Eaton Moeller® series DILMF Contactors for Semiconductor Industries acc. to SEMI F47, 380 V 400 V: 25 A, 1 NC, RAC 120: 100 - 120 V 50/60 Hz, Screw terminals
| Product Name |
Eaton Moeller® series DILMF contactor for semiconductor industries
|
| Catalog Number |
104448
|
| Product Length/Depth |
97 mm
|
| Product Height |
85 mm
|
| Product Width |
45 mm
|
| Product Weight |
0.531 kg
|
| Certifications |
UL 60947-4-1
CSA-C22.2 No. 60947-4-1-14 CSA Class No.: 2411-03, 3211-04 CSA File No.: 012528 UL Category Control No.: NLDX IEC/EN 60947-4-1 UL CE CSA UL File No.: E29096 |
| Catalog Notes |
Also tested according to AC-3e.
|
| Fitted with: |
Built-in suppressor circuit
Mirror contact |
| Number of poles |
Three-pole
|
| Application |
Contactors for Semiconductor Industries acc. to SEMI F47
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Product category |
Contactors
|
| Resistance per pole |
2.65 mΩ
|
| Suitable for |
Also motors with efficiency class IE3
SEMI F47, Magnet systems |
| Utilization category |
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-3: Normal AC induction motors: starting, switch off during running |
| Voltage type |
AC
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
60 °C
|
| Ambient operating temperature (enclosed) - min |
-25 °C
|
| Ambient operating temperature (enclosed) - max |
40 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
80 °C
|
| Emitted interference |
According to EN 60947-1
|
| Interference immunity |
According to EN 60947-1
|
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
45 A
|
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
25 A
|
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
25 A
|
| Rated operational current (Ie) at AC-3, 440 V |
25 A
|
| Rated operational current (Ie) at AC-3, 500 V |
25 A
|
| Rated operational current (Ie) at AC-3, 660 V, 690 V |
15 A
|
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V |
13 A
|
| Rated operational current (Ie) at AC-4, 400 V |
13 A
|
| Rated operational current (Ie) at AC-4, 500 V |
13 A
|
| Rated operational current (Ie) at AC-4, 660 V, 690 V |
10 A
|