Eaton Moeller® series DILMP Contactor, 4 pole, AC operation, AC-1: 22 A, 24 V 50/60 Hz, Push in terminals
| Product Name |
Eaton Moeller® series DILMP 4-pole contactor
|
| Catalog Number |
199261
|
| EAN |
4015081973453
|
| Product Length/Depth |
75 mm
|
| Product Height |
68 mm
|
| Product Width |
45 mm
|
| Product Weight |
0.225 kg
|
| Certifications |
IEC/EN 60947
VDE 0660 |
| Catalog Notes |
Also tested according to AC-3e.
|
| Model Code |
DILMP20(24V50/60HZ)-PI
|
| Number of poles |
Four-pole
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Operating frequency |
5000 mechanical Operations/h (AC operated)
|
| Pollution degree |
3
|
| Climatic proofing |
Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-30 |
| Connection to SmartWire-DT |
No
|
| Rated impulse withstand voltage (Uimp) |
6000 V AC
|
| Utilization category |
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces |
| Connection |
Push in terminals
|
| Ambient operating temperature - max |
60 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature (enclosed) - max |
40 °C
|
| Ambient operating temperature (enclosed) - min |
-25 °C
|
| Ambient storage temperature - max |
80 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Assigned motor power at 115/120 V, 60 Hz, 1-phase |
1 HP
|
| Assigned motor power at 200/208 V, 60 Hz, 3-phase |
5 HP
|
| Assigned motor power at 230/240 V, 60 Hz, 1-phase |
2 HP
|
| Assigned motor power at 230/240 V, 60 Hz, 3-phase |
5 HP
|
| Assigned motor power at 460/480 V, 60 Hz, 3-phase |
10 HP
|
| Assigned motor power at 575/600 V, 60 Hz, 3-phase |
10 HP
|
| Conventional thermal current Ith (1-pole, enclosed) |
54 A
|
| Conventional thermal current Ith (3-pole, enclosed) |
18 A
|
| Conventional thermal current Ith at 55°C (3-pole, open) |
20.5 A
|
| Conventional thermal current Ith of main contacts (1-pole, open) |
60 A
|
| Equipment heat dissipation, current-dependent Pvid |
3 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
1 W
|
| Application |
Contactors for 4 pole electric consumers
|
| Product category |
Contactors
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
| Arcing time |
10 ms
|
| Electrical connection type of main circuit |
Push-in connection
|
| Screwdriver size |
3 x 0.5 mm, Terminal screw
|
| Voltage type |
AC
|
| Degree of protection |
IP20
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Number of contacts (normally closed contacts) |
0
|
| Number of contacts (normally closed) as main contact |
0
|
| Number of contacts (normally open contacts) |
0
|
| Number of main contacts (normally open contact) |
4
|
| Rated breaking capacity at 220/230 V |
120 A
|
| Rated breaking capacity at 380/400 V |
120 A
|
| Rated breaking capacity at 500 V |
100 A
|
| Rated breaking capacity at 660/690 V |
70 A
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
24 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
24 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
24 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
24 V
|
| Drop-out voltage |
AC operated: 0.6 - 0.4 x UC, AC operated
|
| Overvoltage category |
III
|
| Duty factor |
100 %
|
| Interference immunity |
According to EN 60947-1
|
| Lifespan, mechanical |
10,000,000 Operations (AC operated)
|
| Pick-up voltage |
0.8 - 1.1 V AC x Uc
|
| Power consumption, pick-up, 50 Hz |
24 VA, Dual-frequency coil in a cold state and 1.0 x Us
|
| Safe isolation |
400 V AC, Between the contacts, According to EN 61140
400 V AC, Between coil and contacts, According to EN 61140 |
| Power consumption, pick-up, 60 Hz |
24 VA, Dual-frequency coil in a cold state and 1.0 x Us
19 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
| Residual current |
1 mA (with actuation of A1 - A2 by the electronics with "0" signal)
|
| Power consumption, sealing, 50 Hz |
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us
|
| Power consumption, sealing, 60 Hz |
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us
4 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
| Terminal capacity (flexible with unisolated ferrule) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
| Terminal capacity (flexible with ultrasonic welded cable end) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
| Switching capacity (auxiliary contacts, general use) |
1 A, 250 V DC, (UL/CSA)
10 A, 600 V AC, (UL/CSA) |
| Terminal capacity (flexible with ferrule) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 1.5) mm² |
| Shock resistance |
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Terminal capacity (solid) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
| Terminal capacity (solid/stranded AWG) |
20 - 14
|
| Switching capacity (main contacts, general use) |
20 A, Maximum motor rating (UL/CSA)
|
| Terminal capacity (flexible) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
| Rated control supply voltage (Us) at DC - max |
0 V
|
| Rated control supply voltage (Us) at DC - min |
0 V
|
| Rated insulation voltage (Ui) |
690 V
|
| Rated making capacity up to 690 V (cos phi to IEC/EN 60947) |
144 A
|
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
22 A
|
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
12 A
|
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
12 A
|
| Rated operational current (Ie) at AC-3, 440 V |
12 A
|
| Rated operational current (Ie) at AC-3, 500 V |
10 A
|
| Rated operational current (Ie) at AC-3, 660 V, 690 V |
7 A
|
| Rated operational current (Ie) at AC-4, 400 V |
10 A
|
| Rated operational current (Ie) at DC-1, 110 V |
22 A
|
| Rated operational current (Ie) at DC-1, 220 V |
6 A
|
| Rated operational current (Ie) at DC-1, 60 V |
22 A
|
| Rated operational power at AC-1, 220/230 V, 50 Hz |
8 kW
|
| Rated operational power at AC-1, 240 V, 50 Hz |
9 kW
|
| Rated operational power at AC-1, 380/400 V, 50 Hz |
14 kW
|
| Rated operational power at AC-1, 415 V, 50 Hz |
15 kW
|
| Rated operational power at AC-1, 440 V, 50 Hz |
16 kW
|
| Rated operational power at AC-1, 500 V, 50 Hz |
18 kW
|
| Rated operational power at AC-1, 690 V, 50 Hz |
24 kW
|
| Rated operational power at AC-3, 240 V, 50 Hz |
4 kW
|
| Rated operational power at AC-3, 380/400 V, 50 Hz |
5.5 kW
|
| Rated operational power at AC-3, 415 V, 50 Hz |
7 kW
|
| Rated operational power at AC-4, 380/400 V, 50 Hz |
4.5 kW
|
| Rated operational power (NEMA) |
0 kW
|
| Rated operational voltage (Ue) at AC - max |
690 V
|
| Resistance per pole |
2.5 mΩ
|
| Static heat dissipation, non-current-dependent Pvs |
1.4 W
|
| Stripping length (control circuit cable) |
10 mm
|
| Stripping length (main cable) |
10 mm
|
| Switching time (AC operated, make contacts, closing delay) - max |
21 ms
|
| Switching time (AC operated, make contacts, closing delay) - min |
15 ms
|
| Switching time (AC operated, make contacts, opening delay) - max |
18 ms
|
| Switching time (AC operated, make contacts, opening delay) - min |
9 ms
|
| Short-circuit current rating (basic rating) |
5 kA, 45 A max. fuse, SCCR (UL/CSA)
5 kA, 45 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) |
100 kA, 60 A CLASS J max. fuse, SCCR (UL/CSA)
30 kA, 25 A CLASS RK5 max. fuse, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) |
100 kA, 60 A CLASS J max. fuse, SCCR (UL/CSA)
30 kA, 25 A CLASS RK5 max. fuse, SCCR (UL/CSA) |
| Short-circuit protection rating (type 1 coordination) at 400 V |
35 A gG/gL
|
| Short-circuit protection rating (type 1 coordination) at 690 V |
25 A gG/gL
|
| Short-circuit protection rating (type 2 coordination) at 400 V |
20 A gG/gL
|
| Short-circuit protection rating (type 2 coordination) at 690 V |
20 A gG/gL
|
| Special purpose rating of ballast electrical discharge lamps |
20 A (480V 60Hz 3phase, 277V 60Hz 1phase)
20 A (600V 60Hz 3phase, 347V 60Hz 1phase) |
| Special purpose rating of definite purpose rating |
15 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
90 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
| Special purpose rating of elevator control |
9 A, 600 V 60 Hz 3-ph, (UL/CSA)
11 A, 480 V 60 Hz 3-ph, (UL/CSA) 2 HP, 200 V 60 Hz 3-ph, (UL/CSA) 3 HP, 240 V 60 Hz 3-ph, (UL/CSA) 7.8 A, 200 V 60 Hz 3-ph, (UL/CSA) 7.5 HP, 600 V 60 Hz 3-ph, (UL/CSA) 9.6 A, 240 V 60 Hz 3-ph, (UL/CSA) 7.5 HP, 480 V 60 Hz 3-ph, (UL/CSA) |
| Special purpose rating of resistance air heating |
20 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
20 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) |
| Special purpose rating of tungsten incandescent lamps |
14 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
14 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) |
| Operating voltage at AC, 50 Hz - min |
24 V
|
| Operating voltage at AC, 50 Hz - max |
690 V
|
| Operating voltage at AC, 60 Hz - min |
24 V
|
| Operating voltage at AC, 60 Hz - max |
690 V
|