Eaton Moeller® series ES4P Safety relay, 24 V DC, 14DI, 4DO relays, display, easyNet
| Product Name |
Eaton Moeller® series ES4P Safety relay
|
| Catalog Number |
111019
|
| EAN |
4015081105298
|
| Product Length/Depth |
72 mm
|
| Product Height |
90 mm
|
| Product Width |
108 mm
|
| Product Weight |
0.385 kg
|
| Certifications |
IEC 61508
IEC 62061 EN ISO 13849-1 UL 508 IEC/EN 61000-6-2 CE CSA-22.2 No. 142-MI1987 CSA-C22.20.4-04 EN 50156-2 CSA Class No.: 2252-81; 2252-01 CSA File No.: 012528 IEC/EN 61000-6-3 EN 50156-1 CSA IEC/EN 61000-4-2 EN 50178 EN 50581 UL Category Control No.: NRAQ UL File No.: CSA report applies to both US and Canada |
| Catalog Notes |
1000
|
| Model Code |
ES4P-221-DRXD1
|
| Type |
easy800 with safety function blocks
|
| Features |
Safety/standard circuit diagram
Expandable |
| Air discharge |
15 kV
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Display
Keypad Expandable standard bus systems Real time clock Timer Relay output Expandable standard inputs/outputs |
| Operating frequency |
900 Operations/h at input (does not apply to I1, I2, if function block SM or OM is used)
|
| Pollution degree |
2
|
| Accuracy |
± 2 s/day (± 0.5 h⁄year), Real-time clock, normally
± 5 s/day depending on the ambient temperature |
| Burst impulse |
According to IEC/EN 61000-4-4
4 kV, Supply cable 4 kV, Signal cable |
| Rated impulse withstand voltage (Uimp) |
6 kV (contact-coil)
|
| Air pressure |
795 - 1080 hPa (operation)
|
| Bus termination |
First and last station, easyNet
|
| Category (EN 954-1) |
4
|
| Explosion safety category for dust |
None
|
| Environmental conditions |
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 142, EN 60664-1:2003
Condensation: prevent with appropriate measures |
| Indication |
LCD-display used as Output status indication of Transistor outputs
|
| Output voltage |
24 V DC (test signal outputs)
|
| Explosion safety category for gas |
None
|
| Mounting method |
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting Screw fixing using fixing brackets ZB4-101-GF1 (accessories) Rail mounting possible |
| Screwdriver size |
3.5 x 0.8 mm, Terminal screw
|
| Voltage type |
DC
|
| Output |
4 Test signal outputs (T1 - T4)
Relay outputs in groups of 1 |
| Contact discharge |
8 kV
|
| Base type |
Yes
|
| Safety performance level (EN ISO 13849-1) |
Level e
|
| SIL (IEC 61508) |
3
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
55 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
6 A
|
| Display temperature - max |
55 °C
|
| Display temperature - min |
0 °C
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
| Number of HW-interfaces (industrial ethernet) |
0
|
| Number of HW-interfaces (other) |
3
|
| Number of HW-interfaces (parallel) |
0
|
| Number of HW-interfaces (RS-232) |
1
|
| Number of HW-interfaces (RS-422) |
0
|
| Number of HW-interfaces (RS-485) |
0
|
| Number of HW-interfaces (serial TTY) |
0
|
| Number of HW-interfaces (USB) |
0
|
| Number of HW-interfaces (wireless) |
0
|
| Overvoltage category |
III
|
| Module interface |
easyNet/easyLink
|
| Constant acceleration |
2 g, 57 - 150 Hz
|
| Off-delay |
< 1 ms
|
| Constant amplitude |
0,15 mm, 10 - 57 Hz, according to IEC/EN 60068-2-6, Vibrations
|
| Surge rating |
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
4 kV, semi-conductor outputs, symmetrical, power pulses (Surge), EMC 2 kV, Supply cables, symmetrical, power pulses (Surge), EMC |
| Cable length |
3000 m, shielded, Total of single cable lengths from one test signal output to the device inputs, Digital inputs 24 V DC
1000 m, shielded, Single cable length of test signal output to the device input, Digital inputs 24 V DC 100 m, unscreened, Digital inputs 24 V DC |
| Electromagnetic compatibility |
Increased EMC requirements for safety-relevant functions (according to ICE 62061)
|
| Electromagnetic fields |
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3) 30 V/m (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
| Number of inputs (analog) |
0
|
| Connection type |
Ethernet: RJ45 plug, 8-pole
|
| Number of modules |
Max. 8
|
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Immunity to line-conducted interference |
20 V (according to IEC/EN 61000-4-6)
|
| Radio interference class |
Class B (EN 55011)
Class B (EN 55022) |
| Number of outputs (digital) |
4
|
| Data transfer rate |
20 kBit/s, 700 m, easyNet
500 kBit/s, 25 m, easyNet 125 kBit/s, 125 m, easyNet 10 kBit/s, 1000 m, easyNet 50 kBit/s, 300 m, easyNet 1000 kBit/s, 6 m, easyNet 250 kBit/s, 40 m, easyNet |
| Mounting width |
107.5 mm
|
| Pulse characteristics |
1 ms (Off test pulse)
1 ms (max. duration of external test pulse) |
| Relative humidity |
5 - 95 % (non-condensing, IEC 60068-2-30, IEC 60068-2-78)
|
| Degree of protection |
IP20
|
| Safe isolation |
Between coil and contacts in accordance with EN 50178
300 V AC, Between coil and contacts, According to EN 50178 |
| Protocol |
Other bus systems
|
| Residual ripple |
5 % (transistor outputs)
0 % |
| Rated control supply voltage |
24 V DC (Us)
|
| Insulation resistance |
According to EN 50178
|
| Suitable for |
Safety functions
|
| Functions |
Redundancy
|
| Vibration resistance |
3.5 mm / 1 g, According to IEC/EN 60068-2-6
|
| Input current |
< 250 mA (at 115/230 V AC)
5.7 mA (Digital inputs, at 24 V DC, at signal 1, I1 - I6) |
| Safety parameter (EN ISO 13849-1) |
Cat. 4, Category
PL e, Performance level |
| Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Inscription |
Individual laser inscriptions possible
|
| LED indicator |
Status indication of Digital inputs 24 V DC: LCD Display
|
| Lifespan, mechanical |
10,000,000 Operations
10,000,000 Operations (Relay outputs) |
| Memory |
100,000,000,000,000 Write cycles of the retentive memory
|
| Potential isolation |
Between Inputs and internal Power supply: Yes
Between easyNet and Memory card: yes Between easyNet and Inputs: yes Between Power supply and easyNet: yes Between Power supply and Outputs: yes Between Power supply and Inputs: yes Between easyNet and Outputs: yes Between Relay outputs and easyNet: yes Between Digital inputs 24 V DC and Outputs: yes Between Relay outputs and Inputs: yes Between Digital inputs 24 V DC and easyNet: yes Between Relay outputs and easyLink: yes Between Relay outputs and Interface: yes Safe isolation according to EN 50178: 300 V AC (Relay outputs) Between easyNet and Power supply: yes Between Relay outputs and Digital inputs: yes Basic isolation: 600 V AC (Relay outputs) Between Relay outputs and Power supply: yes Between easyNet and PC interface: yes |
| Number of inputs (digital) |
14
|
| Voltage dips |
According to EN 61131-2
≤ 10 ms |
| Safety function/level |
Feedback circuit
According to EN 50156 Highest speed monitoring Enabling switch Safety timing relay Mode selection Two-hand control Protective door ESPE with muting function Zero speed monitoring 3 redundant relay outputs, 6 months test interval Stopping in the event of an emergency OSSD input |
| Number of interfaces (PROFINET) |
0
|
| Number of outputs (analog) |
4
|
| Rated insulation voltage (Ui) |
250 V
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
6 W
|
| Supply voltage at AC, 50 Hz - max |
0 VAC
|
| Supply voltage at AC, 50 Hz - min |
0 VAC
|
| Supply voltage at AC, 60 Hz - max |
0 VAC
|
| Supply voltage at AC, 60 Hz - min |
0 VAC
|
| Supply voltage at DC - max |
28.8 VDC
|
| Supply voltage at DC - min |
20.4 VDC
|
| Switching current |
8 A
|
| Product category |
Control relays for safety applications
|
| Protection |
|
| Resolution |
|
| Power consumption |
6 W
|
| Rated operational voltage |
24 V DC (-15 %/+ 20 % - power supply)
20.4 - 28.8 V DC 250 V AC 24 V DC (digital inputs) < 5 V DC on 0 signal > 15 V DC on 1 signal |
| Switching frequency |
15 Hz, Relay outputs
|
| Terminal capacity |
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
0.2 - 4 mm² (AWG 22 - 12), solid |
| Tightening torque |
0.6 Nm, Screw terminals
|
| Switching capacity |
DC-13, 24 V DC, 0.1 Hz: 40000 operations (in accordance with IEC 60947-5-1), Relay outputs
AC: R300 (in accordance with UL 508), Relay outputs AC-15, 230 V AC, 3 A: 80000 operations (in accordance with IEC 60947-5-1), Relay outputs DC: B300 (in accordance with UL 508), Relay outputs |
| Safety parameter (IEC 62061) |
SILCL 3, Safety integrity level claim limit
SIL 3, Safety integrity level, In accordance with IEC 61508 4.26 x 10-10, PFHd, Probability of failure per hour |