Eaton DC1 Variable frequency drive, 115 V AC, single-phase, 2.3 A, 0.37 kW, IP66/NEMA 4X, 7-digital display assembly, Local controls, Additional PCB protection, UV resistant, FS1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
199394
|
EAN |
4015081977833
|
Product Length/Depth |
162 mm
|
Product Height |
232 mm
|
Product Width |
161 mm
|
Product Weight |
2.5 kg
|
Certifications |
CE marking
EAC RCM CSA-C22.2 No. 14 UL 508C UL Category Control No.: NMMS, NMMS7 UL Listed UL File No.: E172143 IEC/EN61800-5 CUL Certified by UL for use in Canada RoHS, ISO 9001 IEC/EN 61800-5-1 UL CE UL report applies to both US and Canada IEC/EN 61800-2 UkrSEPRO IEC/EN 61800-3 |
Features |
Parameterization: drivesConnect mobile (App)
Parameterization: drivesConnect Parameterization: Fieldbus Parameterization: Keypad |
Fitted with: |
Internal DC link
PC connection Additional PCB protection UV resistance 7-digital display assembly Control unit Local controls IGBT inverter |
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
No
|
Operating mode |
Speed control with slip compensation
Synchronous reluctance motors U/f control BLDC motors PM motors Sensorless vector control (SLV) |
Frame size |
FS1
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m |
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-20 °C
|
Mains voltage - max |
115 V
|
Output voltage - max |
250 V
|
Rated operational power at 220/230 V, 50 Hz, 3-phase |
0.37 kW
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Ambient storage temperature - max |
60 °C
|
Ambient storage temperature - min |
-40 °C
|
Application in industrial area permitted |
Yes
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Voltage rating - max |
120 V
|
Mounting position |
Vertical
|
Communication interface |
OP-Bus (RS485), built in
SmartWire-DT, optional Modbus RTU, built in CANopen®, built in |
Converter type |
U converter
|
Degree of protection |
IP66
NEMA 4X |
Assigned motor power at 230/240 V, 60 Hz, 3-phase |
0.5 HP
|
Input current ILN at 150% overload |
7.8 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
2 A
|
Protocol |
EtherNet/IP
MODBUS CAN Other bus systems |
Overload current IL at 150% overload |
3.45 A
|
Rated frequency - max |
62 Hz
|
Rated frequency - min |
48 Hz
|
System configuration type |
AC supply systems with earthed center point
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie, variable, DC - Main circuit |
Cable length |
150 m, unscreened, with motor choke, maximum permissible, Motor feeder
100 m, screened, with motor choke, maximum permissible, Motor feeder 75 m, unscreened, maximum permissible, Motor feeder 50 m, screened, maximum permissible, Motor feeder |
Output voltage (U2) |
230 V AC, 3-phase
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
4
|
Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
|
Number of outputs (digital) |
1
|
Starting current - max |
175 % IH
|
Number of phases (input) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Number of phases (output) |
3
|
Power consumption |
18.5 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
97 % (η)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
4.8 mA
|
Mains voltage - min |
110 V
|
Nominal output current I2N |
2.3 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
0.37 kW
|
Output at quadratic load at rated output voltage - max |
0.37 kW
|
Output frequency - max |
500 Hz
|
Output frequency - min |
0 Hz
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
Rated operational current (Ie) |
2.3 A at 150% overload (at an operating frequency of 6 kHz and an ambient air temperature of +40 °C)
|
Rated operational voltage |
115 V AC, 1-phase
|
Short-circuit protection rating |
15 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|