Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 4p, 125A, B, frame2, 4-A125
Product Name |
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
|
Catalog Number |
265847
|
Product Length/Depth |
149 mm
|
Product Height |
184 mm
|
Product Width |
140 mm
|
Product Weight |
3 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC/EN 60947
|
Voltage rating |
440 V - 440 V
|
Current rating of neutral conductor |
200% of phase conductor
|
Amperage Rating |
125 A
|
Instantaneous current setting (Ii) - min |
6 A
|
Instantaneous current setting (Ii) - max |
10 A
|
Overload current setting (Ir) |
100 A - 125 A
|
Overload current setting (Ir) - min |
100 A
|
Overload current setting (Ir) - max |
125 A
|
Short delay current setting (Isd) - min |
0 A
|
Short delay current setting (Isd) - max |
0 A
|
Short-circuit release non-delayed setting - min |
750 A
|
Short-circuit release non-delayed setting - max |
1250 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
Electrical connection type of main circuit |
Screw connection
|
Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
Handle type |
Rocker lever
|
Current rating of neutral conductor |
200% of phase conductor
|
Amperage Rating |
125 A
|
Instantaneous current setting (Ii) - min |
6 A
|
Instantaneous current setting (Ii) - max |
10 A
|
Overload current setting (Ir) |
100 A - 125 A
|
Overload current setting (Ir) - min |
100 A
|
Overload current setting (Ir) - max |
125 A
|
Short delay current setting (Isd) - min |
0 A
|
Short delay current setting (Isd) - max |
0 A
|
Short-circuit release non-delayed setting - min |
750 A
|
Short-circuit release non-delayed setting - max |
1250 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
Electrical connection type of main circuit |
Screw connection
|
Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
Handle type |
Rocker lever
|
Mounting Method |
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional Fixed |
Degree of protection |
IP20
|
Protection against direct contact |
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Position of connection for main current circuit |
Front side
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |