Eaton Moeller® series DILM Contactor, 3 pole, 380 V 400 V 22 kW, 230 V 50/60 Hz, AC operation, Screw terminals
| Product Name | 
                                                Eaton Moeller® series DILM contactor
                                             | 
| Catalog Number | 
                                                277838
                                             | 
| Product Length/Depth | 
                                                132.1 mm
                                             | 
| Product Height | 
                                                115 mm
                                             | 
| Product Width | 
                                                55 mm
                                             | 
| Product Weight | 
                                                0.872 kg
                                             | 
| Certifications | 
                                                CSA-C22.2 No. 60947-4-1-14  CSA UL 60947-4-1 CSA File No.: 012528 IEC/EN 60947 IEC/EN 60947-4-1 UL File No.: E29096 CSA Class No.: 2411-03, 3211-04 CE VDE 0660 UL Category Control No.: NLDX UL | 
| Catalog Notes | 
                                                Contacts according to EN 50012
                                             | 
| Number of poles | 
                                                Three-pole
                                             | 
| Application | 
                                                Contactors for Motors
                                             | 
| Frame size | 
                                                FS3
                                             | 
| Lifespan, mechanical | 
                                                7,000,000 Operations (Coil 50/60 Hz)  10,000,000 Operations (AC operated) | 
| Operating frequency | 
                                                5000 mechanical Operations/h (AC operated)
                                             | 
| Overvoltage category | 
                                                III
                                             | 
| Pollution degree | 
                                                3
                                             | 
| Product category | 
                                                Contactors
                                             | 
| Protection | 
                                                Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
                                             | 
| Rated impulse withstand voltage (Uimp) | 
                                                8000 V AC
                                             | 
| Resistance per pole | 
                                                1.9 mΩ
                                             | 
| Suitable for | 
                                                Also motors with efficiency class IE3
                                             | 
| Utilization category | 
                                                AC-1: Non-inductive or slightly inductive loads, resistance furnaces  AC-4: Normal AC induction motors: starting, plugging, reversing, inching AC-3: Normal AC induction motors: starting, switch off during running | 
| Voltage type | 
                                                AC
                                             | 
| Shock resistance | 
                                                5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms  7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms | 
| Ambient operating temperature - min | 
                                                -25 °C
                                             | 
| Ambient operating temperature - max | 
                                                60 °C
                                             | 
| Ambient operating temperature (enclosed) - min | 
                                                -25 °C
                                             | 
| Ambient operating temperature (enclosed) - max | 
                                                40 °C
                                             | 
| Ambient storage temperature - min | 
                                                -40 °C
                                             | 
| Ambient storage temperature - max | 
                                                80 °C
                                             | 
| Climatic proofing | 
                                                Damp heat, constant, to IEC 60068-2-78  Damp heat, cyclic, to IEC 60068-2-30 | 
| Emitted interference | 
                                                According to EN 60947-1
                                             | 
| Interference immunity | 
                                                According to EN 60947-1
                                             | 
| Terminal capacity (copper band) | 
                                                2 x (6 x 9 x 0.8) mm (Number of segments x width x thickness), Main cables
                                             | 
| Terminal capacity (flexible with ferrule) | 
                                                2 x (0.75 - 2.5) mm², Control circuit cables  2 x (0.75 - 25) mm², Main cables 1 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 35) mm², Main cables | 
| Terminal capacity (solid) | 
                                                2 x (0.75 - 2.5) mm², Control circuit cables  2 x (0.75 - 16) mm², Main cables 1 x (0.75 - 16) mm², Main cables 1 x (0.75 - 4) mm², Control circuit cables | 
| Terminal capacity (solid/stranded AWG) | 
                                                Single 14 - 1, double 14 - 2, Main cables  18 - 14, Control circuit cables | 
| Terminal capacity (stranded) | 
                                                1 x (16 - 50) mm², Main cables  2 x (16 - 35) mm², Main cables | 
| Stripping length (main cable) | 
                                                14 mm
                                             | 
| Stripping length (control circuit cable) | 
                                                10 mm
                                             | 
| Screw size | 
                                                M6, Terminal screw, Main cables  M3.5, Terminal screw, Control circuit cables | 
| Screwdriver size | 
                                                2, Terminal screw, Pozidriv screwdriver  0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver | 
| Tightening torque | 
                                                3.3 Nm, Screw terminals, Main cables  1.2 Nm, Screw terminals, Control circuit cables | 
| Rated breaking capacity at 220/230 V | 
                                                500 A
                                             | 
| Rated breaking capacity at 380/400 V | 
                                                500 A
                                             | 
| Rated breaking capacity at 500 V | 
                                                500 A
                                             | 
| Rated breaking capacity at 660/690 V | 
                                                320 A
                                             | 
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 
                                                80 A
                                             | 
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 
                                                50 A
                                             | 
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 
                                                50 A
                                             | 
| Rated operational current (Ie) at AC-3, 440 V | 
                                                50 A
                                             | 
| Rated operational current (Ie) at AC-3, 500 V | 
                                                50 A
                                             | 
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 
                                                32 A
                                             | 
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 
                                                21 A
                                             | 
| Rated operational current (Ie) at AC-4, 400 V | 
                                                21 A
                                             | 
| Rated operational current (Ie) at AC-4, 500 V | 
                                                21 A
                                             | 
| Rated operational current (Ie) at AC-4, 660 V, 690 V | 
                                                17 A
                                             | 
| Rated operational current (Ie) at DC-1, 60 V | 
                                                60 A
                                             | 
| Rated operational current (Ie) at DC-1, 110 V | 
                                                50 A
                                             |