Eaton Moeller series xEffect - AZ MCB. Miniature circuit breaker (MCB) AZ, 3 pole+N, Tripping characteristic: C, Rated current In: 20 A
| Product Name |
Eaton Moeller series xEffect - AZ MCB
|
| Catalog Number |
211773
|
| EAN |
4015082117733
|
| Product Length/Depth |
90 mm
|
| Product Height |
75 mm
|
| Product Width |
108 mm
|
| Product Weight |
0.845 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC/EN 60947-2
EN45545-2 IEC 61373 |
| Model Code |
AZ-3N-C20
|
| Application |
|
| Number of poles |
Three-pole + N
|
| Number of poles (total) |
4
|
| Number of poles (protected) |
3
|
| Tripping characteristic |
C
|
| Release characteristic |
C
|
| Amperage Rating |
20 A
|
| Type |
|
| Voltage type |
AC
|
| Voltage rating |
230 V AC / 400 V AC
|
| Voltage rating at DC |
60 V DC (per pole)
|
| Rated operational voltage (Ue) - max |
400 V
|
| Rated insulation voltage (Ui) |
440 V
|
| Rated impulse withstand voltage (Uimp) |
4 kV
|
| Frequency rating - min |
50 Hz
|
| Frequency rating - max |
60 Hz
|
| Rated switching capacity (IEC/EN 60947-2) |
25 kA
|
| Operational switching capacity |
20 kA
|
| Admissible back-up fuse - max |
200 A gL/gG
|
| Selectivity class |
3
|
| Lifespan, electrical |
10000 operations
|
| Overvoltage category |
III
|
| Pollution degree |
2
|
| Direction of incoming supply |
As required
|
| Frame |
45 mm
|
| Enclosure width |
90 mm
|
| Width in number of modular spacings |
6
|
| Built-in depth |
75 mm
|
| Mounting width per pole |
27 mm
|
| Mounting width |
27 mm
|
| Mounting Method |
Top-hat rail IEC/EN 60715
|
| Degree of protection |
IP40 (when fitted)
IP20 |
| Terminals (top and bottom) |
Lift terminals
|
| Connectable conductor cross section (solid-core) - min |
2.5 mm²
|
| Connectable conductor cross section (solid-core) - max |
50 mm²
|
| Connectable conductor cross section (multi-wired) - min |
2.5 mm²
|
| Connectable conductor cross section (multi-wired) - max |
50 mm²
|
| Terminal capacity (control cable) |
2.5 mm² - 50 mm²
|
| Terminal protection |
Finger and hand touch safe, DGUV VS3, EN 50274
|
| Rated operational current for specified heat dissipation (In) |
20 A
|
| Heat dissipation per pole, current-dependent |
2.7 W
|
| Equipment heat dissipation, current-dependent |
18.4 W
8.1 W |
| Static heat dissipation, non-current-dependent |
0 W
|
| Heat dissipation capacity |
0 W
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature - max |
55 °C
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| Current limiting class |
3
|
| Features |
Additional equipment possible
Concurrently switching N-neutral |
| Special features |
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
|
| Used with |
AZ
Miniature circuit breaker |