Eaton DG1 Variable frequency drive, 500 V AC, 3-phase, 125 A, 75 kW, IP21/NEMA1, Brake chopper, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
9703-5010-00P
|
EAN |
4015081772247
|
Product Length/Depth |
340.7 mm
|
Product Height |
888.5 mm
|
Product Width |
288 mm
|
Product Weight |
76.2 kg
|
Certifications |
UL508
Safety requirements: IEC/EN 61800-5 UkrSEPRO IEC/EN 61800-3 RoHS, ISO 9001 EAC UL report applies to both US and Canada IEC/EN61800-3 CUL Specification for general requirements: IEC/EN 61800-2 UL File No.: E134360 UL CE Certified by UL for use in Canada IEC/EN61800-5 CSA-C22.2 No. 274-13 C-Tick UL Category Control No.: NMMS, NMMS7 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Model Code |
DG1-35125FB-C21C
|
Features |
Externally accessible fan
Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
Functions |
4-quadrant operation possible
|
Air volume capacity |
395 m³/h
|
Cable length |
C3 ≤ 10 m, Radio interference level, maximum motor cable length
200 m, screened, maximum permissible, Motor feeder |
Degree of protection |
NEMA 1
IP21 |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Environmental class |
3C2, 3S2 (Air quality)
|
Fitted with: |
Internal DC link
Additional PCB protection Multi-line graphic display DC link choke Radio interference suppression filter Brake chopper IGBT inverter Control unit PC connection Breaking resistance |
Frame size |
FS5
|
Mounting position |
Vertical
|
Number of slots |
2 (expansion)
|
Overvoltage category |
III
|
Pollution degree |
2
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter, for conducted emissions only |
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Shock resistance |
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
Storage and transportation: maximum 15 g, 11 ms (inside the packaging) UPS drop test (for weights inside the UPS frame) |
Suitable for |
Branch circuits, (UL/CSA)
|
Vibration |
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude |
Altitude |
Max. 2000 m
Max. 1000 m Above 1000 m with 1 % derating per 100 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-30 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Efficiency |
98.6 % (η)
|
Heat dissipation at current/speed |
1190 W at 100% current and 0% speed
1425 W at 50% current and 0% speed 1606 W at 100% current and 90% speed 430 W at 25% current and 0% speed 517 W at 25% current and 50% speed 663 W at 100% current and 50% speed 794 W at 50% current and 50% speed 868 W at 50% current and 90% speed |
Input current ILN at 110% overload |
132.9 A
|
Input current ILN at 150% overload |
116.2 A
|
Leakage current at ground IPE - max |
11.2 mA
|
Mains current distortion |
28.4 %
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage - min |
525 V
|
Mains voltage - max |
600 V
|
Operating mode |
U/f control
Sensorless vector control (SLV) Torque regulation Speed control with slip compensation |
Output frequency - min |
0 Hz
|
Output frequency - max |
400 Hz
|
Output voltage (U2) |
600 V AC, 3-phase
|
Overload current IL at 110% overload |
158.4 A
|
Overload current IL at 150% overload |
187.5 A
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) at 110% overload |
144 A
|
Rated operational current (Ie) at 150% overload |
125 A
|
Rated operational voltage |
600 V AC, 3-phase
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
200 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
1.5 kHz, 1 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Voltage rating - max |
600 VAC
|
Assigned motor current IM at 525 V, 50 Hz, 110% overload |
129 A
|
Assigned motor current IM at 525 V, 50 Hz, 150% overload |
107 A
|
Assigned motor current IM at 600 V, 50 Hz, 110% overload |
137 A
|
Assigned motor current IM at 600 V, 50 Hz, 150% overload |
112 A
|
Apparent power at 600 V |
149.6 kVA
|
Braking resistance |
7 Ω
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit Adjustable to 150 %, DC - Main circuit |
Switch-on threshold for the braking transistor |
1050 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
1
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Communication interface |
BACnet MS/TP, built in
PROFIBUS, optional SmartWire-DT, optional Modbus RTU, built in Modbus TCP, built in Ethernet IP, built in CANopen®, optional DeviceNet, optional |
Connection to SmartWire-DT |
In conjunction with DXG-NET-SWD SmartWire DT module
Yes |
Protocol |
PROFIBUS
TCP/IP CAN MODBUS DeviceNet PROFINET IO Other bus systems BACnet EtherNet/IP |
Equipment heat dissipation, current-dependent Pvid |
1627 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
125 A
|
Static heat dissipation, non-current-dependent Pvs |
27.23 W
|
Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|