下載文件 () / 20
我們讓至關重要的事情運作*

192004

Eaton Moeller series NZM - Molded Case Circuit Breaker. NZM2 PXR10 circuit breaker, 3 pole, 160A, screw terminal, N, 2

常用規格

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
192004
Product Length/Depth
190 mm
Product Height
160 mm
Product Width
115 mm
Product Weight
2.3 kg
Compliances
RoHS conform
Certifications
IEC/EN 60947
IEC

技術資料 - 電氣

Voltage rating
690 V - 690 V
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated short-time withstand current (t = 0.3 s)
1.9 kA
Rated short-time withstand current (t = 1 s)
1.9 kA
Amperage Rating
160 A
Instantaneous current setting (Ii) - min
2 A
Instantaneous current setting (Ii) - max
12 A
Overload current setting (Ir) - min
64 A
Overload current setting (Ir) - max
160 A
Short-circuit release non-delayed setting - min
320 A
Short-circuit release non-delayed setting - max
1920 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz
85 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
35 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz
25 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz
5 kA
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz
187 kA
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz
105 kA
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz
74 kA
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz
53 kA
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
40 kA
Short-circuit total breaktime
< 10 ms
Electrical connection type of main circuit
Screw connection
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Number of operations per hour - max
120
Handle type
Rocker lever
Utilization category
A (IEC/EN 60947-2)
Overvoltage category
III
Pollution degree
3
Lifespan, electrical
10000 operations at 415 V AC-1
10000 operations at 400 V AC-1
7500 operations at 690 V AC-1
Direction of incoming supply
As required

技術資料 - 通訊

Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated short-time withstand current (t = 0.3 s)
1.9 kA
Rated short-time withstand current (t = 1 s)
1.9 kA
Amperage Rating
160 A
Instantaneous current setting (Ii) - min
2 A
Instantaneous current setting (Ii) - max
12 A
Overload current setting (Ir) - min
64 A
Overload current setting (Ir) - max
160 A
Short-circuit release non-delayed setting - min
320 A
Short-circuit release non-delayed setting - max
1920 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz
85 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
35 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz
25 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz
5 kA
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz
187 kA
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz
105 kA
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz
74 kA
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz
53 kA
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
40 kA
Short-circuit total breaktime
< 10 ms
Electrical connection type of main circuit
Screw connection
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Number of operations per hour - max
120
Handle type
Rocker lever
Utilization category
A (IEC/EN 60947-2)
Overvoltage category
III
Pollution degree
3
Lifespan, electrical
10000 operations at 415 V AC-1
10000 operations at 400 V AC-1
7500 operations at 690 V AC-1
Direction of incoming supply
As required

技術資料 - 機械

Mounting Method
DIN rail (top hat rail) mounting optional
Fixed
Built-in device fixed built-in technique
Degree of protection
IP20 (basic degree of protection, in the operating controls area)
IP20
Degree of protection (IP), front side
IP66 (with door coupling rotary handle)
IP40 (with insulating surround)
Degree of protection (terminations)
IP00 (terminations, phase isolator and strip terminal)
IP10 (tunnel terminal)
Protection against direct contact
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Front side
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Lifespan, mechanical
20000 operations

匯出產品規格

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

驗證產品

請輸入您的 16-17 位數的序號
您輸入的序號不應包含特殊字元。 您輸入的序號不正確,它應該是 16 位或 17 位的序號。 找不到您輸入的序號。請重試或 回報此問題 以獲得進一步協助。 您輸入的序號與產品不符。請檢查您的產品序號並重試。 點擊 此處 前往您所輸入序號的產品頁面 伊頓已知該序號為「可疑」,請重試或 回報此問題 以獲得進一步協助。
序號
重設 伊頓已知該序號為「可疑」,請重試或 回報此問題 以獲得進一步協助。 伊頓無法辨識此序號,此序號無效。請使用本表單以 回報此問題 以獲得進一步協助。
請輸入 6 位數驗證碼
您輸入的產品有問題!請重試或 回報此問題 以獲得進一步協助。 您輸入的驗證碼與我們的序號記錄不符。請重試,或 回報此問題 以獲得進一步協助。 無效的驗證碼。長度必須為 6 個字元 回報此問題 以獲得進一步協助。 驗證碼為必填 回報此問題 以獲得進一步協助。
驗證之前請先完成 Captcha 驗證。
與我們聯絡 以回報問題
x
回報問題
請輸入您的全名。
x
感謝您,您的問題已提交,我們的產品團隊將盡快聯絡您。
注意:如果 .zip 下載中缺少檔案,則說明此檔案類型不支援大量下載。