Download document () of 20

138544
Model code: MCCB3-630/I48/I43E-200

Eaton xEnergy Safety Ci LV systems LV switchgear. Housing, insulated material, for molded-case circuit-breaker NZM3 size, HxWxD=1000x375x225mm

General specifications

Product Name
Eaton xEnergy Safety Ci MCCB enclosure
Catalog Number
138544
Model Code
MCCB3-630/I48/I43E-200
EAN
4015081353231
Product Length/Depth
225 mm
Product Height
1000 mm
Product Width
375 mm
Product Weight
14.771 kg
Compliances
RoHS conform

Delivery program

Type
Enclosures for circuit breakers, switch-disconnectors Prepared enclosures xEnergy Safety Ci
Model
Surface mounting

Technical data - electrical

Voltage rating
690 V AC
Voltage rating at AC
690 V AC
Rated uninterrupted current (Iu)
630 A

Technical data - mechanical

Unit type
Complete housing
Enclosure
Ci combination of CI48-200 + CI43E-200 + STB4-CI
Enclosure material
Plastic
Degree of protection
Other
IP65
Cover/door type
Transparent, smoke gray, pre-drilled for door coupling rotary handle

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
57 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
56 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
64 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
115 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
113 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
128 W

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
10 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Additional information

Fitted with:
Transparent cover
Functions
Prepared enclosure
Special features
For use as individual enclosures (order insulated additional terminal for 4th or 5th pole separately) or in distribution boards Observe the technical data of other equipment when connecting distribution boards side walls without knockouts, open at the bottom Side walls can be knocked out or fitted next to other devices Galvanized sheet steel mounting plate pre-drilled for switches & PE and N terminal Sealable cover fasteners With door coupling rotary handle NZM…-XTVD and extension shaft Fixing material for fixing material Including fixing straps for wall mounting can not be combined with remote operator NZM...-XR, plug-in unit NZM...-XSV or withdrawable unit NZM...-XAV
Suitable for
Emergency stop
Used with
K150/1N…
K95/1N…
NZM3(-4)
K240/1N…
K2X240/1N…
LN3(-4)
PN3(-4)
LZM3(-4)
NS3
K50/1
N3(-4)
xEnergy Safety Ci
Enclosures for circuit breakers, switch-disconnectors
Prepared enclosures

Export product specification