Eaton Moeller® series CI-K Insulated enclosure, HxWxD=200x120x160mm, +mounting rail
Product Name |
Eaton Moeller® series CI-K Insulated enclosure
|
Catalog Number |
206885
|
EAN |
4015082068851
|
Product Length/Depth |
160 mm
|
Product Height |
222 mm
|
Product Width |
120 mm
|
Product Weight |
0.58 kg
|
Certifications |
IEC 60068-2-11
DIN EN 62208 IEC/EN 60529 UL94: HB UL94: VO/1.5 mm thickness |
Catalog Notes |
Lamp indicator L‐… can be mounted in base knock-out M20/M25
|
Model Code |
CI-K3-160-TS
|
Type |
Basic enclosure
|
Features |
UV resistance beneath protective shield
Halogen free |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Please enquire
|
10.2.5 Lifting |
Not applicable.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Meets the product standard's requirements.
|
Fitted with: |
Mounting rail to IEC/EN 60715
Control cable entry |
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Enclosure material |
1 Ω x 10¹³ (Surface resistance to IEC 60093)
Plastic |
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
25.5 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Mounting depth |
128 mm
|
Mounting weight capacity - max |
0.85 kg
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Product category |
Empty enclosures
|
Enclosure color |
Light gray, Cover (RAL 7035)
Light gray, Operator (RAL 7035) Black (RAL 9005) |
Environmental resistance |
Partly resistant to alcohol
Resistant against alcohol Resistant against gasoline Not resistant to benzene Chemical resistant (Push-through membrane (CI-K1/CI-K2) and sealing material) Resistant against mineral oil Resistant against benzene Resistant against greases Resistant against alkalis Resistant against acids (< 10%) Partly resistant to acids (> 10%) Partly resistant to greases Chemical resistant (Base, Cover) Not resistant to alkalis Not resistant to Mineral oil Partly resistant to benzene Resistant against salt solutions |
Cover material |
Glass-fiber reinforced polycarbonate
|
Degree of protection |
IP65
NEMA Other |
Model |
Surface mounting
|
Dielectric strength |
30 kV/mm, according to IEC 60243-1
|
Degree of protection (front side) |
IP65
|
Temperature resistance |
-40 - 120 °C (enclosure)
-40 - 80 °C (gasket) |
Suitable for |
Emergency stop
|
Flammability characteristics |
650 °C/1 mm thick (push-through membrane) to VDE 0471 Part 2)
960 °C/1 mm thickness (base, cover; glow wire to VDE 0471 Part 2) |
Knockouts |
Hard knockout version
Metric cable entry knockouts at the top, bottom and back plate |
Impact resistance |
IK06 (according to EN 50102)
|
Radiated heat dissipation with separate mounting |
25.5 W (at an ambient temperature of 20 °C)
|
Surface treatment |
Resistant to corrosion
|
Track resistance |
CTI 175 (base, to IEC 60112)
CTI 175 (cover, to IEC 60112) |
Water consumption |
0.29 % (According to DIN EN ISO 62)
|