Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 5A, B1-S5-CNA
| Product Name |
Eaton Moeller series NZM molded case circuit breaker magnetic
|
| Catalog Number |
102909
|
| Product Length/Depth |
88 mm
|
| Product Height |
165.5 mm
|
| Product Width |
90 mm
|
| Product Weight |
1.046 kg
|
| Compliances |
RoHS conform
|
| Certifications |
Specially designed for North America
UL (Category Control Number DKPU2) CSA-C22.2 No. 5-09 UL listed UL (File No. E31593) CSA (File No. 22086) UL/CSA CSA certified UL 489 CSA (Class No. 1432-01) |
| Voltage rating |
440 V - 440 V
|
| Rated operating voltage Ue (UL) - max |
480 Y / 277 V
|
| Rated insulation voltage (Ui) |
690 V
|
| Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
| Rated impulse withstand voltage (Uimp) at main contacts |
6000 V
|
| Amperage Rating |
5 A
|
| Instantaneous current setting (Ii) - min |
30 A
|
| Instantaneous current setting (Ii) - max |
55 A
|
| Short-circuit release non-delayed setting - min |
30 A
|
| Short-circuit release non-delayed setting - max |
55 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
25 kA
|
| Rated operating power at AC-3, 230 V |
1.1 kW
|
| Rated operating power at AC-3, 400 V |
2.2 kW
|
| Short-circuit total breaktime |
< 10 ms
|
| Electrical connection type of main circuit |
Other
|
| Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
| Number of operations per hour - max |
120
|
| Handle type |
Rocker lever
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Lifespan, electrical |
7500 operations at 415 V AC-3
|
| Direction of incoming supply |
As required
|
| Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
| Rated impulse withstand voltage (Uimp) at main contacts |
6000 V
|
| Amperage Rating |
5 A
|
| Instantaneous current setting (Ii) - min |
30 A
|
| Instantaneous current setting (Ii) - max |
55 A
|
| Short-circuit release non-delayed setting - min |
30 A
|
| Short-circuit release non-delayed setting - max |
55 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
25 kA
|
| Rated operating power at AC-3, 230 V |
1.1 kW
|
| Rated operating power at AC-3, 400 V |
2.2 kW
|
| Short-circuit total breaktime |
< 10 ms
|
| Electrical connection type of main circuit |
Other
|
| Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
| Number of operations per hour - max |
120
|
| Handle type |
Rocker lever
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Lifespan, electrical |
7500 operations at 415 V AC-3
|
| Direction of incoming supply |
As required
|
| Mounting Method |
Fixed
Built-in device fixed built-in technique |
| Degree of protection |
IP20
IP20 (basic degree of protection, in the operating controls area) |
| Degree of protection (IP), front side |
IP66 (with door coupling rotary handle)
IP40 (with insulating surround) |
| Degree of protection (terminations) |
IP00 (terminations, phase isolator and strip terminal)
IP10 (tunnel terminal) |
| Protection against direct contact |
Finger and back-of-hand proof to VDE 0106 part 100
|
| Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
| Switch off technique |
Magnetic
|
| Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
| Lifespan, mechanical |
20000 operations
|