Eaton XNE Digital output module XI/ON ECO, 24 V DC, 16DO, 0.5A, pulse-switching
Product Name |
Eaton XNE Output module
|
Catalog Number |
140039
|
EAN |
7640130120532
|
Product Length/Depth |
161.5 mm
|
Product Height |
74.5 mm
|
Product Width |
13 mm
|
Product Weight |
0.068 kg
|
Compliances |
RoHS Compliant
CE Marked |
Certifications |
UL Listed
CE IEC/EN 61131-2 UL File No.: E205091 cULus IEC/EN 61000-6-2 IEC/EN 61000-6-4 Certified by UL for use in Canada IEC/EN 6113-2 UL report applies to both US and Canada CSA-C22.2 No. 142 UL Category Control No.: NRAQ, NRAQ7 CSA Class No.: 2252-01, 2252-81 UL Recognized Rated data for terminations according to IEC/EN 60947-7-1 UL 508 |
Model Code |
XNE-16DO-24VDC-0.5A-P
|
Electric connection type |
Plug-in connection
|
Features |
Fieldbus connection over separate bus coupler possible
|
Fitted with: |
Connectable sensors for lamp loads
Connectable sensors for resistive loads Connectable sensors for inductive loads |
Functions |
Positive switching
Short-circuit protection, outputs available |
Current consumption |
3 mA, from supply terminal
25 mA, from module bus, Analog input modules |
Degree of protection |
IP20
|
Mounting method |
Rail mounting possible
|
Number of channels |
16
|
Operating frequency |
As per DC13 to IEC 60947-5-1 at inductive load
|
Product category |
XNE Slice module
|
Switching frequency |
100 Hz, with resistive load, Digital outputs
10 Hz, with lamp load, Digital outputs |
Type |
XI/ON I/O module
|
Voltage type |
DC
|
Drop and topple |
According to IEC 60068-2-31, free fall according to IEC 60068-2-32
|
Shock resistance |
Continuous according to IEC/EN 60068-2-29
Mechanical, According to IEC/EN 60068-2-27 |
Vibration resistance |
According to IEC/EN 60068-2-6
|
Ambient operating temperature - min |
0 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient storage temperature - min |
-25 °C
|
Ambient storage temperature - max |
85 °C
|
Environmental conditions |
Harmful gasses - SO2: 10 ppm (relative humidity < 75%, no condensation)
Harmful gasses - H2S: 1 ppm (relative humidity < 75%, no condensation) |
Relative humidity |
5 - 95 % (indoor, Level RH-2, non-condensing for storage at 45°C)
|
Air discharge |
According to EN 61100-4-2
|
Burst impulse |
According to IEC/EN 61000-4-4
|
Contact discharge |
According to EN 61100-4-2
|
Electromagnetic fields |
According to IEC EN 61100-4-2
|
Emitted interference |
30 - 230 MHz (radiated, high frequency, according to EN 55016-2-3)
230 - 1000 MHz (radiated, high frequency, according to EN 55016-2-3) |
Radiated RFI |
IEC/EN 61100-4-6
|
Surge rating |
According to IEC/EN 61000-4-5 Level 4
|
Voltage dips |
According to EN 61131-2 (Voltage fluctuations/voltage dips)
|
Terminal capacity |
0.25 - 1.5 mm², solid, H07V-U
0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) 0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) 0.25 - 1.5 mm², flexible without ferrule, H07V-K |
Gauge pin |
A1 (according to IEC/EN 60947-1)
|
Stripping length (main cable) |
8 mm
|
Power loss |
2.5 W
|
Rated operational voltage |
24 V DC (supply terminal)
|
Short-circuit protection |
Short-circuit proof, Short-circuit rating, Digital outputs
|
Short-circuit release |
Automatic, Ii, Reset after short-circuit rectified, Digital outputs
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at DC - min |
18 VDC
|
Supply voltage at DC - max |
30 VDC
|
Connection type |
Push-In spring-cage terminals, Connection design in TOP direction
|
Protocol |
Other bus systems
|
Delay time |
300 µs, Digital outputs, Delay on signal change and resistive load, from High to Low signal
300 µs, Digital outputs, Delay on signal change and resistive load, from Low to High signal |
Input current at signal 1 |
0 mA
|
Lamp load |
≤ 6 W (at RLL)
|
Load resistance |
≥ 48 Ω
According to DC13 to IEC 60947-5-1 |
Number of inputs (digital) |
0
|
Number of outputs (digital) |
16
|
Output |
16 Digital Outputs (24 V DC, 0.5 A)
|
Output current |
< 1 A (high level, permissible range)
0.5 A |
Output voltage |
23 V DC (Digital outputs)
|
Utilization factor |
100 %
50 %, max. 4 A |
Explosion safety category for dust |
None
|
Explosion safety category for gas |
None
|
Potential isolation |
Through optocoupler: yes
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
2.5 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|