Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 200A, box terminals, B2-S200-BT-CNA
Product Name |
Eaton Moeller series NZM molded case circuit breaker magnetic
|
Catalog Number |
107666
|
Product Length/Depth |
149 mm
|
Product Height |
195 mm
|
Product Width |
105 mm
|
Product Weight |
2.345 kg
|
Compliances |
RoHS conform
|
Certifications |
UL/CSA
UL (File No. E31593) UL 489 UL (Category Control Number DKPU2) IEC 60947-2 IEC/EN 60947 CSA certified Specially designed for North America CSA (File No. 22086) CE marking CSA-C22.2 No. 5-09 CSA (Class No. 1432-01) UL listed IEC |
Voltage rating |
440 V - 440 V
|
Rated operational current |
300 A (415 V AC-1, making and breaking capacity)
300 A (380/400 V AC-1, making and breaking capacity) 200 A (660-690 V AC-3, making and breaking capacity) |
Amperage Rating |
200 A
|
Short-circuit total breaktime |
< 10 ms
|
Electrical connection type of main circuit |
Frame clamp
|
Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
Utilization category |
A (IEC/EN 60947-2)
|
Overvoltage category |
III
|
Pollution degree |
3
|
Lifespan, electrical |
7500 operations at 400 V AC-1
6500 operations at 415 V AC-3 |
Direction of incoming supply |
As required
|
Rated operational current |
300 A (415 V AC-1, making and breaking capacity)
300 A (380/400 V AC-1, making and breaking capacity) 200 A (660-690 V AC-3, making and breaking capacity) |
Amperage Rating |
200 A
|
Short-circuit total breaktime |
< 10 ms
|
Electrical connection type of main circuit |
Frame clamp
|
Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
Utilization category |
A (IEC/EN 60947-2)
|
Overvoltage category |
III
|
Pollution degree |
3
|
Lifespan, electrical |
7500 operations at 400 V AC-1
6500 operations at 415 V AC-3 |
Direction of incoming supply |
As required
|
Mounting Method |
Fixed
DIN rail (top hat rail) mounting optional Built-in device fixed built-in technique |
Degree of protection |
IP20
IP20 (basic degree of protection, in the operating controls area) |
Degree of protection (IP), front side |
IP40 (with insulating surround)
IP66 (with door coupling rotary handle) |
Degree of protection (terminations) |
IP00 (terminations, phase isolator and strip terminal)
IP10 (tunnel terminal) |
Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Lifespan, mechanical |
20000 operations
|