Eaton Moeller® series DILM Contactor, 3 pole, 380 V 400 V 7.5 kW, 1 NC, 220 V 50/60 Hz, AC operation, Push in terminals
Product Name |
Eaton Moeller® series DILM contactor
|
Catalog Number |
199657
|
Product Length/Depth |
75 mm
|
Product Height |
68 mm
|
Product Width |
45 mm
|
Product Weight |
0.225 kg
|
Certifications |
VDE 0660
IEC/EN 60947 |
Fitted with: |
Mirror contact
|
Number of poles |
Three-pole
|
Application |
Contactors for Motors
|
Frame size |
FS1
|
Lifespan, mechanical |
10,000,000 Operations (AC operated)
|
Operating frequency |
5000 mechanical Operations/h (AC operated)
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Contactors
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
Voltage type |
AC
|
Shock resistance |
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 3.4 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 3.4 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 5.7 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms |
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Emitted interference |
According to EN 60947-1
|
Interference immunity |
According to EN 60947-1
|
Terminal capacity (flexible with unisolated ferrule) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
Terminal capacity (flexible with ferrule) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 1.5) mm² |
Terminal capacity (flexible) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
Terminal capacity (solid) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
Terminal capacity (solid/stranded AWG) |
20 - 14
|
Stripping length (main cable) |
10 mm
|
Screwdriver size |
3.0 x 0.5 mm, Terminal screw
3 x 0.5 mm, Terminal screw |
Rated breaking capacity at 220/230 V |
124 A
|
Rated breaking capacity at 380/400 V |
124 A
|
Rated breaking capacity at 500 V |
100 A
|
Rated breaking capacity at 660/690 V |
70 A
|
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
22 A
|
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
15.5 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
15.5 A
|
Rated operational current (Ie) at AC-3, 440 V |
15.5 A
|
Rated operational current (Ie) at AC-3, 500 V |
12.5 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
9 A
|
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V |
7 A
|
Rated operational current (Ie) at AC-4, 400 V |
7 A
|
Rated operational current (Ie) at AC-4, 500 V |
6 A
|
Rated operational current (Ie) at AC-4, 660 V, 690 V |
5 A
|
Rated operational current (Ie) at DC-1, 60 V |
20 A
|
Rated operational current (Ie) at DC-1, 110 V |
20 A
|