Download document () of 20

174733
Model code: EU2E-SWD-2PT

Eaton EU2E SmartWire-DT IP67 T-Connector analog module, two configurable Pt100/Pt1000/Ni1000 temperature inputs, two M12 I/O sockets

General specifications

Product Name
Eaton EU2E Analog module
Catalog Number
174733
EAN
4015081712199
Product Length/Depth
98 mm
Product Height
20.1 mm
Product Width
56.9 mm
Product Weight
0.085 kg
Certifications
IEC/EN 61131-2
UL
UL File No.: E170645
CSA
Model Code
EU2E-SWD-2PT

Features & Functions

Electric connection type
Screw connection
Features
Analog outputs configurable
Input signal, configurable
Fieldbus connection over separate bus coupler possible
Input, resistance thermometer
Analog inputs configurable
Fitted with:
Temperature sensors PT100, PT1000 and Ni1000
Display mode for temperatures (°C, °F, raw value)
Functions
For connection of analog I/O signals
Adjustable parameter settings

General

Current consumption
37 mA, SmartWire-DT network
Degree of protection
IP69K
NEMA 4X
Mounting method
Rail mounting possible
Wall mounting/direct mounting
DIN rail
Mounting section (Clip M20)
Screw fixing (M4)
Overvoltage category
II
Pollution degree
3
Product category
SmartWire-DT slave
Repetition accuracy
0.5 % (Temperature inputs)
Type
Analog modules
Voltage type
DC

Ambient conditions, mechanical

Constant acceleration
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
As required
Shock resistance
30 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3
Environmental conditions
Condensation: permissible
Operating temperature - min
-100 °C
Operating temperature - max
70 °C
Relative humidity
5 - 95 % (non-condensing, IEC/EN 60068-2-30)

Electro magnetic compatibility

Air discharge
8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
Contact discharge
4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI
10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference class
Class A (EN 55011)
Surge rating
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC

Electrical rating

Power loss
0.9 W
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
0 VDC
Supply voltage at DC - max
0 VDC

Communication

Connection to SmartWire-DT
Yes
Connection type
SWD-OUT: M12 socket (A-keyed), 5 pole
5-pin M12 socket (A-keyed), Supply and I/O sensor
SWD-IN : M12 plug (A-keyed), 5 pole
Data transfer rate
2 MBit/s, SmartWire-DT
Setting automatically
LED indicator
Status indication of SmartWire-DT network: Green LED
Protocol
Other bus systems
Station
SmartWire-DT slave, SmartWire-DT network

Input/Output

Conversions
250 ms, Temperature inputs
Input
Inputs, configurable (PT100, PT1000, Ni1000)
Number of inputs (analog)
2
Number of outputs (analog)
0
Resolution
0.1 °C, Temperature inputs
Total error
± 1 %, Temperature Inputs

Safety

Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Inputs for SmartWire-DT: no
Input to input: no

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0.9 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Export product specification