Eaton DG1 Variable frequency drive, 400 V AC, 3-phase, 310 A, 160 kW, IP00, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
3-4917-101A
|
EAN |
4015081941728
|
Product Length/Depth |
561 mm
|
Product Height |
980 mm
|
Product Width |
506 mm
|
Product Weight |
205 kg
|
Certifications |
IEC/EN 61800-3
CE CUL RoHS, ISO 9001 C-Tick EAC Specification for general requirements: IEC/EN 61800-2 UkrSEPRO UL Category Control No.: NMMS, NMMS7 UL File No.: E134360 Safety requirements: IEC/EN 61800-5 UL |
Model Code |
DG1-34310FN-C00C
|
Features |
Temperature-controlled fan
Externally accessible fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
Air volume capacity |
1400 m³/h
|
Cable length |
50 m, screened, maximum permissible, Motor feeder
C2 ≤ 10 m, Radio interference level, maximum motor cable length C3 ≤ 50 m, Radio interference level, maximum motor cable length |
Degree of protection |
IP00
NEMA Other |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Environmental class |
3C2, 3S2 (Air quality)
|
Fitted with: |
Radio interference suppression filter
Multi-line graphic display IGBT inverter DC link choke Internal DC link Additional PCB protection Control unit PC connection |
Frame size |
FS7
|
Mounting position |
Vertical
|
Number of slots |
2 (expansion)
|
Overvoltage category |
III
|
Pollution degree |
2
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter, for conducted emissions only |
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Shock resistance |
UPS drop test (for weights inside the UPS frame)
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 Storage and transportation: maximum 15 g, 11 ms (inside the packaging) |
Suitable for |
Branch circuits, (UL/CSA)
|
Vibration |
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 |
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 1000 m Max. 3000 m Max. 2000 m for Corner Grounded TN Systems |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Efficiency |
97.9 % (η)
|
Heat dissipation at current/speed |
1277 W at 25% current and 0% speed
1373 W at 25% current and 50% speed 1732 W at 100% current and 50% speed 1931 W at 50% current and 50% speed 2164 W at 50% current and 90% speed 3106 W at 100% current and 0% speed 3558 W at 50% current and 0% speed 4143 W at 100% current and 90% speed |
Input current ILN at 110% overload |
385 A
|
Input current ILN at 150% overload |
311 A
|
Mains current distortion |
28 %
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
500 V
|
Operating mode |
Speed control with slip compensation
U/f control Sensorless vector control (SLV) Torque regulation |
Output frequency - min |
0 Hz
|
Output frequency - max |
400 Hz
|
Output voltage (U2) |
480 V AC, 3-phase
500 V AC, 3-phase 400 V AC, 3-phase |
Overload current IL at 110% overload |
423.5 A
|
Overload current IL at 150% overload |
465 A
|
Rated conditional short-circuit current (Iq) |
65 kA
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) at 110% overload |
385 A
|
Rated operational current (Ie) at 150% overload |
310 A
|
Rated operational power at 380/400 V, 50 Hz |
160 kW
|
Rated operational power at 380/400 V, 50 Hz, 110% overload |
200 kW
|
Rated operational power at 500 V, 50 Hz |
200 kW
|
Rated operational power at 500 V, 50 Hz, 110% overload |
250 kW
|
Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase 500 V AC, 3-phase |
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
500 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
2 kHz, 1.5 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Voltage rating - max |
500 VAC
|
Assigned motor current IM at 400 V, 50 Hz, 110% overload |
353 A
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
283 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
302 A
|
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
361 A
|
Assigned motor current IM at 500 V, 50 Hz, 110% overload |
349 A
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
279 A
|
Assigned motor power at 460/480 V, 60 Hz |
250 HP
|
Assigned motor power at 460/480 V, 60 Hz, 110% overload |
300 HP
|
Apparent power at 400 V |
266.7 kVA
|
Apparent power at 480 V |
333.4 kVA
|
Braking resistance |
1.4 Ω
|
Braking torque |
Adjustable to 150 %, DC - Main circuit
Max. 30 % MN, Standard - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Switch-on threshold for the braking transistor |
850 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
1
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Communication interface |
PROFIBUS, optional
Ethernet IP, built in Modbus RTU, built in Modbus TCP, built in SmartWire-DT, optional BACnet MS/TP, built in CANopen®, optional DeviceNet, optional |
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Protocol |
BACnet
CAN DeviceNet EtherNet/IP MODBUS Other bus systems PROFIBUS PROFINET IO TCP/IP |
Equipment heat dissipation, current-dependent Pvid |
5465 W
|
Rated operational current for specified heat dissipation (In) |
310 A
|
Static heat dissipation, non-current-dependent Pvs |
108 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|