Eaton Moeller® series DILM Contactor, 3 pole, 380 V 400 V 3 kW, 1 N/O, 220 V 50/60 Hz, AC operation, Push in terminals
Product Name |
Eaton Moeller® series DILM contactor
|
Catalog Number |
199643
|
Model Code |
DILM7-10(220V50/60HZ)-PI
|
EAN |
4015081983445
|
Product Length/Depth |
75 mm
|
Product Height |
68 mm
|
Product Width |
45 mm
|
Product Weight |
0.225 kg
|
Certifications |
IEC/EN 60947
VDE 0660 |
Number of poles |
Three-pole
|
Application |
Contactors for Motors
|
Degree of protection |
IP20
|
Frame size |
FS1
|
Lifespan, mechanical |
10,000,000 Operations (AC operated)
|
Connection |
Push in terminals
|
Operating frequency |
9000 mechanical Operations/h (AC operated)
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Contactors
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Suitable for |
Also motors with efficiency class IE3
|
Utilization category |
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-3: Normal AC induction motors: starting, switch off during running AC-1: Non-inductive or slightly inductive loads, resistance furnaces |
Voltage type |
AC
|
Shock resistance |
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 3.4 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 3.4 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 5.7 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Emitted interference |
According to EN 60947-1
|
Interference immunity |
According to EN 60947-1
|
Terminal capacity (flexible with unisolated ferrule) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
Terminal capacity (flexible with ferrule) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 1.5) mm² |
Terminal capacity (flexible) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
Terminal capacity (solid) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
Terminal capacity (solid/stranded AWG) |
20 - 14
|
Stripping length (main cable) |
10 mm
|
Screwdriver size |
3 x 0.5 mm, Terminal screw
3.0 x 0.5 mm, Terminal screw |
Rated breaking capacity at 220/230 V |
70 A
|
Rated breaking capacity at 380/400 V |
70 A
|
Rated breaking capacity at 500 V |
50 A
|
Rated breaking capacity at 660/690 V |
40 A
|
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
22 A
|
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
7 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
7 A
|
Rated operational current (Ie) at AC-3, 440 V |
7 A
|
Rated operational current (Ie) at AC-3, 500 V |
5 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
4 A
|
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V |
5 A
|
Rated operational current (Ie) at AC-4, 440 V |
5 A
|
Rated operational current (Ie) at AC-4, 500 V |
4.5 A
|
Rated operational current (Ie) at AC-4, 660 V, 690 V |
4 A
|
Rated operational current (Ie) at DC-1, 60 V |
20 A
|
Rated operational current (Ie) at DC-1, 110 V |
20 A
|
Rated operational current (Ie) at DC-1, 220 V |
15 A
|
Rated insulation voltage (Ui) |
690 V
|
Rated making capacity up to 690 V (cos phi to IEC/EN 60947) |
112 A
|
Rated operational power at AC-3, 240 V, 50 Hz |
2.2 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
3 kW
|
Rated operational power at AC-3, 415 V, 50 Hz |
4 kW
|
Rated operational power at AC-4, 220/230 V, 50 Hz |
1 kW
|
Rated operational power at AC-4, 240 V, 50 Hz |
1.5 kW
|
Rated operational power at AC-4, 415 V, 50 Hz |
2.3 kW
|
Rated operational power at AC-4, 440 V, 50 Hz |
2.4 kW
|
Rated operational power at AC-4, 500 V, 50 Hz |
2.5 kW
|
Rated operational power at AC-4, 660/690 V, 50 Hz |
2.9 kW
|
Rated operational voltage (Ue) at AC - max |
690 V
|
Short-circuit protection rating (type 1 coordination) at 400 V |
35 A gG/gL
|
Short-circuit protection rating (type 1 coordination) at 690 V |
20 A gG/gL
|
Short-circuit protection rating (type 2 coordination) at 400 V |
20 A gG/gL
|
Short-circuit protection rating (type 2 coordination) at 690 V |
16 A gG/gL
|
Conventional thermal current Ith (1-pole, enclosed) |
45 A
|
Conventional thermal current Ith (3-pole, enclosed) |
18 A
|
Conventional thermal current Ith at 55°C (3-pole, open) |
21 A
|
Conventional thermal current Ith of main contacts (1-pole, open) |
50 A
|
Arcing time |
10 ms
|
Drop-out voltage |
AC operated: 0.6 - 0.3 x UC, AC operated
|
Duty factor |
100 %
|
Pick-up voltage |
0.8 - 1.1 V AC x Uc
|
Power consumption, pick-up, 50 Hz |
27 VA, Dual-frequency coil in a cold state and 1.0 x Us
|
Power consumption, pick-up, 60 Hz |
25 VA, Dual-frequency coil in a cold state and 1.0 x Us
|
Power consumption, sealing, 50 Hz |
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us
1.2 W, Dual-frequency coil in a cold state and 1.0 x Us |
Power consumption, sealing, 60 Hz |
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us
3.3 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz 1.2 W, Dual-frequency coil in a cold state and 1.0 x Us 4.2 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
Rated control supply voltage (Us) at AC, 50 Hz - min |
220 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
220 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
220 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
220 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Switching time (AC operated, make contacts, closing delay) - min |
15 ms
|
Switching time (AC operated, make contacts, closing delay) - max |
21 ms
|
Switching time (AC operated, make contacts, opening delay) - min |
9 ms
|
Switching time (AC operated, make contacts, opening delay) - max |
18 ms
|
Connection to SmartWire-DT |
No
|
Number of contacts (normally open contacts) |
1
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
1
|
Safe isolation |
400 V AC, Between the contacts, According to EN 61140
400 V AC, Between coil and contacts, According to EN 61140 |
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|