Eaton DG1 Variable frequency drive, 230 V AC, 3-phase, 17.5 A, 4 kW, IP21/NEMA1, Brake chopper, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
9701-2004-00P
|
EAN |
4015081734061
|
Product Length/Depth |
244.7 mm
|
Product Height |
419 mm
|
Product Width |
167.8 mm
|
Product Weight |
10.2 kg
|
Certifications |
UL report applies to both US and Canada
Specification for general requirements: IEC/EN 61800-2 IEC/EN61800-3 EAC UkrSEPRO UL File No.: E134360 UL508 IEC/EN61800-5 UL CSA-C22.2 No. 274-13 CE Certified by UL for use in Canada RoHS, ISO 9001 CUL IEC/EN 61800-3 Safety requirements: IEC/EN 61800-5 UL Category Control No.: NMMS, NMMS7 C-Tick |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Model Code |
DG1-32017FB-C21C
|
Product Category |
Variable frequency drives
|
Features |
Temperature-controlled fan
Tool-less swapping of fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
DC link choke
Additional PCB protection PC connection Brake chopper Breaking resistance Radio interference suppression filter Control unit Internal DC link Multi-line graphic display IGBT inverter |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Operating mode |
Sensorless vector control (SLV)
Torque regulation Speed control with slip compensation U/f control |
Frame size |
FS2
|
Air volume capacity |
94 m³/h
|
Altitude |
Max. 3000 m
Max. 1000 m Above 1000 m with 1 % derating per 100 m Max. 2000 m for Corner Grounded TN Systems |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-30 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 230 V |
10 kVA
|
Apparent power at 240 V |
10.4 kVA
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
15.2 A
|
Assigned motor current IM at 230 V, 50 Hz, 110% overload |
19.6 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
14.8 A
|
Assigned motor current IM at 230 V, 60 Hz, 110% overload |
22 A
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
16.62 W
|
Switch-on threshold for the braking transistor |
425 VDC
|
Voltage rating - max |
240 VAC
|
Overvoltage category |
III
|
Communication interface |
Modbus RTU, built in
Ethernet IP, built in BACnet MS/TP, built in PROFIBUS, optional SmartWire-DT, optional Modbus TCP, built in CANopen®, optional DeviceNet, optional |
Converter type |
U converter
|
Degree of protection |
NEMA 1
IP21 |
Protocol |
PROFINET IO
PROFIBUS TCP/IP MODBUS Other bus systems DeviceNet CAN BACnet EtherNet/IP |
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
5 HP
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 230/240 V, 60 Hz, 3-phase, 110 % overload |
7.5 HP
|
Braking resistance |
20 Ω
|
Equipment heat dissipation, current-dependent Pvid |
229 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 110% overload |
23.2 A
|
Input current ILN at 150% overload |
16.2 A
|
Mains current distortion |
33.3 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
2 (expansion)
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit Adjustable to 150 %, DC - Main circuit |
Cable length |
C2 ≤ 10 m, Radio interference level, maximum motor cable length
150 m, screened, maximum permissible, Motor feeder C3 ≤ 50 m, Radio interference level, maximum motor cable length |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
240 V AC, 3-phase
230 V AC, 3-phase |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter, for conducted emissions only |
Number of outputs (digital) |
1
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Number of phases (output) |
3
|
Power consumption |
229 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
97.4 % (η)
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
6 mA
|
Mains voltage - max |
240 V
|
Mains voltage - min |
208 V
|
Nominal output current I2N |
17.5 A
|
Number of HW-interfaces (industrial ethernet) |
1
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|
Output at linear load at rated output voltage - max |
3.7 kW
|
Output at quadratic load at rated output voltage - max |
5.5 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
240 V
|
Overload current IL at 110% overload |
27.5 A
|
Overload current IL at 150% overload |
26.25 A
|
Shock resistance |
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
Storage and transportation: maximum 15 g, 11 ms (inside the packaging) UPS drop test (for weights inside the UPS frame) |
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
4 kHz, 1 - 12 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
240 V AC, 3-phase
230 V AC, 3-phase |
Short-circuit protection rating |
30 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Vibration |
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) |
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
25 A
|
Rated operational current (Ie) at 150% overload |
17.5 A
|
Rated operational current for specified heat dissipation (In) |
17.5 A
|
Rated operational power at 220/230 V, 50 Hz, 1-phase |
4 kW
|
Rated operational power at 220/230 V, 50 Hz, 3-phase, 110% overload |
5.5 kW
|
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Heat dissipation at current/speed |
101 W at 100% current and 50% speed