下載文件 () / 20

104408

Eaton Moeller® series DILL Lamp load contactor, 230 V 50 Hz, 240 V 60 Hz, 220 V 230 V: 20 A, Contactors for lighting systems

常用規格

Product Name
Eaton Moeller® series DILL lamp load contactor
Catalog Number
104408
Product Length/Depth
97 mm
Product Height
85 mm
Product Width
45 mm
Product Weight
0.426 kg
Compliances
CE Marked
Certifications
IEC 60947-4-1
EN 60947-4-1
CSA Std. C22.2 No. 14-05
UL 508
VDE
CE
CSA Class No.: 3211-04
VDE 0660
CSA-C22.2 No. 60947-4-1-14
UL Category Control No.: NLDX
IEC/EN 60947
CSA File No.: 012528
CSA
IEC/EN 60947-4-1
UL 60947-4-1
UL
UL File No.: E29096

特色 & 功能

Number of poles
Three-pole

一般

Application
Contactors for lighting systems
Lifespan, electrical
10,000 Operations
Lifespan, mechanical
1,000,000 Operations (AC operated)
Operating frequency
60 mechanical Operations/h (AC operated)
60 electrical Operations/h
Overvoltage category
III
Pollution degree
3
Product category
DILL Lighting contactors
Rated impulse withstand voltage (Uimp)
8000 V AC
Resistance per pole
2.65 mΩ
Utilization category
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Voltage type
AC

環境條件,機械

Shock resistance
6.9 g, N/O main contact, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

天候環境狀況

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient operating temperature (enclosed) - min
-25 °C
Ambient operating temperature (enclosed) - max
40 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
80 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78

電磁相容性

Emitted interference
According to EN 60947-1
Interference immunity
According to EN 60947-1

電力額定值

Permissible compensation capacity
470 µF
Rated breaking capacity at 380/400 V
320 A
Rated operational current (Ie)
23 A (Mercury blended lamps)
12 A (Low-pressure sodium lamps)
20 A (High-pressure mercury vapor lamps)
27 A at AC-3, 220/230 V
35 A (Conventional reactor starter circuit)
20 A at AC-1, 220 V 230 V
20 A (Electronic upstream devices)
20 A (High-pressure sodium lamps)
20 A at AC-1, 380 V 400 V
27 A (Filament bulbs)
35 A (Fluorescent lamp load - duo circuit)
20 A (Metal-halide lamps)
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V
20 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
0 A
Rated operational current (Ie) at AC-4, 400 V
0 A

匯出產品規格