代表照片
Download
Eaton Moeller series NZM Undervoltage release, 480-525VAC, +2early N/O, for NZM1
Product Name |
Eaton Moeller series NZM Undervoltage release
|
Catalog Number |
259543
|
Product Length/Depth |
37 mm
|
Product Height |
66 mm
|
Product Width |
32 mm
|
Product Weight |
0.056 kg
|
Compliances |
IEC
UL/CSA RoHS conform |
Certifications |
UL (File No. E140305)
CSA (File No. 22086) UL listed CSA (Class No. 1437-01) UL489 UL (Category Control Number DIHS) CSA-C22.2 No. 5-09 CE marking IEC60947 CSA certified |
Voltage type |
AC
|
Rated control voltage (relay contacts) |
525 V AC
480 V AC |
Rated control supply voltage |
480 - 525 V 50/60 Hz
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
480 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
525 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
480 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
525 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Voltage tolerance - min |
0.85
|
Voltage tolerance - max |
1.1
|
Drop-out voltage of undervoltage release AC/DC - min |
0.35 x Us
|
Drop-out voltage of undervoltage release AC/DC - max |
0.7 x Us
|
Power consumption |
1.5 VA (sealing AC)
0.8 W (sealing DC) |
Pick-up power consumption at AC (undervoltage release) |
1.5 VA
|
Pick-up power consumption at DC (undervoltage release) |
0.8 W
|
Reaction time |
19 ms
|
Minimum command time - min |
10 ms
|
Minimum command time - max |
15 ms
|
Electric connection type |
Screw connection
|
Rated control voltage (relay contacts) |
525 V AC
480 V AC |
Rated control supply voltage |
480 - 525 V 50/60 Hz
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
480 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
525 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
480 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
525 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Voltage tolerance - min |
0.85
|
Voltage tolerance - max |
1.1
|
Drop-out voltage of undervoltage release AC/DC - min |
0.35 x Us
|
Drop-out voltage of undervoltage release AC/DC - max |
0.7 x Us
|
Power consumption |
1.5 VA (sealing AC)
0.8 W (sealing DC) |
Pick-up power consumption at AC (undervoltage release) |
1.5 VA
|
Pick-up power consumption at DC (undervoltage release) |
0.8 W
|
Reaction time |
19 ms
|
Minimum command time - min |
10 ms
|
Minimum command time - max |
15 ms
|
Electric connection type |
Screw connection
|
Number of contacts (change-over contacts) |
0
|
Number of contacts (normally closed contacts) |
0
|
Number of contacts (normally open contacts) |
2
|
Connection type |
With terminal block on the left-hand switch side
|