下載文件 () / 20

104455

Eaton Moeller® series DILMF Contactors for Semiconductor Industries acc. to SEMI F47, 380 V 400 V: 32 A, 1 NC, RAC 48: 42 - 48 V 50/60 Hz, Screw terminals

常用規格

Product Name
Eaton Moeller® series DILMF contactor for semiconductor industries
Catalog Number
104455
Product Length/Depth
97 mm
Product Height
85 mm
Product Width
45 mm
Product Weight
0.531 kg
Certifications
UL File No.: E29096
CSA
UL
CSA-C22.2 No. 60947-4-1-14
CE
UL Category Control No.: NLDX
IEC/EN 60947-4-1
UL 60947-4-1
CSA File No.: 012528
CSA Class No.: 2411-03, 3211-04
Catalog Notes
Also tested according to AC-3e.

特色 & 功能

Fitted with:
Built-in suppressor circuit
Mirror contact
Number of poles
Three-pole

一般

Application
Contactors for Semiconductor Industries acc. to SEMI F47
Product category
Contactors
Resistance per pole
2.65 mΩ
Suitable for
SEMI F47, Magnet systems
Also motors with efficiency class IE3
Utilization category
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running
Voltage type
AC

天候環境狀況

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C

電磁相容性

Emitted interference
According to EN 60947-1
Interference immunity
According to EN 60947-1

電力額定值

Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V
45 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V
32 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
32 A
Rated operational current (Ie) at AC-3, 440 V
32 A
Rated operational current (Ie) at AC-3, 500 V
32 A
Rated operational current (Ie) at AC-3, 660 V, 690 V
18 A
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V
15 A
Rated operational current (Ie) at AC-4, 400 V
15 A
Rated operational current (Ie) at AC-4, 500 V
15 A
Rated operational current (Ie) at AC-4, 660 V, 690 V
12 A

匯出產品規格