Eaton Moeller® series DILM Contactor, 3 pole, 380 V 400 V 22 kW, 230 V 50/60 Hz, AC operation, Screw terminals
Product Name |
Eaton Moeller® series DILM contactor
|
Catalog Number |
277838
|
Product Length/Depth |
132.1 mm
|
Product Height |
115 mm
|
Product Width |
55 mm
|
Product Weight |
0.872 kg
|
Certifications |
CSA-C22.2 No. 60947-4-1-14
CSA UL 60947-4-1 CSA File No.: 012528 IEC/EN 60947 IEC/EN 60947-4-1 UL File No.: E29096 CSA Class No.: 2411-03, 3211-04 CE VDE 0660 UL Category Control No.: NLDX UL |
Catalog Notes |
Contacts according to EN 50012
|
Number of poles |
Three-pole
|
Application |
Contactors for Motors
|
Frame size |
FS3
|
Lifespan, mechanical |
7,000,000 Operations (Coil 50/60 Hz)
10,000,000 Operations (AC operated) |
Operating frequency |
5000 mechanical Operations/h (AC operated)
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Contactors
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Rated impulse withstand voltage (Uimp) |
8000 V AC
|
Resistance per pole |
1.9 mΩ
|
Suitable for |
Also motors with efficiency class IE3
|
Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching AC-3: Normal AC induction motors: starting, switch off during running |
Voltage type |
AC
|
Shock resistance |
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature (enclosed) - min |
25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Emitted interference |
According to EN 60947-1
|
Interference immunity |
According to EN 60947-1
|
Terminal capacity (copper band) |
2 x (6 x 9 x 0.8) mm (Number of segments x width x thickness), Main cables
|
Terminal capacity (flexible with ferrule) |
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 25) mm², Main cables 1 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 35) mm², Main cables |
Terminal capacity (solid) |
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 16) mm², Main cables 1 x (0.75 - 16) mm², Main cables 1 x (0.75 - 4) mm², Control circuit cables |
Terminal capacity (solid/stranded AWG) |
Single 14 - 1, double 14 - 2, Main cables
18 - 14, Control circuit cables |
Terminal capacity (stranded) |
1 x (16 - 50) mm², Main cables
2 x (16 - 35) mm², Main cables |
Stripping length (main cable) |
14 mm
|
Stripping length (control circuit cable) |
10 mm
|
Screw size |
M6, Terminal screw, Main cables
M3.5, Terminal screw, Control circuit cables |
Screwdriver size |
2, Terminal screw, Pozidriv screwdriver
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver |
Tightening torque |
3.3 Nm, Screw terminals, Main cables
1.2 Nm, Screw terminals, Control circuit cables |
Rated breaking capacity at 220/230 V |
500 A
|
Rated breaking capacity at 380/400 V |
500 A
|
Rated breaking capacity at 500 V |
500 A
|
Rated breaking capacity at 660/690 V |
320 A
|
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
80 A
|
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
50 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
50 A
|
Rated operational current (Ie) at AC-3, 440 V |
50 A
|
Rated operational current (Ie) at AC-3, 500 V |
50 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
32 A
|
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V |
21 A
|
Rated operational current (Ie) at AC-4, 400 V |
21 A
|
Rated operational current (Ie) at AC-4, 500 V |
21 A
|
Rated operational current (Ie) at AC-4, 660 V, 690 V |
17 A
|
Rated operational current (Ie) at DC-1, 60 V |
60 A
|
Rated operational current (Ie) at DC-1, 110 V |
50 A
|