Eaton Moeller® series DILH Contactor, Ith =Ie: 3185 A, RAW 250: 230 - 250 V 50 - 60 Hz/230 - 350 V DC, AC and DC operation, Screw connection
Product Name |
Eaton Moeller® series DILH contactor
|
Catalog Number |
125945
|
EAN |
4015081235551
|
Product Length/Depth |
252 mm
|
Product Height |
462 mm
|
Product Width |
515 mm
|
Product Weight |
35.2 kg
|
Certifications |
UL Category Control No.: NLDX
CSA File No.: 012528 CE IEC/EN 60947 IEC/EN 60947-4-1 CSA Class No.: 3211-04 CCC UL File No.: E29096 VDE 0660 UL UL 60947-4-1 CSA CSA-C22.2 No. 60947-4-1-14 |
Catalog Notes |
|
Model Code |
DILH2600/22(RAW250)
|
Accessories |
Fitting options auxiliary contacts: on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
|
Application |
Mains contactors for resistive loads from 1000 A
|
Connection |
Screw terminals
|
Degree of protection |
IP00
|
Electromagnetic compatibility |
Designed for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression.
|
Fitted with: |
Suppressor circuit in actuating electronics
|
Lifespan, mechanical |
5,000,000 Operations (DC operated)
5,000,000 Operations (AC operated) |
Operating frequency |
1000 mechanical Operations/h (DC operated)
1000 mechanical Operations/h (AC operated) |
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Contactors
|
Rated impulse withstand voltage (Uimp) |
8000 V AC
|
Resistance |
500 mΩ (Admissible transitional contact resistance - of the external control circuit device when actuating A11)
|
Shock resistance |
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Signal level |
5 V - 15 V, PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2), Magnet systems
|
Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
|
Voltage type |
AC/DC
|
Altitude |
Max. 2000 m
|
Ambient operating temperature - min |
-40 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Terminal capacity (busbar) |
100 mm width, Main connection
|
Terminal capacity (flexible with ferrule) |
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables |
Terminal capacity (solid) |
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables |
Terminal capacity (solid/stranded AWG) |
18 - 14, Control circuit cables
|
Width across flats |
18 mm
|
Stripping length (control circuit cable) |
10 mm
|
Screw size |
M12, Terminal screw, Main connections
M3.5, Terminal screw, Control circuit cables |
Screwdriver size |
2, Terminal screw, Control circuit cables, Pozidriv screwdriver
0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver |
Tightening torque |
1.2 Nm, Screw terminals, Control circuit cables
35 Nm, Main cable connection screw/bolt |
Rated breaking capacity at 220/230 V |
8200 A
|
Rated breaking capacity at 380/400 V |
8200 A
|
Rated breaking capacity at 500 V |
8200 A
|
Rated breaking capacity at 660/690 V |
8200 A
|
Rated breaking capacity at 1000 V |
5800 A
|
Rated insulation voltage (Ui) |
1000 V
|
Rated making capacity (cos phi to IEC/EN 60947) |
9840 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
0 A
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
0 kW
|
Rated operational voltage (Ue) at AC - max |
1000 V
|
Safe isolation |
1000 V AC, Between coil and contacts, According to EN 61140
|
Special purpose rating of resistance air heating |
2600 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
2600 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) |
Conventional thermal current Ith at 40°C (3-pole, open) |
3185 A
|
Conventional thermal current Ith at 50°C (3-pole, open) |
2847 A
|
Conventional thermal current Ith at 55°C (3-pole, open) |
2716 A
|
Conventional thermal current Ith of main contacts (1-pole, open) |
6500 A
|
Switching capacity (main contacts, general use) |
2600 A, Maximum motor rating (UL/CSA)
|
Switching capacity (auxiliary contacts, general use) |
1 A, 250 V DC, (UL/CSA)
15 A, 600 V AC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
P300, DC operated (UL/CSA)
A600, AC operated (UL/CSA) |
Behavior in marginal and transitional conditions |
Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on
Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on |
Drop-out voltage |
0.2 x US max - 0.6 x US min, DC operated
AC operated: 0.2 x US max - 0.6 x US min, AC operated |
Duty factor |
100 %
|
Pick-up voltage |
0.7 - 1.15 V DC x Us
0.7 - 1.15 V AC x Us |
Power consumption |
Control transformer with uk ≤ 7%
|
Power consumption, pick-up, 50 Hz |
1600 VA, Pull-in power, Coil in a cold state and 1.0 x Us
1400 W, Pull-in power, Coil in a cold state and 1.0 x Us |
Power consumption, pick-up, 60 Hz |
1600 VA, Pull-in power, Coil in a cold state and 1.0 x Us
1400 W, Pull-in power, Coil in a cold state and 1.0 x Us |
Power consumption, sealing, 50 Hz |
17.3 W, Coil in a cold state and 1.0 x Us
36.5 VA, Coil in a cold state and 1.0 x Us |
Power consumption, sealing, 60 Hz |
36.5 VA, Coil in a cold state and 1.0 x Us
17.3 W, Coil in a cold state and 1.0 x Us |
Rated control supply voltage (Us) at AC, 50 Hz - min |
230 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
250 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
230 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
250 V
|
Rated control supply voltage (Us) at DC - min |
230 V
|
Rated control supply voltage (Us) at DC - max |
250 V
|
Switching time (AC operated, make contacts, closing delay) - max |
70 ms
|
Switching time (AC operated, make contacts, opening delay) - max |
40 ms
|
Number of auxiliary contacts (normally closed contacts) |
2
|
Number of auxiliary contacts (normally open contacts) |
2
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
83 W
|
Rated operational current for specified heat dissipation (In) |
2600 A
|
Static heat dissipation, non-current-dependent Pvs |
13 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|