Eaton DG1 Variable frequency drive, 230 V AC, 3-phase, 88 A, 22 kW, IP21/NEMA1, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
9701-4001-00P
|
EAN |
4015081735037
|
Product Length/Depth |
294 mm
|
Product Height |
630 mm
|
Product Width |
237.7 mm
|
Product Weight |
34 kg
|
Certifications |
CSA-C22.2 No. 274-13
Certified by UL for use in Canada IEC/EN61800-5 CE UL508 UL Category Control No.: NMMS, NMMS7 Safety requirements: IEC/EN 61800-5 RoHS, ISO 9001 UkrSEPRO C-Tick IEC/EN 61800-3 IEC/EN61800-3 Specification for general requirements: IEC/EN 61800-2 UL EAC CUL UL File No.: E134360 UL report applies to both US and Canada |
Model Code |
DG1-32088FN-C21C
|
Product Category |
Variable frequency drives
|
Features |
Temperature-controlled fan
Externally accessible fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
DC link choke
Multi-line graphic display Control unit Internal DC link PC connection Radio interference suppression filter Additional PCB protection IGBT inverter |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Operating mode |
Speed control with slip compensation
U/f control Sensorless vector control (SLV) Torque regulation |
Frame size |
FS4
|
Air volume capacity |
260 m³/h
|
Altitude |
Max. 3000 m
Above 1000 m with 1 % derating per 100 m Max. 1000 m Max. 2000 m for Corner Grounded TN Systems |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-30 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 230 V |
45.4 kVA
|
Apparent power at 240 V |
47.4 kVA
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
80 A
|
Assigned motor current IM at 230 V, 50 Hz, 110% overload |
96 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
71 A
|
Assigned motor current IM at 230 V, 60 Hz, 110% overload |
104 A
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
17.1 W
|
Switch-on threshold for the braking transistor |
425 VDC
|
Voltage rating - max |
240 VAC
|
Overvoltage category |
III
|
Communication interface |
Ethernet IP, built in
BACnet MS/TP, built in DeviceNet, optional PROFIBUS, optional SmartWire-DT, optional Modbus RTU, built in Modbus TCP, built in CANopen®, optional |
Converter type |
U converter
|
Degree of protection |
IP21
NEMA 1 |
Protocol |
BACnet
Other bus systems DeviceNet TCP/IP CAN PROFIBUS PROFINET IO EtherNet/IP MODBUS |
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
30 HP
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 230/240 V, 60 Hz, 3-phase, 110 % overload |
40 HP
|
Braking resistance |
3.3 Ω
|
Equipment heat dissipation, current-dependent Pvid |
1167 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 110% overload |
94.3 A
|
Input current ILN at 150% overload |
81.4 A
|
Mains current distortion |
25.6 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
2 (expansion)
|
Braking torque |
Adjustable to 150 %, DC - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Max. 30 % MN, Standard - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit |
Cable length |
C3 ≤ 50 m, Radio interference level, maximum motor cable length
200 m, screened, maximum permissible, Motor feeder C2 ≤ 10 m, Radio interference level, maximum motor cable length |
Output voltage (U2) |
230 V AC, 3-phase
240 V AC, 3-phase |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: with external filter, for conducted emissions only Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Number of outputs (digital) |
1
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Number of phases (output) |
3
|
Power consumption |
1167 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
97.4 % (η)
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
6.2 mA
|
Mains voltage - max |
240 V
|
Mains voltage - min |
208 V
|
Nominal output current I2N |
88 A
|
Number of HW-interfaces (industrial ethernet) |
1
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|
Output at linear load at rated output voltage - max |
22 kW
|
Output at quadratic load at rated output voltage - max |
30 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
240 V
|
Overload current IL at 110% overload |
125.4 A
|
Overload current IL at 150% overload |
132 A
|
Shock resistance |
Storage and transportation: maximum 15 g, 11 ms (inside the packaging)
UPS drop test (for weights inside the UPS frame) Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 |
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
3.6 kHz, 1 - 10 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
230 V AC, 3-phase
240 V AC, 3-phase |
Short-circuit protection rating |
125 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Vibration |
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude |
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
114 A
|
Rated operational current (Ie) at 150% overload |
88 A
|
Rated operational current for specified heat dissipation (In) |
88 A
|
Rated operational power at 220/230 V, 50 Hz, 1-phase |
22 kW
|
Rated operational power at 220/230 V, 50 Hz, 3-phase, 110% overload |
30 kW
|
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Heat dissipation at current/speed |
1185 W at 100% current and 90% speed
303 W at 25% current and 0% speed 388 W at 25% current and 50% speed 408 W at 100% current and 50% speed 533 W at 50% current and 50% speed 612 W at 50% current and 90% speed 753 W at 100% current and 0% speed 994 W at 50% current and 0% speed |