Eaton Moeller® series DILMF Contactors for Semiconductor Industries acc. to SEMI F47, 380 V 400 V: 18 A, 1 N/O, RAC 48: 42 - 48 V 50/60 Hz, Screw terminals
Product Name |
Eaton Moeller® series DILMF contactor for semiconductor industries
|
Catalog Number |
104435
|
EAN |
4015081042524
|
Product Length/Depth |
97 mm
|
Product Height |
85 mm
|
Product Width |
45 mm
|
Product Weight |
0.531 kg
|
Certifications |
UL 60947-4-1
CSA CSA File No.: 012528 CSA-C22.2 No. 60947-4-1-14 UL File No.: E29096 CE CSA Class No.: 2411-03, 3211-04 UL IEC/EN 60947-4-1 UL Category Control No.: NLDX |
Catalog Notes |
Also tested according to AC-3e.
|
Fitted with: |
Built-in suppressor circuit
|
Number of poles |
Three-pole
|
Application |
Contactors for Semiconductor Industries acc. to SEMI F47
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Contactors
|
Resistance per pole |
2.65 mΩ
|
Suitable for |
SEMI F47, Magnet systems
Also motors with efficiency class IE3 |
Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
Voltage type |
AC
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
80 °C
|
Emitted interference |
According to EN 60947-1
|
Interference immunity |
According to EN 60947-1
|
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
35 A
|
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
18 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
18 A
|
Rated operational current (Ie) at AC-3, 440 V |
18 A
|
Rated operational current (Ie) at AC-3, 500 V |
18 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
12 A
|
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V |
10 A
|
Rated operational current (Ie) at AC-4, 400 V |
10 A
|
Rated operational current (Ie) at AC-4, 500 V |
10 A
|
Rated operational current (Ie) at AC-4, 660 V, 690 V |
8 A
|
Rated insulation voltage (Ui) |
690 V
|
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
35 A
|
Rated operational power at AC-3, 240 V, 50 Hz |
5.5 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
7.5 kW
|
Rated operational power at AC-3, 415 V, 50 Hz |
10 kW
|
Rated operational power at AC-4, 220/230 V, 50 Hz |
2.5 kW
|
Rated operational power at AC-4, 240 V, 50 Hz |
3 kW
|
Rated operational power at AC-4, 415 V, 50 Hz |
5 kW
|
Rated operational power at AC-4, 440 V, 50 Hz |
5.5 kW
|
Rated operational power at AC-4, 500 V, 50 Hz |
6 kW
|
Rated operational power at AC-4, 660/690 V, 50 Hz |
6.5 kW
|
Short-circuit current rating (basic rating) |
5 kA, SCCR (UL/CSA)
125 A, max. Fuse, SCCR (UL/CSA) 125 A, max. CB, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 480 V) |
50/32 A, max. CB, SCCR (UL/CSA)
10/100 kA, Fuse, SCCR (UL/CSA) 125/70 A, Class J, max. Fuse, SCCR (UL/CSA) 10/65 kA, CB, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 600 V) |
50/32 A, max. CB, SCCR (UL/CSA)
10/22 kA, CB, SCCR (UL/CSA) 125/70 A, Class J, max. Fuse, SCCR (UL/CSA) 10/100 kA, Fuse, SCCR (UL/CSA) |
Conventional thermal current Ith (1-pole, enclosed) |
80 A
|
Conventional thermal current Ith (3-pole, enclosed) |
32 A
|
Conventional thermal current Ith of main contacts (1-pole, open) |
88 A
|
Switching capacity (main contacts, general use) |
40 A, Maximum motor rating (UL/CSA)
|
Switching capacity (auxiliary contacts, general use) |
10 A, 600 V AC, (UL/CSA)
1 A, 250 V DC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
A600, AC operated (UL/CSA)
P300, DC operated (UL/CSA) |
Switching time (AC operated, make contacts, closing delay) - max |
40 ms
|
Switching time (AC operated, make contacts, opening delay) - max |
45 ms
|
Drop-out voltage |
AC operated: 0.5 - 0.2 x UC, AC operated
|
Duty factor |
100 %
|
Pick-up voltage |
0.8 - 1.15 V AC x Uc
|
Power consumption, pick-up, 50 Hz |
14 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
|
Power consumption, sealing, 50 Hz |
0.8 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
0.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
Rated control supply voltage (Us) at AC, 50 Hz - min |
42 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
48 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
42 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
48 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Assigned motor power at 115/120 V, 60 Hz, 1-phase |
2 HP
|
Assigned motor power at 200/208 V, 60 Hz, 3-phase |
5 HP
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
3 HP
|
Assigned motor power at 230/240 V, 60 Hz, 3-phase |
5 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
10 HP
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
15 HP
|
Connection |
Screw terminals
|
Number of contacts (normally open contacts) |
1
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
1
|
Special purpose rating of ballast electrical discharge lamps |
40 A (600V 60Hz 3phase, 347V 60Hz 1phase)
40 A (480V 60Hz 3phase, 277V 60Hz 1phase) |
Special purpose rating of definite purpose rating |
108 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
18 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
Special purpose rating of elevator control |
7.5 HP, 480 V 60 Hz 3-ph, (UL/CSA)
10 HP, 600 V 60 Hz 3-ph, (UL/CSA) 11 A, 200 V 60 Hz 3-ph, (UL/CSA) 3 HP, 200 V 60 Hz 3-ph, (UL/CSA) 9.6 A, 240 V 60 Hz 3-ph, (UL/CSA) 11 A, 480 V 60 Hz 3-ph, (UL/CSA) 11 A, 600 V 60 Hz 3-ph, (UL/CSA) 3 HP, 240 V 60 Hz 3-ph, (UL/CSA) |
Special purpose rating of refrigeration control (CSA only) |
30 A, FLA 600 V 60 Hz 3phase; (CSA)
240 A, LRA 480 V 60 Hz 3phase; (CSA) 40 A, FLA 480 V 60 Hz 3phase; (CSA) 180 A, LRA 600 V 60 Hz 3phase; (CSA) |
Special purpose rating of resistance air heating |
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) |
Special purpose rating of tungsten incandescent lamps |
40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA) |
Equipment heat dissipation, current-dependent Pvid |
2.1 W
|
Heat dissipation capacity Pdiss |
0 W
|
Rated operational current for specified heat dissipation (In) |
18 A
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|