Eaton Moeller series HLR Solid-state relay, 3-phase, 20 A, 42 - 660 V, DC
Product Name |
Eaton Moeller series HLR solid state relay
|
Catalog Number |
360046
|
EAN |
4015081998135
|
Product Length/Depth |
103 mm
|
Product Height |
110 mm
|
Product Width |
54 mm
|
Product Weight |
0.505 kg
|
Compliances |
CE Marked
RoHS Compliant |
Certifications |
CE
UL 508 EAC CCC UL-File No.: E251034, UL report applies to both US and Canada |
Model Code |
HLR20/3(DC)600V
|
Type |
Solid-state relay
|
Operating temperature - max |
80 °C
|
Operating temperature - min |
-40 °C
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
6
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Please enquire
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Ambient storage temperature - max |
100 °C
|
Ambient storage temperature - min |
-40 °C
|
Phase |
3
|
Rated operational current (Ie) at AC-51 |
20 A
|
Rated operational current (Ie) at AC-53A |
10 A
|
Rated operational current for specified heat dissipation (In) |
20 A
|
Rated operational power at 220/230 V, 50 Hz |
2.2 kW
|
Rated operational power at 400 V, 50 Hz |
4 kW
|
Rated operational voltage (Ue) at AC - max |
660 V
|
Rated operational voltage (Ue) at AC - min |
42 V
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Voltage type |
DC
|
Rated operational power at 230 V, 60 Hz |
3 HP
|
Rated operational power at 480 V, 60 Hz |
7.5 HP
|
Rated operational power at 600 V, 60 Hz |
10 HP
|
Frequency rating |
45 Hz - 65 Hz
|
Series |
HLR
|
Equipment heat dissipation, current-dependent Pvid |
58 W
|
Heat dissipation per pole, current-dependent Pvid |
19.3 W
|
Number of phases |
3
|
Number of pilot lights |
1
|
Operating voltage - max. |
660 V
|
Operating voltage - min. |
42 V
|
Rated control supply voltage (Us) at DC - max |
32 V
|
Rated control supply voltage (Us) at DC - min |
5 V
|
Air discharge |
8 kV (according to IEC/EN 61000-4-2)
|
Altitude |
9
|
Burst Impulse |
Main: 2 kV, 5 kHz PC 1 (according to IEC/EN 61000-4-4)
Control: 1 kV, 5 kHz PC 1 (according to IEC/EN 61000-4-4) |
Climatic proofing |
95% relative humidity non-condensing at 40°C
|
Contact discharge |
4 kV (according to IEC/EN 61000-4-2)
|
Degree of protection |
IP20
|
Delay time |
1/2 period + 500 microseconds at 24 V DC
|
Electrical connection type of main circuit |
Screw connection
|
Electromagnetic fields |
10 V/m, 80 - 1000 MHz and 1.4 - 2.0 GHz, PC 1 (according to IEC/EN 61000-4-3)
10 V/m, 2.0 - 2.7 GHz, PC 1 (according to IEC/EN 61000-4-3) |
Features |
Modular version
|
Functions |
Switching at zero-crossing
|
Input current |
29.5 mA at 24 V DC
|
Mounting position |
Mount device in specified orientation and do not obstruct the heatsink
|
Pollution degree |
2
|
Radio interference class |
Class A
|
Overvoltage category |
III
|
Screwdriver size |
Main: Pozidriv 2
Control: Pozidriv 1 |
Shock resistance |
15/11 g/ms (according to EN 50155, EN 61373)
|
Tightening torque |
Main: 2 Nm (17.7 lb-in)
Control: 0.5 Nm (4.4 lb-in) |
Vibration resistance |
2 g/axis (2-100 Hz, IEC 60068-2-6, EN 50155, EN 61373)
|
Drop-out time |
< 20 ms
|
Drop-out voltage |
1 V DC
|
Electrical connection type for auxiliary- and control-current circuit |
Screw connection
|
Fitted with: |
LED indication
|
Immunity to line-conducted interference |
10 V/m, 0.15 - 80 MHz, PC 1 (according to IEC/EN 61000-4-6)
|
Pick-up voltage |
4.8 V DC
|
Rated impulse withstand voltage (Uimp) |
6 kV (1.2/50 μs)
|
Terminal capacity (flexible with ferrule) |
Main: 1 x 1-4 mm², 2 x 1-4 mm²
Control: 1 x 0.5-2.5 mm², 2 x 0.5-2.5 mm² |
Terminal capacity (solid) |
Main: 1 x 2.5-6 mm², 2 x 2.5-6 mm²
Control: 1 x 0.5-2.5 mm², 2 x 0.5-2.5 mm² |
Terminal capacity (solid/stranded AWG) |
Main: 1 x 14-10, 2 x 14-10
Control: 1 x 18-12, 2 x 18-12 |
Terminal capacity (stranded) |
Main: 1 x 2.5-6 mm², 2 x 2.5-6 mm²
Control: 1 x 0.5-2.5 mm², 2 x 0.5-2.5 mm² |
Rated conditional short-circuit current (Iq) (type 2 coordination) at 230 V |
100 kA, "FWP-32G22FI"
|
Rated conditional short-circuit current Iq (type 2 coordination) @ 380/400/415 V |
100 kA, "FWP-32G22FI"
|
Short-circuit current rating 600 Y/347 V, SCCR (UL/CSA) |
100 kA, 30A Class J or CC
|
Rated conditional short-circuit current (Iq) (type 1 coordination) at 230 V |
15 kA, "FAZ-C20/3"
|
Rated conditional short-circuit current Iq (type 1 coordination) @ 380/400/415 V |
15 kA, "FAZ-C20/3"
|
Model |
Other
|
Voltage type of operating voltage |
AC
|
Operating voltage at AC, 50 Hz - min |
42 V
|
Operating voltage at AC, 50 Hz - max |
600 V
|
Operating voltage at AC, 60 Hz - min |
42 V
|
Operating voltage at AC, 60 Hz - max |
600 V
|
Operating voltage at DC - min |
0 V
|
Operating voltage at DC - max |
0 V
|
Electric connection type |
Screw connection
|