Eaton Moeller® series DILMF Contactors for Semiconductor Industries acc. to SEMI F47, 380 V 400 V: 40 A, RAC 120: 100 - 120 V 50/60 Hz, Screw terminals
| Product Name |
Eaton Moeller® series DILMF contactor for semiconductor industries
|
| Catalog Number |
104460
|
| Product Length/Depth |
132.1 mm
|
| Product Height |
115 mm
|
| Product Width |
55 mm
|
| Product Weight |
1.04 kg
|
| Certifications |
UL
UL File No.: E29096 CSA-C22.2 No. 60947-4-1-14 CSA File No.: 012528 CSA IEC/EN 60947-4-1 UL 60947-4-1 UL Category Control No.: NLDX CE CSA Class No.: 2411-03, 3211-04 |
| Catalog Notes |
Also tested according to AC-3e.
|
| Fitted with: |
Built-in suppressor circuit
|
| Number of poles |
Three-pole
|
| Application |
Contactors for Semiconductor Industries acc. to SEMI F47
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Product category |
Contactors
|
| Resistance per pole |
1.86 mΩ
|
| Suitable for |
SEMI F47, Magnet systems
Also motors with efficiency class IE3 |
| Utilization category |
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
| Voltage type |
AC
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
60 °C
|
| Ambient operating temperature (enclosed) - min |
-25 °C
|
| Ambient operating temperature (enclosed) - max |
40 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Ambient storage temperature - max |
80 °C
|
| Emitted interference |
According to EN 60947-1
|
| Interference immunity |
According to EN 60947-1
|
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
60 A
|
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
40 A
|
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
40 A
|
| Rated operational current (Ie) at AC-3, 440 V |
40 A
|
| Rated operational current (Ie) at AC-3, 500 V |
40 A
|
| Rated operational current (Ie) at AC-3, 660 V, 690 V |
25 A
|
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V |
18 A
|
| Rated operational current (Ie) at AC-4, 400 V |
18 A
|
| Rated operational current (Ie) at AC-4, 500 V |
18 A
|
| Rated operational current (Ie) at AC-4, 660 V, 690 V |
14 A
|