Explosion safety category for gas |
None
|
Potential isolation |
Between Relay outputs and PC interface, memory card, network NET, easyLink: yes
Between Relay outputs and Power supply: yes Basic isolation: 600 V AC (Relay outputs) Between Relay outputs and Inputs: yes Between Digital inputs 24 V DC and Outputs: yes Safe isolation according to EN 50178: 300 V AC (Relay outputs) |
Explosion safety category for dust |
None
|
Safe isolation |
300 V AC, Between coil and contact, According to EN 50178
300 V AC, Between two contacts, According to EN 50178 |
Equipment heat dissipation, current-dependent Pvid |
3.5 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
3.4 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|