Eaton Moeller® series DILM Contactor, 380 V 400 V 132 kW, 2 N/O, 2 NC, 220 - 240 V 50/60 Hz, AC operation, Screw connection
Product Name |
Eaton Moeller® series DILM Contactor
|
Catalog Number |
274190
|
EAN |
4015082741907
|
Product Length/Depth |
208 mm
|
Product Height |
189 mm
|
Product Width |
140 mm
|
Product Weight |
6.71 kg
|
Certifications |
IEC/EN 60947-4-1
UL File No.: E29096 UL Category Control No.: NLDX VDE 0660 UL 60947-4-1 CSA Class No.: 3211-04 UL/CSA CSA File No. 1017510 North America (UL listed, CSA certified) EN 45545: Fire protection on railway vehicles IEC 61373: Vibration and shock, tested for category 1 class B CE marking |
Catalog Notes |
|
Accessories |
Fitting options auxiliary contacts: on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
|
Application |
Contactors for Motors
|
Connection |
Screw terminals
|
Degree of protection |
IP00
|
Electromagnetic compatibility |
Designed for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression.
|
Fitted with: |
Suppressor circuit in actuating electronics
|
Lifespan, electrical |
100,000 Operations (at Condensor operation)
|
Lifespan, mechanical |
10,000,000 Operations (AC operated)
|
Operating frequency |
3000 mechanical Operations/h (AC operated)
200 Operations/h |
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Contactors
|
Protection |
Finger and back-of-hand proof with terminal shroud or terminal block, Protection against direct contact when actuated from front (EN 50274)
|
Rated impulse withstand voltage (Uimp) |
8000 V AC
|
Resistance |
500 mΩ (Admissible transitional contact resistance - of the external control circuit device when actuating A11)
|
Shock resistance |
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Utilization category |
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-3: Normal AC induction motors: starting, switch off during running |
Voltage type |
AC
|
Altitude |
Max. 2000 m
|
Ambient operating temperature - min |
-40 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature (enclosed) - min |
-40 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Terminal capacity (busbar) |
25 mm width, Main connection
|
Terminal capacity (copper band) |
Fixing with flat cable terminal or cable terminal blocks; See terminal capacity for cable terminal blocks
|
Terminal capacity (flexible with cable lug) |
50 - 240 mm²
|
Terminal capacity (flexible with ferrule) |
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables |
Terminal capacity (solid) |
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm², Control circuit cables |
Terminal capacity (solid/stranded AWG) |
2/0 - 500 MCM, Main cables
18 - 14, Control circuit cables |
Terminal capacity (stranded with cable lug) |
70 - 240 mm²
|
Width across flats |
16 mm
|
Screw size |
M10, Terminal screw, Main connections
M3.5, Terminal screw, Control circuit cables |
Screwdriver size |
2, Terminal screw, Control circuit cables, Pozidriv screwdriver
|
Tightening torque |
1.2 Nm, Screw terminals, Control circuit cables
24 Nm, Main cable connection screw/bolt |
Inrush current |
Max. 30 x Ie (peak)
|
Rated breaking capacity at 220/230 V |
2500 A
|
Rated breaking capacity at 380/400 V |
2500 A
|
Rated breaking capacity at 500 V |
2500 A
|
Rated breaking capacity at 660/690 V |
2500 A
|
Rated breaking capacity at 1000 V |
760 A
|
Rated insulation voltage (Ui) |
1000 V
|
Rated making capacity (cos phi to IEC/EN 60947) |
3000 A
|
Rated operational current (Ie) |
220 A at up to 525 V (Individual compensation, three-phase capacitors, open)
133 A at 690 V (Individual compensation, three-phase capacitors, open) |
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
250 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
250 A
|
Rated operational current (Ie) at AC-3, 440 V |
250 A
|
Rated operational current (Ie) at AC-3, 500 V |
250 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
185 A
|
Rated operational current (Ie) at AC-3, 1000 V |
76 A
|
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V |
200 A
|
Rated operational current (Ie) at AC-4, 440 V |
200 A
|
Rated operational current (Ie) at AC-4, 500 V |
200 A
|
Rated operational current (Ie) at AC-4, 660 V, 690 V |
150 A
|
Rated operational current (Ie) at AC-4, 1000 V |
76 A
|
Rated operational power at AC-3, 240 V, 50 Hz |
85 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
132 kW
|
Rated operational power at AC-3, 415 V, 50 Hz |
143 kW
|
Rated operational power at AC-3, 440 V, 50 Hz |
152 kW
|
Rated operational power at AC-3, 500 V, 50 Hz |
173 kW
|
Rated operational power at AC-3, 690 V, 50 Hz |
170 kW
|
Rated operational power at AC-3, 1000 V, 50 Hz |
108 kW
|
Rated operational power at AC-4, 220/230 V, 50 Hz |
62 kW
|
Rated operational power at AC-4, 240 V, 50 Hz |
68 kW
|
Rated operational power at AC-4, 415 V, 50 Hz |
117 kW
|
Rated operational power at AC-4, 440 V, 50 Hz |
125 kW
|
Rated operational power at AC-4, 500 V, 50 Hz |
138 kW
|
Rated operational power at AC-4, 660/690 V, 50 Hz |
137 kW
|
Rated operational voltage (Ue) at AC - max |
1000 V
|
Rated operational power at AC-4, 1000 V, 50 Hz |
108 kW
|
Safe isolation |
500 V AC, Between coil and contacts, According to EN 61140
500 V AC, Between the contacts, According to EN 61140 |
Special purpose rating of definite purpose rating |
2050 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
300 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) 1800 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) 250 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
Short-circuit current rating (basic rating) |
700 A, max. Fuse, SCCR (UL/CSA)
18 kA, SCCR (UL/CSA) 600 A, max. CB, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 480 V) |
250 A, max. CB, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA) 18 kA, Fuse, SCCR (UL/CSA) 700 A, Class L, max. Fuse, SCCR (UL/CSA) 700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA) 18/100 kA, Fuse, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 600 V) |
18 kA, CB, SCCR (UL/CSA)
18 kA, Fuse, SCCR (UL/CSA) 700 A, Class J, max. Fuse, SCCR (UL/CSA) 600 A, max. CB, SCCR (UL/CSA) 700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA) 18/100 kA, Fuse, SCCR (UL/CSA) |
Short-circuit protection rating (type 1 coordination) at 1000 V |
200 A gG/gL
|
Short-circuit protection rating (type 1 coordination) at 400 V |
400 A gG/gL
|
Short-circuit protection rating (type 1 coordination) at 690 V |
400 A gG/gL
|
Short-circuit protection rating (type 2 coordination) at 1000 V |
160 A gG/gL
|
Short-circuit protection rating (type 2 coordination) at 400 V |
315 A gG/gL
|
Short-circuit protection rating (type 2 coordination) at 690 V |
315 A gG/gL
|
Conventional thermal current Ith (1-pole, enclosed) |
750 A
|
Conventional thermal current Ith (3-pole, enclosed) |
300 A
|
Conventional thermal current Ith at 55°C (3-pole, open) |
365 A
|
Conventional thermal current Ith of main contacts (1-pole, open) |
875 A
|
Switching capacity (main contacts, general use) |
350 A, Maximum motor rating (UL/CSA)
|
Switching capacity (auxiliary contacts, general use) |
1 A, 250 V DC, (UL/CSA)
15 A, 600 V AC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
P300, DC operated (UL/CSA)
A600, AC operated (UL/CSA) |
Behavior in marginal and transitional conditions |
Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on
Sealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on |
Drop-out voltage |
AC operated: 0.2 x US max - 0.4 x US min, AC operated
AC operated: 0.25 x US max - 0.6 x US min, AC operated |
Duty factor |
100 %
|
Pick-up voltage |
0.85 - 1.1 V AC x Us
|
Power consumption |
Control transformer with uk ≤ 10%
|
Power consumption, pick-up, 50 Hz |
325 W, Pull-in power, Coil in a cold state and 1.0 x Us
360 VA, Pull-in power, Coil in a cold state and 1.0 x Us |
Power consumption, pick-up, 60 Hz |
360 VA, Pull-in power, Coil in a cold state and 1.0 x Us
325 W, Pull-in power, Coil in a cold state and 1.0 x Us |
Power consumption, sealing, 50 Hz |
7.3 VA, Coil in a cold state and 1.0 x Us
4.8 W, Coil in a cold state and 1.0 x Us |
Power consumption, sealing, 60 Hz |
7.3 VA, Coil in a cold state and 1.0 x Us
4.8 W, Coil in a cold state and 1.0 x Us |
Rated control supply voltage (Us) at AC, 50 Hz - min |
220 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
240 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
220 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Switching time (AC operated, make contacts, closing delay) - max |
55 ms
|
Switching time (AC operated, make contacts, opening delay) - max |
40 ms
|
Assigned motor power at 200/208 V, 60 Hz, 3-phase |
75 HP
|
Assigned motor power at 230/240 V, 60 Hz, 3-phase |
100 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
200 HP
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
250 HP
|
Number of auxiliary contacts (normally closed contacts) |
2
|
Number of auxiliary contacts (normally open contacts) |
2
|
Number of contacts (normally closed contacts) |
2
|
Number of contacts (normally open contacts) |
2
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
9.33 W
|
Rated operational current for specified heat dissipation (In) |
250 A
|
Static heat dissipation, non-current-dependent Pvs |
4.8 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|