Eaton Moeller® series M22 Combination of contact element and self-monitoring contact element M22-K01SMC10 with screw terminals, M22-A mounting adapter, and M22-XSMC signaling contact actuator, 2 N/O, 2 NC
Product Name |
Eaton Moeller® series M22 Accessory Contact element
|
Catalog Number |
173027
|
Model Code |
M22-AK12SMC10
|
EAN |
4015081696185
|
Product Length/Depth |
40.2 mm
|
Product Height |
32.5 mm
|
Product Width |
47 mm
|
Product Weight |
0.047 kg
|
Certifications |
UL File No.: E340491
CSA-C22.2 No. 14-05 CSA Class No.: 3211-03 CE CSA UL CSA-C22.2 No. 94-91 UL Category Control No.: NISD CSA File No.: 012528_C_000 IEC 60947-5-1 IEC/EN 60947-5 UL 508 |
Electric connection type |
Screw connection
|
Degree of protection |
IP20
|
Model |
Top mounting
|
Mounting method |
Front fastening
|
Operating torque |
0.8 Nm
|
Overvoltage category |
III
|
Pollution degree |
3
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
70 °C
|
Ambient storage temperature - min |
-25 °C
|
Ambient storage temperature - max |
85 °C
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Terminal capacity (flexible with ferrule) |
0.5 - 1.5 mm²
|
Terminal capacity (solid) |
0.75 - 2.5 mm²
|
Terminal capacity (stranded) |
0.5 - 2.5 mm²
|
Rated insulation voltage (Ui) |
500 V
|
Rated operational current (Ie) at AC-15, 115 V |
6 A
|
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V |
6 A
|
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V |
4 A
|
Rated operational current (Ie) at AC-15, 500 V |
2 A
|
Rated operational current (Ie) at DC-13, 110 V |
0.6 A
|
Rated operational current (Ie) at DC-13, 220 V, 230 V |
0.3 A
|
Rated operational current (Ie) at DC-13, 24 V |
3 A
|
Rated operational current (Ie) at DC-13, 42 V |
1.7 A
|
Rated operational current (Ie) at DC-13, 60 V |
1.2 A
|
Rated operational current (Ie) at DC-13, 500 V |
0.1 A
|
Short-circuit protection |
PKZM0-10/FAZ-B6/1, Contacts, Max. short-circuit protective device, Fuseless
|
Short-circuit protection rating |
Max. 10 A gG/gL, Fuse, Contacts
|
Connection to SmartWire-DT |
No
|
Connection type |
Front fixing
Screw connection |
Actuating force - max |
15 N
|
Force for positive opening - min |
0 N
|
Number of contacts (change-over contacts) |
0
|
Number of contacts (normally closed contacts) |
2
|
Number of contacts (normally open contacts) |
1
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0.11 W
|
Rated operational current for specified heat dissipation (In) |
6 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|