Eaton DE1 Variable speed starter, Rated operational voltage 400 V AC, 3-phase, Ie 11.3 A, 5.5 kW, 7.5 HP, Radio interference suppression filter
Product Name |
Eaton DE1 Variable speed starter
|
Catalog Number |
174339
|
EAN |
4015081708017
|
Product Length/Depth |
169 mm
|
Product Height |
230 mm
|
Product Width |
90 mm
|
Product Weight |
1.6 kg
|
Certifications |
CSA-C22.2 No. 14
CUL RoHS, ISO 9001 Certified by UL for use in Canada IEC/EN61800-3 UL CE IEC/EN61800-5 RCM Safety requirements: IEC/EN 61800-5-1 IEC/EN 61800-3 UL 508C Specification for general requirements: IEC/EN 61800-2 UL Category Control No.: NMMS, NMMS7 UL File No.: E172143 UL report applies to both US and Canada |
Catalog Notes |
Overload cycle for 60 s every 600 s
|
Model Code |
DE1-34011FN-N20N
|
Features |
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus Parameterization: Keypad |
Fitted with: |
PC connection
Radio interference suppression filter |
Fitted with: |
PC connection
Radio interference suppression filter |
Cable length |
C3 ≤ 25 m, Radio interference level, maximum motor cable length
C2 ≤ 10 m, Radio interference level, maximum motor cable length |
Communication interface |
Modbus RTU, built in
OP-Bus (RS485), built in |
Connection to SmartWire-DT |
In conjunction with DX-NET-SWD3 SmartWire DT module
Yes |
Degree of protection |
IP20
NEMA Other |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Frame size |
FS2
|
Product category |
Variable speed starter
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
MODBUS
Other bus systems EtherNet/IP |
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms
|
Suitable for |
Branch circuits, (UL/CSA)
|
Vibration |
Resistance: According to EN 61800-5-1
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 2000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient operating temperature details |
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Input current ILN at 150% overload |
12 A
|
Leakage current at ground IPE - max |
< 3.5 mA (AC-operated)
< 10 mA (DC-operated) |
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
480 V
|
Operating mode |
U/f control
Speed control with slip compensation |
Output frequency - min |
0 Hz
|
Output frequency - max |
300 Hz
|
Output voltage (U2) |
480 V AC, 3-phase
400 V AC, 3-phase |
Overload current IL at 150% overload |
16.95 A
|
Rated control supply voltage |
10 V DC (Us, max. 0.2 mA)
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) |
11.3 A at 150% overload (at an operating frequency of 16 kHz and an ambient air temperature of +50 °C)
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
5.5 kW
|
Rated operational voltage |
400 V AC, 3-phase
480 V AC, 3-phase |
Resolution |
0.025 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
15 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 1.875 seconds every 600 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
16 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
Voltage rating - max |
480 V
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
11.3 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
11 A
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
7.5 HP
|
Apparent power at 400 V |
7.62 kVA
|
Apparent power at 480 V |
9.15 kVA
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Adjustable to 100 %, DC - Main circuit |
Number of inputs (analog) |
1 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
|
Number of inputs (digital) |
4 (parameterizable, 10 - 30 V DC)
|
Number of outputs (analog) |
0
|
Number of outputs (digital) |
0
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Equipment heat dissipation, current-dependent Pvid |
159 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
11.3 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|