Download document () of 20
To be discontinued

290450
Model code: XIO-EXT121-1

Eaton XIOC Expansion for compact PLC XC-CPU121, 10DI, 8DI/DO(T), 6AI, 2AO

General specifications

Product Name
Eaton XIOC Insulated enclosure
Catalog Number
290450
EAN
4015082904500
Product Length/Depth
100 mm
Product Height
100 mm
Product Width
60 mm
Product Weight
0.195 kg
Certifications
CE
UL File No.: E135462
EN 50178
UL
Shipping classification (DNV, GL, ABS, BV, LR)
CSA Class No.: 2252-01
CSA-C22.2 No. 142-M
UL/CSA
UL508
CSA File No.: 012528
IEC/EN 61131-2
CSA-C22.2 No. 0-M
UL Category Control No.: NRAQ
CSA
Model Code
XIO-EXT121-1

Features & Functions

Electric connection type
Plug-in connection
Features
Analog input, current
Analog input, resistor temperature
Analog input, voltage
Analog output, voltage
Functions
Digital in-/outputs, configurable
Overvoltage protection

General

Admissible range
20.4 - 28.8 V DC, Rated voltage for the digital outputs
Degree of protection
IP20
Duty factor
100 % (Digital outputs)
Operating frequency
40000 Operations/h at resistive load
Overvoltage category
II
Pollution degree
2
Repetition rate
1 s
Residual current
0.1 mA (on signal "1" per channel)
Residual ripple
5 % (digital outputs)
≤ 5 %
Resistance
10 kΩ (impedance)
18.5 - 175.8 Ω (Pt100)
Resolution
  • 10 Bit
  • 12 Bit (Analog outputs, voltage)
Voltage type
DC

Ambient conditions, mechanical

Mounting position
Horizontal
Shock resistance
15 g, Mechanical, Shock duration 11 ms
Vibration resistance
9 - 150 Hz, 1 g constant acceleration
5 - 9 Hz, Amplitude 3.5 mm

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-25 °C
Ambient storage temperature - max
70 °C
Operating temperature - min
-200 °C
Operating temperature - max
200 °C
Relative humidity
10 - 95 % (non-condensing)

Electro magnetic compatibility

Emitted interference
According to IEC/EN 61000-6-4
Interference immunity
According to EN 61000-6-2
Voltage dips
10 ms

Terminal capacities

Terminal capacity
0.5 - 1.0 mm², solid/stranded, Spring-loaded terminal block, 20-pole, B2L 3.5 (Weidmüller)
0.5 - 1.0 mm², solid, Spring-loaded terminal block, 10-pole, BLZF 3.5/180 or BLI/O 3.5/10F with LEDs (Weidmüller)
Terminals
Plug in spring-cage terminals

Electrical rating

Inrush current
Max. 1 A
Peak short-circuit current
32 A
Power consumption
Max. 1.68 W
Power loss
Max. 1.7 W
Rated insulation voltage (Ui)
500 V
Rated operational current (Ie)
0.5 A at 24 V AC (state "1")
3.3 mA (on signal "1")
Rated operational voltage
24 V DC
> 15 V DC on 1 signal
< 5 V DC on 0 signal
Short-circuit tripping current
0.7 ≤ Ie ≤ 2 per output, For Ra ≤ 10 mΩ, Digital outputs
16 A, Total, Digital outputs
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
20.4 VDC
Supply voltage at DC - max
28.8 VDC

Communication

Connection type
Spring-loaded terminal block, 20-pole, B2L 3.5 (Weidmüller), X1 plug
Spring-loaded terminal block, 10-pole, BLZF 3.5/180 or BLI/O 3.5/10F with LEDs (Weidmüller), X2/X3 plug

Input/Output

Accuracy
≤ ± 1 % (of end of scale), Analog inputs/Analog outputs
≤ ± 2 %, Pt 100
Conversions
5 ms
Delay time
Off 24 V → 0 V
20 µs, Digital inputs, On 0 V -> 24 V
20 ms, Digital inputs
250 µs, Digital inputs
Input
6 analog inputs (0 - 10V: 2, 0 - 20 mA: 2 or Pt100: 2)
8 additional digital inputs (can also be used as outputs)
10 digital inputs (6 can also be used as interrupts)
Input current
70 mA
Input current at signal 1
0 mA
Input impedance
50 Ω
200 kΩ
Input voltage
24 V DC (Power supply of local inputs/outputs)
24 V DC (Power supply)
0 - 10 V
Lamp load
5 W (without Rv per channel)
Number of inputs (analog)
2
Number of inputs (digital)
X3: 8 (can also be used as outputs)
X2: 9 with plug BLI/O 3.5/10F or 10 with plug BLZF 3.5/180
8
Number of outputs (analog)
2
Number of outputs (digital)
8
Output
Parallel switching
8 Digital Outputs (also usable as inputs)
2 Analog Outputs (0 - 10 V)
Output current
2 A
Output voltage
U = Uₑ - 1 V (signal 1 at Iₑ = 0.5 A, transistor outputs)
Max. 2.5 V (at signal 0 at external load < 10 MΩ, transistor outputs)
0 - 10 V
Rapid counter inputs
With X3: 8 (can also be used as inputs)
Utilization factor
1

Safety

Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Between Digital inputs: no
Digital outputs: no
X2 Interface: DI4 - DI9: no
Protection against polarity reversal
Yes

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.7 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Export product specification