Eaton Moeller series Power Defense - Molded Case Circuit Breaker. Circuit-breaker LZM, 4 p, 63A, N1-4-A63-I
Product Name |
Eaton Moeller series Power Defense molded case circuit-breaker
|
Catalog Number |
174429
|
Model Code |
LZMN1-4-A63-I
|
EAN |
4015081708918
|
Product Length/Depth |
84.5 mm
|
Product Height |
145 mm
|
Product Width |
120 mm
|
Product Weight |
1.318 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC
IEC/EN 60947 VDE 0660 |
Circuit breaker frame type |
LZM1
|
Application |
Use in unearthed supply systems at 690 V
|
Amperage Rating |
63 A
|
Number of poles |
Four-pole
|
Voltage rating |
690 V - 690 V
|
Voltage rating (DC) |
500 VDC
|
Rated insulation voltage (Ui) |
690 V AC
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
6000 V
|
Rated operational current |
160 A (690 V AC-1, making and breaking capacity)
125 A (415 V AC-1, making and breaking capacity) 63 A (660-690 V AC-3, making and breaking capacity) 125 A (500 V DC-1, making and breaking capacity) 63 A (415 V AC-3, making and breaking capacity) 160 A (380/400 V AC-1, making and breaking capacity) 125 A (500 V DC-3, making and breaking capacity) |
Current rating of neutral conductor |
200% of phase conductor
|
Instantaneous current setting (Ii) - min |
380 A
|
Instantaneous current setting (Ii) - max |
630 A
|
Overload current setting (Ir) |
50 A - 63 A
|
Overload current setting (Ir) - min |
50 A
|
Overload current setting (Ir) - max |
63 A
|
Short delay current setting (Isd) - min |
0 A
|
Short delay current setting (Isd) - max |
0 A
|
Short-circuit release non-delayed setting - min |
378 A
|
Short-circuit release non-delayed setting - max |
630 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
85 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
50 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
35 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz |
10 kA
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
187 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
105 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
74 kA
|
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz |
40 kA
|
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz |
17 kA
|
Short-circuit total breaktime |
< 10 ms
|
Electrical connection type of main circuit |
Frame clamp
|
Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
Overvoltage category |
III
|
Utilization category |
A (IEC/EN 60947-2)
|
Pollution degree |
3
|
Lifespan, electrical |
7500 operations at 415 V AC-3
10000 operations at 415 V AC-1 10000 operations at 400 V AC-1 5000 operations at 500 V DC-3 7500 operations at 690 V AC-1 10000 operations at 500 V DC-1 5000 operations at 690 V AC-3 7500 operations at 400 V AC-3 |
Type |
Circuit breaker
|
Release system |
Thermomagnetic release
|
Mounting Method |
DIN rail (top hat rail) mounting optional
Fixed Built-in device fixed built-in technique |
Degree of protection |
IP20
In the area of the HMI devices: IP20 (basic protection type) |
Degree of protection (IP), front side |
IP40 (with insulating surround)
IP66 (with door coupling rotary handle) |
Degree of protection (terminations) |
IP00 (terminations, phase isolator and band terminal)
IP10 (tunnel terminal) |
Protection against direct contact |
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
|
Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Number of operations per hour - max |
120
|
Handle type |
Rocker lever
|
Position of connection for main current circuit |
Front side
|
Direction of incoming supply |
As required
|
Standard terminals |
Box terminal
|
Terminal capacity (control cable) |
0.75 mm² - 1.5 mm² (2x)
0.75 mm² - 2.5 mm² (1x) |
Terminal capacity (aluminum solid conductor/cable) |
16 mm² (1x) at tunnel terminal
|
Terminal capacity (copper busbar) |
Max. 16 mm x 5 mm direct at switch rear-side connection
M8 at rear-side screw connection Min. 12 mm x 5 mm direct at switch rear-side connection |
Terminal capacity (copper solid conductor/cable) |
10 mm² - 16 mm² (1x) direct at switch rear-side connection
6 mm² - 16 mm² (2x) at box terminal 6 mm² - 16 mm² (2x) direct at switch rear-side connection 10 mm² - 16 mm² (1x) at box terminal 16 mm² - 95 mm² (1x) at tunnel terminal |
Terminal capacity (copper stranded conductor/cable) |
25 mm² - 70 mm² (1x) at box terminal
25 mm² (2x) direct at switch rear-side connection 25 mm² (2x) at box terminal 25 mm² - 70 mm² (1x) direct at switch rear-side connection 25 mm² - 95 mm² (1x) at tunnel terminal |
Terminal capacity (copper strip) |
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 9 segments of 9 mm x 0.8 mm at box terminal |
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Lifespan, mechanical |
20000 operations
|
Rated operational current for specified heat dissipation (In) |
63 A
|
Equipment heat dissipation, current-dependent |
14.17 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
Features |
Protection unit
|
Functions |
System and cable protection
|
Special features |
|