Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 140A, box terminals, H2-ME140-BT-NA
Product Name |
Eaton Moeller series NZM molded case circuit breaker electronic
|
Catalog Number |
142425
|
EAN |
4015081391516
|
Product Length/Depth |
149 mm
|
Product Height |
195 mm
|
Product Width |
105 mm
|
Product Weight |
3.044 kg
|
Compliances |
RoHS conform
|
Certifications |
CSA-C22.2 No. 5-09
CSA certified Specially designed for North America CSA (File No. 22086) CE marking UL/CSA IEC UL (Category Control Number DIVQ) UL (File No. E31593) IEC 60947-2 UL 489 UL508 IEC/EN 60947 UL listed CSA (Class No. 1432-01) |
Model Code |
NZMH2-ME140-BT-NA
|
Amperage Rating |
140 A
|
Voltage rating |
690 V - 690 V
|
Circuit breaker frame type |
NZM2
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Thermal protection
|
Pollution degree |
3
|
Mounting Method |
Built-in device fixed built-in technique
Fixed |
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Equipment heat dissipation, current-dependent |
16.17 W
|
Utilization category |
A (IEC/EN 60947-2)
|
Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
40 °C
|
Low-voltage HBC fuse - max |
355 A gG/gL
|
Motor power at 460/480 V (UL) |
100 HP
|
Protection against direct contact |
Finger and back-of-hand proof to VDE 0106 part 100
|
Rated insulation voltage (Ui) |
1000 V
|
Rated operating power at AC-3, 230 V |
45 kW
|
Rated operating power at AC-3, 400 V |
75 kW
|
Switch off technique |
Electronic
|
Degree of protection |
IP20
IP20 (basic degree of protection, in the operating controls area) |
Direction of incoming supply |
As required
|
Electrical connection type of main circuit |
Other
|
Lifespan, mechanical |
20000 operations
|
Overvoltage category |
III
|
Rated operational current |
140 A (690 V AC-1, making and breaking capacity)
300 A (400 V AC-1, making and breaking capacity) 140 A (660-690 V AC-3, making and breaking capacity) 300 A (415 V AC-1, making and breaking capacity) |
Degree of protection (IP), front side |
IP40 (with insulating surround)
IP66 (with door coupling rotary handle) |
Degree of protection (terminations) |
IP00 (terminations, phase isolator and strip terminal)
IP10 (tunnel terminal) |
Number of poles |
Three-pole
|
Lifespan, electrical |
5000 operations at 690 V AC-3
6500 operations at 415 V AC-3 7500 operations at 690 V AC-1 6500 operations at 400 V AC-3 10000 operations at 400 V AC-1 |
Functions |
Current limiting circuit breaker
Motor protection Phase failure sensitive |
Type |
Circuit breaker
|
Special features |
|
Application |
|
Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
Rated operational current for specified heat dissipation (In) |
140 A
|
Rated short-time withstand current (t = 0.3 s) |
1.9 kA
|
Rated short-time withstand current (t = 1 s) |
1.9 kA
|
Short-circuit release non-delayed setting - max |
1960 A
|
Short-circuit release non-delayed setting - min |
280 A
|
Handle type |
Rocker lever
|
Instantaneous current setting (Ii) - max |
1960 A
|
Instantaneous current setting (Ii) - min |
280 A
|
Number of operations per hour - max |
120
|
Overload current setting (Ir) - max |
140 A
|
Overload current setting (Ir) - min |
70 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
150 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
130 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
130 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz |
37.5 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz |
5 kA
|
Standard terminals |
Box terminal
|
Rated operating voltage Ue (UL) - max |
480 V
|
Release system |
Electronic release
|
Short-circuit total breaktime |
< 10 ms
|
Terminal capacity (aluminum solid conductor/cable) |
16 mm² (1x) at tunnel terminal
|
Terminal capacity (copper busbar) |
M8 at rear-side screw connection
|
Terminal capacity (copper solid conductor/cable) |
16 mm² (1x) at tunnel terminal
|
Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 400/415 V, 50/60 Hz |
130 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
330 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
286 kA
|
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz |
105 kA
|
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz |
40 kA
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
330 kA
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
8000 V
|
Power loss |
16.17 W
|